Trane Rtaaiom3 Manual
Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
71RTAA-IOM-3 Alarm/Running/Maximum Capacity Indicator Wiring If the optional remote Alarm/Running/ Maximum Capacity contacts are used, provide electrical power, 115 VAC (contact load not to exceed 1150 VA inrush, 115 VA sealed), with fused- disconnect to a customer-furnished remote device. Also provide proper remote device ground connection. To install the available remote running and alarm indication, the installer must provide leads 525 thru 532 from the panel to the proper terminals of terminal strip 1U1TB4 on the UCM, as shown in Figures 31 thru 32. Refer to the field diagrams which are shipped with the unit. Low Voltage Wiring The remote devices described below require low voltage wiring. All wiring to and from these remote input devices to the UCM must be made with shielded, twisted pair conductors. Be sure to ground the shielding only at the UCM. See Figures 34 thru 36 for the recommended conductor sizes. Caution: To prevent control malfunctions, do not run low voltage wiring (
72RTAA-IOM-3 External Chilled Water Setpoint (CWS): Remote Resistor/Potentiometer, Voltage Source 2-10 VDC, or Current Source 4-20 mA This option allows the external setting of the Chilled Water Setpoint, independent of the Front Panel Chilled Water Setpoint, by one of three means: 1. A remote resistor/potentiometer input (fixed or adjustable)2. An isolated voltage input 2-10 VDC 3. An isolated current loop input 4-20 mA Methods 2 and 3 are usually used in interfacing with a Generic BAS or a process controller to the chiller. To enable external setpoint operation, Item 30 of Menu 3, “External Chilled Water Setpoint d/E”, should be set to “E” using the Front Panel Operator Interface.1. Remote Resistor/Potentiometer Input (fixed or adjustable) Connect the remote resistor and/or potentiometer to terminals TB1 -3 and TB1 -5 of Options Module 1U2, as shown in Figure 38. For units with 40 F to 60 F LCWS range, a field-furnished 25 Kohm linear taper potentiometer (±10%) and a fixed 5.6 Kohm (±10%) 1/4 watt resistor should be used. For units with 20 F to 39 F LCWS range, a field-furnished 25 Kohm linear taper potentiometer (±1 0%) and a fixed 15 Kohm (±1 0%) 1/4 watt resistor should be used. If the potentiometer is to be remotely mounted, it and the resistor must be connected to the UCM prior to mounting. Then, with the UCM display in Menu 0 and the display advanced to “Active Chilled Water Setpoint”, the UCM can be used to calibrate the positions of the potentiometer to correspond with the desired settings for the leaving water temperature. External resistor input values for various chilled water setpoints are shown in Table 13. Table 13 Input Values Vs. External Chilled Water Setpoint InputsResulting Chilled Resistance (Ohms) Current (mA) Voltage (Vdc) Water Setpoint (F) 94433 4.0 2.0 0.0 68609 5.2 2.6 5.0 52946 6.5 3.2 10.0 42434 7.7 3.9 15.0 34889 8.9 4.5 20.0 29212 10.2 5.1 25.0 24785 11.4 5.7 30.0 21236 12.6 6.3 35.0 18327 13.8 6.9 40.0 15900 15.1 7.6 45.0 13844 16.3 8.2 50.0 12080 17.5 8.8 55.0 10549 18.8 9.4 60.0 9050 20.0 10.0 65.0 Figure 38 Resistor and Potentiometer Arrangement for External Chilled Water Setpoint
73RTAA-IOM-3 2. Isolated 2-10 VDC Voltage Source Input Set DIP Switch SW1-1 of Options Module 1U2 to “OFF”. Connect the voltage source to terminals TB1 -4 (+) and TB1 -5 (-) on Options Module 1U2. CWS is now based on the following equation: CW Setpoint 0 F = (VDC x 8.125) - 16.25 Sample values for CWS vs. VDC signals are shown in Table 13. Minimum setpoint = 0 F (2.0 VDC input) Maximum setpoint = 65 F (9.4 VDC input) Maximum continuous input voltage = 15 VDC Input impedance = 40.1 Kohms SW1 -1 off) 3. Isolated 4-20 mA Current Source Input Set DIP Switch SW1-1 of Options Module 1U2 to “ON”. Connect the current source to terminals TB1-4 (+)and TB1-5 (-). CWS is now based on the following equation: Setpoint °F = (mA x 4.0625) - 16.25 Sample values for CWS vs. mA signals are shown in Table 13. Minimum setpoint = 0 F (4.0 mA) Maximum setpoint = 65 F (18.8 mA) Maximum continuous = 30 mA input current Input impedance = 499 ohms SW1 -1 on) Note: The negative terminal TB1 -5 is referenced to the UCM chassis ground. To assure correct operation, 2-10 VDC or 4-20 mA signals must be isolated or “floating” with respect to the UCM chassis ground. See Figures 34 thru 36.External Current Limit Setpoint (CLS): Remote Resistor/ Potentiometer, Voltage Source 2-10 VDC or Current Source 4-20 mA This option allows the external setting of the Current Limit Setpoint, independent of the Front Panel Current Limit Setpoint, by one of three means: 1. A remote resistor/potentiometer input (fixed or adjustable) 2. An isolated voltage input 2-10 VDC 3. An isolated current loop input 4-20 mA Methods 2 and 3 are usually used in interfacing with a Generic BAS.To enable external Current Limit Setpoint operation, Item 31 of Menu 3, “External Current Limit Setpoint WE”, should be set to “E” using the Front Panel Operator Interface. 1. Remote Resistor/Potentiometer Input To cover the entire range of Current Limit Setpoints; (40 to 120%), a field furnished 50 Kohm log taper potentiometer (±10%) and a fixed 820 ohm (±1 0%) 1/4 Waft resistor should be wired in series and connected to terminals TB1 -6 and TB1 -8, of options module 1U2, as shown in Figure 39. Table 14 Input Values Vs. External Current Limit Setpoint InputsResulting Current Resistance (Ohms) Current (mA) Voltage (Vdc) Limit Setpoint (% RLA) 49000 4.0 2.0 40 29000 6.0 3.0 50 19000 8.0 4.0 60 13000 10.0 5.0 70 9000 12.0 6.0 80 6143 14.0 7.0 90 4010 16.0 8.0 100 2333 18.0 9.0 110 1000 20.0 10.0 120 Figure 39 Resistor and Potentiometer Arrangement for External Current Limit Setpoint
74RTAA-IOM-3 If the potentiometer is to be remotely mounted, it and the resistor must be connected to the UCM prior to mounting. Then, with the UCM display in Menu 0 and the display advanced to “Active Current Limit Setpoint”, the UCM can be used to calibrate the positions of the potentiometer to correspond with the desired settings for the current limits. External resistor input values for various current limit setpoints are shown in Table 14. 2. 2-10 VDC Voltage Source Input Set DIP Switch SW1-2 of Options Module 1U2 to “OFF”. Connect the voltage source to terminals TB1 -7 (+) and TB1 -8 (-) of Options Module 1U2. CLS is now based on the following equation: CL Setpoint % = (VDC x 10) + 20 Sample values for CLS vs. VDC signals are shown below: Minimum setpoint = 40% (2.0 VDC input) Maximum setpoint = 120% (10.0 VDC input) Maximum continuous input voltage = 15 VDC Input impedance = 40.1 Kohms (SW1 -2 off)3. 4-20 mA Current Source Input Set DIP Switch SW1-2 of Options Module 1U2 to “ON”. Connect the current source to terminals TB1 -7 (+) and TB1 -8 (-) of Options Module 1U2. CLS is now based on the following equation: CL Setpoint % = (mA x 5) + 20 Sample values for CLS vs. mA signals are shown in Table 14. Minimum setpoint = 40% (4.0 mA) Maximum setpoint = 120% (20.0 mA) Maximum continuous input current = 30 mA Input impedance = 499 ohms (SW1 - 2 on) Note: The negative terminal TB1 -8 is referenced to the UCM chassis ground. To assure correct operation, 2-10 VDC or 4-20 mA signals must be isolated or “floating” with respect to the UCM chassis ground. See Figures 31 thru 32. Optional Bidirectional Communications Link (BCL) This option allows the UCM in the control panel to exchange information (e.g. operating setpoints and Auto/ Standby commands) with a higher level control device, such as a Tracer, a multiple-machine controller or a remote display panel. A shielded, twisted-pair connection establishes the bidirectional communications link between the unit control panel and the Tracer, multiple-machine controller or remote display panel. Note: The shielded, twisted-pair conductors must run in a separate conduit. Caution: To prevent control malfunctions, do not run low voltage wiring (
75RTAA-IOM-3 Installation Check List Complete this checklist as the unit is installed, to verify that all recommended procedures are accomplished before the unit is started. This checklist does not replace the detailed Instructions given in the “Installation -Mechanical” and “Installation -Electrical” sections of this manual. Read both sections completely, to become familiar with the installation procedures, prior to beginning the work. Receiving [ ] Verify that the unit nameplate data corresponds to the ordering information. [ ] Inspect the unit for shipping damage and any shortages of materials. Report any damage or shortage to the carder. Unit Location and Mounting [ ] Inspect the location desired for installation and verify adequate service access clearances. [ ] Provide drainage for evaporator water. [ ] Remove and discard all shipping materials (cartons, etc.) [ ] Install optional spring isolators, if required. [ ] Level the unit and secure it to the mounting surface. Unit Piping [ ] Flush all unit water piping before making final connections to the unit. Caution: If using an acidic commercial flushing solution, construct a temporary bypass around the unit to prevent damage to internal components of the evaporator. Caution: To avoid possible equipment damage, do not use untreated or improperly treated system water. [ ] Connect the chilled water piping to the evaporator. [ ] Install pressure gauges and shutoff valves on the chilled water inlet and outlet to the evaporator. [ ] Install a water strainer in the entering chilled water line. [ ] Install a balancing valve and flow switch (discretionary) in the leaving chilled water line. [ ] Install a drain with shutoff valve or a drain plug on the evaporator. [ ] Vent the chilled water system at high points in the system piping. [ ] Apply heat tape and insulation, as necessary, to protect all exposed piping from freeze-up. Electrical Wiring WARNING: To prevent injury or death, disconnect electrical power source before completing wiring connections to the unit. Caution: To avoid corrosion and overheating at terminal connections, use copper conductors only. [ ] Connect the unit power supply wiring with fused-disconnect to the terminal block (or unit-mounted disconnect) in the power section of the control panel. [ ] Connect the control power supply wiring with fused-disconnect to the terminal strip in the power section of the control panel. [ ] Connect power supply wiring to the evaporator heat tape. Connect leads 551 and 552 to terminals 11 and 12 of terminal strip 1TB3. [ ] Connect power supply wiring to the chilled water pump. [ ] Connect power supply wiring to any auxiliary heat tapes. [ ] Connect the auxiliary contact of the chilled water pump (5K1) in series with the optional flow switch, if installed, and then connect to the proper terminals. [ ] For the External Start/Stop function, install wiring from remote contacts (5K5, 5K21) to the proper terminals on terminal strip 1U1TB3. Caution: Information in Interconnecting Wiring: Chilled Water Pump Interlock and External Auto/Stop must be adhered to or equipment damage may occur. [ ] If the remote alarm/running/ maximum capacity contacts are used, install leads 525 thru 532 from the panel to the proper terminals on terminal strip 1U1TB4. [ ] If the emergency stop function is used, install low voltage leads 513 and 514 to terminals 3 and 4 of 1U1TB1. [ ] If indoor zone temperature is to be used, install leads 501 and 502 on 6RT4 to the proper terminals on 1U2TB1. [ ] If the ice making-option is used, install leads 501 and 502 on 5K20 to the proper terminals on 1U2TB1.
77RTAA-IOM-3 Operating Principles – Mechanical General This section describes the mechanical operating principles of Series R air- cooled chillers equipped with microcomputer-based control systems. The 130 thru 400-ton Model RTAA units are dual-circuited, helical-rotary type air-cooled liquid chillers. The basic components of an RTAA unit are: - Unit Control Module (UCM) - Unit-mounted panel - Helical-rotary compressor - Direct Expansion evaporator - Air-cooled condenser - Oil supply system (hydraulic and lubrication) - Interconnecting piping Components of a typical RTAA unit are identified in Figures 1 thru 6. Refrigeration (Cooling) Cycle Cycle Description Figures 40 and 41 represent the refrigeration system and control components. Vaporized refrigerant leaves the evaporator and is drawn into the compressor. Here it is compressed and leaves the compressor as a mixture of hot gas and oil (which was injected during the compression cycle). The mixture enters the oil separator at the two in/out caps. The separated oil flows to the bottom of the separator, while the refrigerant gas flows out the top and passes on to the tubes in the condensing coils. Here circulating air removes heat from the refrigerant and condenses it. The condensed refrigerant passes through the electronic expansion valve and into the tubes of the evaporator. As the refrigerant vaporizes, it cools the system water that surrounds the tubes in the evaporator. Compressor Description The compressors used by the Model RTAA Series “R” Air-cooled chiller consists of two distinct components: the motor and the rotors. Refer to Figure 42. Compressor Motor A two-pole, hermetic, squirrel-cage induction motor directly drives the compressor rotors. The motor is cooled by suction refrigerant gas from the evaporator, entering the end of the motor housing through the suction line, as shown in Figures 40 and 41. Compressor Rotors The compressor is a semi-hermetic, direct drive helical rotary type compressor. Each compressor has only three moving parts: Two rotors - “male” and ‘female” - provide compression, and a slide valve controls capacity. See Figure 42. The male rotor is attached to, and driven by, the motor, and the female rotor is, in turn, driven by the male rotor. Separately housed bearing sets are provided at each end of both rotors. The slide valve is located above, and moves along, the top of the rotors. The helical rotary compressor is a positive displacement device. The refrigerant from the evaporator is drawn into the suction opening at the end of the motor barrel, through a suction strainer screen, across the motor, and into the intake of the compressor rotor section. The gas is then compressed and discharged directly into the discharge line. There is no physical contact between the rotors and compressor housing. The rotors contact each other at the point where the driving action between the male and female rotors occurs. Oil is injected along the top of the compressor rotor section, coating both rotors and the compressor housing interior. Although this oil does provide rotor lubrication, its primary purpose is to seal the clearance spaces between the rotors and compressor housing. A positive seal between these internal parts enhances compressor efficiency by limiting leakage between the high pressure and low pressure cavities.Capacity control is accomplished by means of a slide valve assembly located in the rotor section of the compressor. Positioned along the top of the rotors, the slide valve is driven by a piston/cylinder along an axis that parallels those of the rotors. Compressor load condition is dictated by the position of the slide valve over the rotors. When the slide valve is fully extended over the rotors and away from the discharge end, the compressor is fully loaded. Unloading occurs as the slide valve is drawn towards the discharge end. Slide valve unloading lowers refrigeration capacity by reducing the compression surface of the rotors. Compressor Loading Sequence When there is a call for chilled water, the UCM will start the compressor which has the least number of starts. If the first compressor cannot satisfy the demand, the UCM will start another compressor and then balance the load on all compressors by pulsing the load/ unload solenoids. The load on the compressors will be kept in balance, as load fluctuates, until the demand for chilled water is reduced to a level that can be handled by one compressor. At this time, the UCM will drop off the compressor that has the greatest number of operating hours and will adjust the load on the other compressor, as required.
78RTAA-IOM-3 Figure 40 Refrigeration System and Control Components Single Circuit(Continued on Next Page)
79RTAA-IOM-3 Figure 40 (Continued from Previous Page) 1 Schrader valve 2 Suction temperature sensor* 3 Manufacturing process tube 4 Suction service valve (optional) 5 Motor winding thermostat* 6 Discharge temperature sensor* 7 Pressure relief valve (450 psi) 8 High pressure cutout (405 psi)* 9 Discharge check valve 10 Evaporator waterside vent 11 Discharge line shutoff valve 12 Oil separator in/out cap 13 Saturated condensing temperature sensor* 14 Condenser header 15 Subcooler header 16 Liquid line shutoff valve17 25 micron filter/drier 18 Liquid line sight glass 19 Electronic expansion valve 20 Saturated evaporator temperature sensor* 21 Evaporator waterside drain 22 Leaving water temperature sensor* 23 Leaving water connection 24 Entering water connection 25 Entering water temperature sensor* 26 Drain with Schrader valve 27 Oil line 28 Entering oil cooler header 29 Leaving oil cooler header 30 Schrader valve with stem depressor 31 Oil line shutoff valve 32 5 micron oil filter33 Master solenoid valve* 34 Oil line to load/unload slide valve solenoids 35 Injection oil check valve 36 Heater 37 Slide valve solenoids and orifices* 38 Oil flow differential pressure switch* 39 Compressor Drain Plug 40 Domestic water heater (option) 41 Oil line thermostat (option, Domestic Water Heater) 42 Oil line bypass solenoid valve (option, Domestic Water Heater) *UCM Input/Output Control
80RTAA-IOM-3 Figure 41 Refrigeration System and Control Components Duplex Circuit(Continued on Next Page)