Home > Trane > Cooler > Trane Rtaaiom3 Manual

Trane Rtaaiom3 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							71RTAA-IOM-3
    Alarm/Running/Maximum
    Capacity Indicator Wiring
    If the optional remote Alarm/Running/
    Maximum Capacity contacts are used,
    provide electrical power, 115 VAC
    (contact load not to exceed 1150 VA
    inrush, 115 VA sealed), with fused-
    disconnect to a customer-furnished
    remote device. Also provide proper
    remote device ground connection.
    To install the available remote running
    and alarm indication, the installer must
    provide leads 525 thru 532 from the
    panel to the proper terminals of
    terminal strip 1U1TB4 on the UCM, as
    shown in Figures 31 thru 32. Refer to
    the field diagrams which are shipped
    with the unit.
    Low Voltage Wiring
    The remote devices described below
    require low voltage wiring. All wiring to
    and from these remote input devices to
    the UCM must be made with shielded,
    twisted pair conductors. Be sure to
    ground the shielding only at the UCM.
    See Figures 34 thru 36 for the
    recommended conductor sizes.
    Caution: To prevent control
    malfunctions, do not run low
    voltage wiring (
    						
    							72RTAA-IOM-3
    External Chilled Water
    Setpoint (CWS):
    Remote Resistor/Potentiometer,
    Voltage Source 2-10 VDC, or
    Current Source 4-20 mA
    This option allows the external setting
    of the Chilled Water Setpoint,
    independent of the Front Panel Chilled
    Water Setpoint, by one of three means:
    1. A remote resistor/potentiometer
    input (fixed or adjustable)2. An isolated voltage input 2-10 VDC
    3. An isolated current loop input
    4-20 mA
    Methods 2 and 3 are usually used in
    interfacing with a Generic BAS or a
    process controller to the chiller.
    To enable external setpoint operation,
    Item 30 of Menu 3, “External Chilled
    Water Setpoint d/E”, should be set to
    “E” using the Front Panel Operator
    Interface.1. Remote Resistor/Potentiometer Input
    (fixed or adjustable)
    Connect the remote resistor and/or
    potentiometer to terminals TB1 -3
    and TB1 -5 of Options Module 1U2,
    as shown in Figure 38.
    For units with 40 F to 60 F LCWS
    range, a field-furnished 25 Kohm
    linear taper potentiometer (±10%)
    and a fixed 5.6 Kohm (±10%) 1/4 watt
    resistor should be used.
    For units with 20 F to 39 F LCWS
    range, a field-furnished 25 Kohm
    linear taper potentiometer (±1 0%)
    and a fixed 15 Kohm (±1 0%) 1/4 watt
    resistor should be used.
    If the potentiometer is to be remotely
    mounted, it and the resistor must be
    connected to the UCM prior to
    mounting. Then, with the UCM
    display in Menu 0 and the display
    advanced to “Active Chilled Water
    Setpoint”, the UCM can be used to
    calibrate the positions of the
    potentiometer to correspond with
    the desired settings for the leaving
    water temperature. External resistor
    input values for various chilled water
    setpoints are shown in Table 13.
    Table 13
    Input Values Vs. External Chilled Water Setpoint
    InputsResulting Chilled
    Resistance (Ohms) Current (mA) Voltage (Vdc) Water Setpoint (F)
    94433 4.0 2.0 0.0
    68609 5.2 2.6 5.0
    52946 6.5 3.2 10.0
    42434 7.7 3.9 15.0
    34889 8.9 4.5 20.0
    29212 10.2 5.1 25.0
    24785 11.4 5.7 30.0
    21236 12.6 6.3 35.0
    18327 13.8 6.9 40.0
    15900 15.1 7.6 45.0
    13844 16.3 8.2 50.0
    12080 17.5 8.8 55.0
    10549 18.8 9.4 60.0
    9050 20.0 10.0 65.0
    Figure 38
    Resistor and Potentiometer
    Arrangement for External Chilled
    Water Setpoint 
    						
    							73RTAA-IOM-3
    2. Isolated 2-10 VDC Voltage Source
    Input
    Set DIP Switch SW1-1 of Options
    Module 1U2 to “OFF”. Connect the
    voltage source to terminals TB1 -4 (+)
    and TB1 -5 (-) on Options Module
    1U2. CWS is now based on the
    following equation:
    CW Setpoint 0 F = (VDC x 8.125) -
    16.25
    Sample values for CWS vs. VDC
    signals are shown in Table 13.
    Minimum setpoint
    = 0 F (2.0 VDC input)
    Maximum setpoint
    = 65 F (9.4 VDC input)
    Maximum continuous input voltage
    = 15 VDC
    Input impedance = 40.1 Kohms
    SW1 -1 off)
    3. Isolated 4-20 mA Current Source
    Input
    Set DIP Switch SW1-1 of Options
    Module 1U2 to “ON”. Connect the
    current source to terminals TB1-4
    (+)and TB1-5 (-). CWS is now based
    on the following equation:
    Setpoint °F = (mA x 4.0625) - 16.25
    Sample values for CWS vs. mA
    signals are shown in Table 13.
    Minimum setpoint = 0 F (4.0 mA)
    Maximum setpoint = 65 F (18.8 mA)
    Maximum continuous = 30 mA
    input current
    Input impedance = 499 ohms
    SW1 -1 on)
    Note: The negative terminal TB1 -5 is
    referenced to the UCM chassis ground.
    To assure correct operation, 2-10 VDC
    or 4-20 mA signals must be isolated or
    “floating” with respect to the UCM
    chassis ground. See Figures 34 thru 36.External Current Limit Setpoint
    (CLS): Remote Resistor/
    Potentiometer, Voltage Source 2-10
    VDC or Current Source 4-20 mA
    This option allows the external setting
    of the Current Limit Setpoint,
    independent of the Front Panel Current
    Limit Setpoint, by one of three means:
    1. A remote resistor/potentiometer
    input (fixed or adjustable)
    2. An isolated voltage input 2-10 VDC
    3. An isolated current loop input 4-20
    mA
    Methods 2 and 3 are usually used in
    interfacing with a Generic BAS.To enable external Current Limit
    Setpoint operation, Item 31 of Menu 3,
    “External Current Limit Setpoint WE”,
    should be set to “E” using the Front
    Panel Operator Interface.
    1. Remote Resistor/Potentiometer Input
     To cover the entire range of Current
    Limit Setpoints; (40 to 120%), a field
    furnished 50 Kohm log taper
    potentiometer (±10%) and a fixed
    820 ohm (±1 0%) 1/4 Waft resistor
    should be wired in series and
    connected to terminals TB1 -6 and
    TB1 -8, of options module 1U2, as
    shown in Figure 39.
    Table 14
    Input Values Vs. External Current Limit Setpoint
    InputsResulting Current
    Resistance  (Ohms) Current (mA) Voltage (Vdc) Limit Setpoint (% RLA)
    49000 4.0 2.0 40
    29000 6.0 3.0 50
    19000 8.0 4.0 60
    13000 10.0 5.0 70
    9000 12.0 6.0 80
    6143 14.0 7.0 90
    4010 16.0 8.0 100
    2333 18.0 9.0 110
    1000 20.0 10.0 120
    Figure 39
    Resistor and Potentiometer
    Arrangement for External
    Current Limit Setpoint 
    						
    							74RTAA-IOM-3
    If the potentiometer is to be remotely
    mounted, it and the resistor must be
    connected to the UCM prior to
    mounting. Then, with the UCM display
    in Menu 0 and the display advanced to
    “Active Current Limit Setpoint”, the
    UCM can be used to calibrate the
    positions of the potentiometer to
    correspond with the desired settings
    for the current limits. External resistor
    input values for various current limit
    setpoints are shown in Table 14.
    2. 2-10 VDC Voltage Source Input
    Set DIP Switch SW1-2 of Options
    Module 1U2 to “OFF”. Connect the
    voltage source to terminals TB1 -7 (+)
    and TB1 -8 (-) of Options
    Module 1U2. CLS is now based on the
    following equation:
    CL Setpoint % = (VDC x 10) + 20
    Sample values for CLS vs. VDC signals
    are shown below:
    Minimum setpoint
    = 40% (2.0 VDC input)
    Maximum setpoint
    = 120% (10.0 VDC input)
    Maximum continuous input voltage
    = 15 VDC
    Input impedance = 40.1 Kohms
    (SW1 -2 off)3. 4-20 mA Current Source Input
    Set DIP Switch SW1-2 of Options
    Module 1U2 to “ON”. Connect the
    current source to terminals TB1 -7 (+)
    and TB1 -8 (-) of Options Module 1U2.
    CLS is now based on the following
    equation:
    CL Setpoint % = (mA x 5) + 20
    Sample values for CLS vs. mA signals
    are shown in Table 14.
    Minimum setpoint = 40% (4.0 mA)
    Maximum setpoint = 120% (20.0 mA)
    Maximum continuous input current
    = 30 mA
    Input impedance = 499 ohms
    (SW1 - 2 on)
    Note: The negative terminal TB1 -8 is
    referenced to the UCM chassis ground.
    To assure correct operation, 2-10 VDC
    or 4-20 mA signals must be isolated or
    “floating” with respect to the UCM
    chassis ground. See Figures 31 thru 32.
    Optional Bidirectional
    Communications Link (BCL)
    This option allows the UCM in the
    control panel to exchange information
    (e.g. operating setpoints and Auto/
    Standby commands) with a higher
    level control device, such as a Tracer, a
    multiple-machine controller or a
    remote display panel. A shielded,
    twisted-pair connection establishes the
    bidirectional communications link
    between the unit control panel and the
    Tracer, multiple-machine controller or
    remote display panel.
    Note: The shielded, twisted-pair
    conductors must run in a separate
    conduit.
    Caution: To prevent control
    malfunctions, do not run low
    voltage wiring (
    						
    							75RTAA-IOM-3
    Installation Check List
    Complete this checklist as the unit is
    installed, to verify that all
    recommended procedures are
    accomplished before the unit is started.
    This checklist does not replace the
    detailed Instructions given in the
    “Installation -Mechanical” and
    “Installation -Electrical” sections of this
    manual. Read both sections
    completely, to become familiar with the
    installation procedures, prior to
    beginning the work.
    Receiving
    [  ] Verify that the unit nameplate data
    corresponds to the ordering
    information.
    [  ] Inspect the unit for shipping
    damage and any shortages of
    materials. Report any damage or
    shortage to the carder.
    Unit Location and Mounting
    [  ] Inspect the location desired for
    installation and verify adequate
    service access clearances.
    [  ] Provide drainage for evaporator
    water.
    [  ] Remove and discard all shipping
    materials (cartons, etc.)
    [  ] Install optional spring isolators, if
    required.
    [  ] Level the unit and secure it to the
    mounting surface.
    Unit Piping
    [  ] Flush all unit water piping before
    making final connections to the unit.
    Caution: If using an acidic
    commercial flushing solution,
    construct a temporary bypass
    around the unit to prevent damage
    to internal components of the
    evaporator.
    Caution: To avoid possible
    equipment damage, do not use
    untreated or improperly treated
    system water.
    [  ] Connect the chilled water piping to
    the evaporator.
    [  ] Install pressure gauges and shutoff
    valves on the chilled water inlet and
    outlet to the evaporator.
    [  ] Install a water strainer in the
    entering chilled water line.
    [  ] Install a balancing valve and flow
    switch (discretionary) in the leaving
    chilled water line.
    [  ] Install a drain with shutoff valve or a
    drain plug on the evaporator.
    [  ] Vent the chilled water system at
    high points in the system piping.
    [  ] Apply heat tape and insulation, as
    necessary, to protect all exposed
    piping from freeze-up.
    Electrical Wiring
    WARNING: To prevent injury or
    death, disconnect electrical
    power source before completing
    wiring connections to the unit.
    Caution: To avoid corrosion and
    overheating at terminal
    connections, use copper
    conductors only.
    [  ] Connect the unit power supply
    wiring with fused-disconnect to the
    terminal block (or unit-mounted
    disconnect) in the power section of
    the control panel.
    [  ] Connect the control power supply
    wiring with fused-disconnect to the
    terminal strip in the power section
    of the control panel.
    [  ] Connect power supply wiring to the
    evaporator heat tape. Connect leads
    551 and 552 to terminals 11 and 12
    of terminal strip 1TB3.
    [  ] Connect power supply wiring to the
    chilled water pump.
    [  ] Connect power supply wiring to any
    auxiliary heat tapes.
    [  ] Connect the auxiliary contact of the
    chilled water pump (5K1) in series
    with the optional flow switch, if
    installed, and then connect to the
    proper terminals.
    [  ] For the External Start/Stop function,
    install wiring from remote contacts
    (5K5, 5K21) to the proper terminals
    on terminal strip 1U1TB3.
    Caution: Information in
    Interconnecting Wiring: Chilled
    Water Pump Interlock and External
    Auto/Stop must be adhered to or
    equipment damage may occur.
    [  ] If the remote alarm/running/
    maximum capacity contacts are
    used, install leads 525 thru 532 from
    the panel to the proper terminals on
    terminal strip 1U1TB4.
    [  ] If the emergency stop function is
    used, install low voltage leads 513
    and 514 to terminals 3 and 4 of
    1U1TB1.
    [  ] If indoor zone temperature is to be
    used, install leads 501 and 502 on
    6RT4 to the proper terminals on
    1U2TB1.
    [  ] If the ice making-option is used,
    install leads 501 and 502 on 5K20 to
    the proper terminals on 1U2TB1. 
    						
    							77RTAA-IOM-3
    Operating
    Principles –
    Mechanical
    General
    This section describes the mechanical
    operating principles of Series R air-
    cooled chillers equipped with
    microcomputer-based control systems.
    The 130 thru 400-ton Model RTAA units
    are dual-circuited, helical-rotary type
    air-cooled liquid chillers. The basic
    components of an RTAA unit are:
    - Unit Control Module (UCM)
    - Unit-mounted panel
    - Helical-rotary compressor
    - Direct Expansion evaporator
    - Air-cooled condenser
    - Oil supply system (hydraulic and
      lubrication)
    - Interconnecting piping
    Components of a typical RTAA unit are
    identified in Figures 1 thru 6.
    Refrigeration
    (Cooling) Cycle
    Cycle Description
    Figures 40 and 41 represent the
    refrigeration system and control
    components. Vaporized refrigerant
    leaves the evaporator and is drawn into
    the compressor. Here it is compressed
    and leaves the compressor as a
    mixture of hot gas and oil (which was
    injected during the compression cycle).
    The mixture enters the oil separator at
    the two in/out caps. The separated oil
    flows to the bottom of the separator,
    while the refrigerant gas flows out the
    top and passes on to the tubes in the
    condensing coils. Here circulating air
    removes heat from the refrigerant and
    condenses it.
    The condensed refrigerant passes
    through the electronic expansion valve
    and into the tubes of the evaporator.
    As the refrigerant vaporizes, it cools the
    system water that surrounds the tubes
    in the evaporator.
    Compressor Description
    The compressors used by the Model
    RTAA Series “R” Air-cooled chiller
    consists of two distinct components:
    the motor and the rotors. Refer to
    Figure 42.
    Compressor Motor
    A two-pole, hermetic, squirrel-cage
    induction motor directly drives the
    compressor rotors. The motor is cooled
    by suction refrigerant gas from the
    evaporator, entering the end of the
    motor housing through the suction
    line, as shown in Figures 40 and 41.
    Compressor Rotors
    The compressor is a semi-hermetic,
    direct drive helical rotary type
    compressor. Each compressor has only
    three moving parts: Two rotors -
    “male” and ‘female” - provide
    compression, and a slide valve controls
    capacity. See Figure 42. The male rotor
    is attached to, and driven by, the motor,
    and the female rotor is, in turn, driven
    by the male rotor. Separately housed
    bearing sets are provided at each end
    of 
    both rotors. The slide valve is located
    above, and moves along, the top of the
    rotors.
    The helical rotary compressor is a
    positive displacement device. The
    refrigerant from the evaporator is
    drawn into the suction opening at the
    end of the motor barrel, through a
    suction strainer screen, across the
    motor, and into the intake of the
    compressor rotor section. The gas is
    then compressed and discharged
    directly into the discharge line.
    There is no physical contact between
    the rotors and compressor housing.
    The rotors contact each other at the
    point where the driving action between
    the male and female rotors occurs. Oil
    is injected along the top of the
    compressor rotor section, coating both
    rotors and the compressor housing
    interior. Although this oil does provide
    rotor lubrication, its primary purpose is
    to seal the clearance spaces between
    the rotors and compressor housing.
    A positive seal between these internal
    parts enhances compressor efficiency
    by limiting leakage between the high
    pressure and low pressure cavities.Capacity control is accomplished by
    means of a slide valve assembly
    located in the rotor section of the
    compressor. Positioned along the top
    of the rotors, the slide valve is driven
    by a piston/cylinder along an axis that
    parallels those of the rotors.
    Compressor load condition is dictated
    by the position of the slide valve over
    the rotors. When the slide valve is fully
    extended over the rotors and away
    from the discharge end, the
    compressor is fully loaded. Unloading
    occurs as the slide valve is drawn
    towards the discharge end. Slide valve
    unloading lowers refrigeration capacity
    by reducing the compression surface of
    the rotors.
    Compressor Loading Sequence
    When there is a call for chilled water,
    the UCM will start the compressor
    which has the least number of starts. If
    the first compressor cannot satisfy the
    demand, the UCM will start another
    compressor and then balance the load
    on all compressors by pulsing the load/
    unload solenoids.
    The load on the compressors will be
    kept in balance, as load fluctuates, until
    the demand for chilled water is reduced
    to a level that can be handled by one
    compressor. At this time, the UCM will
    drop off the compressor that has the
    greatest number of operating hours
    and will adjust the load on the other
    compressor, as required. 
    						
    							78RTAA-IOM-3
    Figure 40
    Refrigeration System and
    Control Components
    Single Circuit(Continued on Next Page) 
    						
    							79RTAA-IOM-3
    Figure 40
    (Continued from Previous Page)
    1 Schrader valve
    2 Suction temperature sensor*
    3 Manufacturing process tube
    4 Suction service valve (optional)
    5 Motor winding thermostat*
    6 Discharge temperature sensor*
    7 Pressure relief valve (450 psi)
    8 High pressure cutout (405 psi)*
    9 Discharge check valve
    10 Evaporator waterside vent
    11 Discharge line shutoff valve
    12 Oil separator in/out cap
    13 Saturated condensing temperature
    sensor*
    14 Condenser header
    15 Subcooler header
    16 Liquid line shutoff valve17 25 micron filter/drier
    18 Liquid line sight glass
    19 Electronic expansion valve
    20 Saturated evaporator temperature
    sensor*
    21 Evaporator waterside drain
    22 Leaving water temperature sensor*
    23 Leaving water connection
    24 Entering water connection
    25 Entering water temperature sensor*
    26 Drain with Schrader valve
    27 Oil line
    28 Entering oil cooler header
    29 Leaving oil cooler header
    30 Schrader valve with stem depressor
    31 Oil line shutoff valve
    32 5 micron oil filter33 Master solenoid valve*
    34 Oil line to load/unload slide valve
    solenoids
    35 Injection oil check valve
    36 Heater
    37 Slide valve solenoids and orifices*
    38 Oil flow differential pressure switch*
    39 Compressor Drain Plug
    40 Domestic water heater (option)
    41 Oil line thermostat (option,
    Domestic Water Heater)
    42 Oil line bypass solenoid valve
    (option, Domestic Water Heater)
    *UCM Input/Output Control 
    						
    							80RTAA-IOM-3
    Figure 41
    Refrigeration System and
    Control Components
    Duplex Circuit(Continued on Next Page) 
    						
    All Trane manuals Comments (0)

    Related Manuals for Trane Rtaaiom3 Manual