Trane Rtaaiom3 Manual
Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
41RTAA-IOM-3 Evaporator Piping Figure 22 illustrates typical evaporator piping components. Components and layout will vary slightly, depending on the location of connections and the water source. Caution: The chilled water connections to the evaporator are to be “victaulic” type connections. Do not attempt to weld these connections, as the heat generated from welding can cause internal damage to the evaporator. The chilled water connections are on the left side of the unit. If it is necessary for the chilled water piping to enter the unit from the right side, elbows can be used to route the piping 1800 over the top of the evaporator, as shown in Figure 22, for RTAA 130-200 units only. A vent is provided on the top of the evaporator at the return end. Be sure to provide additional vents at high points in the piping to bleed air from the chilled water system. Install necessary pressure gauges to monitor the entering and leaving chilled water pressures. Caution: To prevent damage to chilled water components, do not allow evaporator pressure (maximum working pressure) to exceed 215 psig. Provide shutoff valves in lines to the gauges to isolate them from the system when they are not in use. Use rubber vibration eliminators to prevent vibration transmission through the water lines. If desired, install thermometers in the lines to monitor entering and leaving water temperatures. Install a balancing valve in the leaving water line to control water flow balance. Install shutoff valves on both the entering and leaving water lines so that the evaporator can be isolated for service. A pipe strainer should be installed in the entering water line to prevent waterborne debris from entering the evaporator. Figure 22 Suggested Piping for Typical RTAA Evaporator VentsValved Pressure Gauge DrainUnion Vibration EliminatorFlow Switch (Optional) Balancing ValveGate Valve Union Water Strainer Vibration Eliminator Gate Valve RTAA 130-200 with Opposite-Side Connections (View from end opposite control panel)
42RTAA-IOM-3 Evaporator Piping Components “Piping components” include all devices and controls used to provide proper water system operation and unit operating safety. These components and their general locations are given below. Entering Chilled Water Piping [ ] Air vents (to bleed air from system). [ ] Water pressure gauges with shutoff valves. [ ] Vibration eliminators. [ ] Shutoff (isolation) valves. Thermometers (if desired). [ ] Clean-out tees. [ ] Pipe strainer. Caution: To prevent tube damage install strainer in evaporator water inlet piping. Leaving Chilled Water Piping [ ] Air vents (to bleed air from system). [ ] Water pressure gauges with shutoff valves. Vibration eliminators. [ ] Shutoff (isolation) valves. [ ] Thermometers. [ ] Clean-out tees. [ ] Balancing valve. [ ] Flow Switch (If desired) Caution: To prevent evaporator damage, do not exceed 215 psig (14.6 bar) evaporator water pressure. Evaporator Drain A 3/4 drain connection is located under the outlet end of the evaporator. This may be connected to a suitable drain to permit evaporator drainage during unit servicing. A shutoff valve must be installed on the drain line. Evaporator Flow Switch Chilled water flow protection is provided by the UCM without the need for a chilled water flow switch. A flow switch for chilled water is strictly discretionary but if not installed, a signal still must be sent to the chiller to indicate that water flow has been established, e.g. chilled water pump motor starter auxiliary contacts. If additional chilled water flow protection is desired, use a field- installed flow switch or differential pressure switch with the pump interlock to sense system water flow. Install and wire the flow switch in series with the chilled water pump motor starter auxiliaries (refer to “Electrical Wiring”). Specific connection and schematic wiring diagrams are shipped with the unit. Some piping and control schemes, particularly those using a single water pump for both chilled and hot water, must be analyzed to determine how and or if a flow sensing device will provide desired operation. Follow the manufacturer’s recommendations for selection and installation procedures. General guidelines for flow switch installation are outlined below 1. Mount the switch upright, with a minimum of 5 pipe diameters of straight horizontal run on each side. Do not install close to elbows, orifices or valves. Note: The arrow on the switch must point in the direction of flow. 2. To prevent switch fluttering, remove all air from the water system. Note: The UCM provides a 6-second time delay after a “loss-of-flow” diagnostic before shutting the unit down. Contact a qualified service representative if nuisance machine shutdowns persist.
43RTAA-IOM-3 3. Adjust the switch to open when water flow falls below nominal. Evaporator data is shown in Figure 23. Refer to Table 1 for minimum flow recommendations. Flow switch contacts are closed on proof of water flow.4. Install a pipe strainer in the entering evaporator water line to protect components from waterborne debris. Figure 23 RTAA 130 thru 400 Evaporator Water Pressure Drop
44RTAA-IOM-3 Water Treatment Using untreated or improperly treated water in these units may result in inefficient operation and possible tube damage. Consult a qualified water treatment specialist to determine whether treatment is needed. The following disclamatory label is provided on each RTAA unit: Customer Note The use of improperly treated or untreated water in this equipment may result in scaling, erosion, corrosion, algae or slime. The services of a qualified water treatment specialist should be engaged to determine what treatment, if any, is advisable. The Trane Company warranty specifically excludes liability for corrosion, erosion or deterioration of Trane equipment. Trane assumes no responsibilities for the results of the use of untreated or improperly treated water, or saline or brackish water. Caution: Do not use untreated or improperly treated water. Equipment damage may occur. Water Pressure Gauges Install field-supplied pressure gauges (with manifolds, whenever practical) as shown in Figure 22. Locate pressure gauges or taps in a straight run of pipe; avoid placement near elbows, etc. Be sure to install the gauges at the same elevation on each shell if the shells have opposite-end water connections. To read manifolded pressure gauges, open one valve and close the other (depending upon the reading desired). This eliminates errors resulting from differently calibrated gauges installed at unmatched elevations. Water Pressure Relief Valves Install a water pressure relief valve in the evaporator inlet piping between the evaporator and the inlet shutoff valve, as shown in Figure 22. Water vessels with close-coupled shutoff valves have a high potential for hydrostatic pressure buildup on a water temperature increase. Refer to applicable codes for relief valve installation guidelines. Caution: To prevent shell damage, install pressure relief valves in the evaporator water system. Freeze Protection If the unit will remain operational at subfreezing ambient temperatures, the chilled water system must be protected from freezing, following the steps listed below 1. Heat tape is factory-installed on the packaged unit evaporator and will protect it from freezing in ambient temperatures down to -20 F. 2. Install heat tape on all water piping, pumps, and other components that may be damaged if exposed to freezing temperatures. Heat tape must be designed for low ambient temperature applications. Heat tape selection should be based on the lowest expected ambient temperature. 3. Add a non-freezing, low temperature, corrosion inhibiting, heat transfer fluid to the chilled water system. The solution must be strong enough to provide protection against ice formation at the lowest anticipated ambient temperature. Refer to Table 1 for evaporator water storage capacities. Note: Use of glycol type antifreeze reduces the cooling capacity of the unit and must be considered in the design of the system specifications.
45RTAA-IOM-3 Domestic Water Heater Piping Figure 24 illustrates typical domestic water heater piping components. Components and layout will vary slightly, depending on the location of connections and the water source. See unit submittals to insure identification of water inlet and outlet connections. Be sure to provide additional vents at high points in the piping to bleed air from the water system. Caution: To prevent damage to components, do not allow domestic water heater pressure (maximum working pressure) to exceed 150 psig. Use rubber vibration eliminators to prevent vibration transmission through the water lines. Install a balancing valve in the leaving water line to control water flow balance. Install shutoff valves on both the entering and leaving water lines so that the domestic water heater can be isolated for service. The vent and drain can be used to temporarily install gauges and determine pressure drop at the heater. Water flow rates, as a function of pressure drop, are charted in Figure 25, or pressure drop can be calculated using the following formula: Pressure Drop (Ft. H20) = 2.31 (Drain psig -Vent psig) A pipe strainer should be installed in the entering water line to prevent waterborne debris from entering the domestic water heater. Domestic Water Heater Piping Components “Piping components” include all devices and controls used to provide proper water system operation and unit operating safety. These components and their general locations are given below. Entering Water Piping [ ] Drain [ ] Vibration eliminators. [ ] Shutoff (isolation) valves. [ ] Pipe strainer. Caution: To prevent tube damage install strainer in the water inlet piping. Leaving Chilled Water Piping [ ] Air vents (to bleed air from system) [ ] Vibration eliminators. [ ] Shutoff (isolation) valves. [ ] Balancing valve. Caution: To prevent damage, do not exceed 215 psig (14.6 bar) domestic water heater water pressure. Water Pressure Relief Valves Install a water pressure relief valve in the outlet piping between the domestic water heater and the outlet shutoff valve, as shown in Figure 24. Water vessels with close-coupled shutoff valves have a high potential for hydrostatic pressure buildup on a water temperature increase. Refer to applicable codes for relief valve installation guidelines. Caution: To prevent shell damage, install pressure relief valves in the evaporator water system. Freeze Protection If water in the domestic water heater will be subjected to subfreezing ambient temperatures, the water system must be protected from freezing, following the steps listed below: 1. Heat tape is factory-installed on the domestic water heater and will protect it from freezing in ambient temperatures down to -20 F Insure that electrical power is provided for the heat tape. 2. Install heat tape on all water piping, pumps, and other components that may be damaged if exposed to freezing temperatures. Heat tape must be designed for low ambient temperature applications. Heat tape selection should be based on the lowest expected ambient temperature.
46RTAA-IOM-3 Figure 24 Typical Domestic Water Heater Piping Figure 25 Typical Domestic Water Heater Piping
47RTAA-IOM-3 Installation - Mechanical Remote Evaporator Interconnecting Refrigerant Piping. General The RTAA outdoor unit with the Remote Evaporator option is shipped as two pieces: the outdoor unit (condensing) and the evaporator. The outdoor unit includes a suction accumulator line on each circuit and has the field connections for the refrigerant at the end opposite the control panel. The evaporator is shipped complete with factory-mounted refrigeration specialties (electronic expansion valves, sight-glasses and removable core filter-dryers). All evaporator refrigerant line connections are at one end of the evaporator. The installing contractor need only provide and install the refrigerant piping between the evaporator and the outdoor unit. System Configuration The system may be configured in either of the two primary arrangements as shown in Figures 26 and 27. The configuration and its associated elevation, along with the total distance between the remote evaporator and the compressor/condenser section, play a critical role in determining suction and liquid line sizes. This will also affect field refrigerant and oil charges. Consequently, there are physical limits which must not be violated if the system is to operate as designed. Please note the following restrictions: Figure 26 Remote Evaporator Installation – No Elevation Difference
48RTAA-IOM-3 A. The line sizes established in this installation manual are to be used only for 40-50 F leaving water temperature and full-load ice-making applications. B. The evaporator can be mounted only on the SAME PLANE OR LOWER PLANE than the outdoor unit. Figure 28 illustrates what not to do. The elevation difference is to not exceed 100 feet.C. Piping between evaporator and outdoor unit is to not exceed 200 (linear) feet or an equivalent length (includes equivalent length pressure drop of fittings) of 300 feet. D. The suction line must never cross or be above a plane that is 1’8 above the bottom of the outdoor unit. Figure 29 illustrates what not to do. Figure 27 Remote Evaporator Installation – Condenser and Compressor above Evaporator
49RTAA-IOM-3 E. Horizontal portions of the suction lines must be downward sloping to the compressors. Suction lines must be insulated. F. Install an inverted trap in the liquid line when the evaporator is on a lower plane than the outdoor unit. The apex of the trap should be at a height above the top of the condenser coils. See Figure 27. G. Install a suction line trap at the evaporator when the evaporator is on a lower plane than the outdoor unit. See Figure 27.H. The evaporator MUST be matched with its respective outdoor unit. The nameplate on the evaporator will have a serial number that is matched to the outdoor unit’s serial number. See Figure 7. Also the circuits on the outdoor unit must match the circuits on the evaporator (I.E. circuit #1 on the outdoor units must be connected with circuit #1 on the evaporator). Caution: If the circuits are crossed, serious equipment damage may occur. See Figure 30 for circuit number identification. Figure 28 Restricted Installation – Evaporator is on a Higher Plane than the Outdoor Unit Figure 29 – Restricted Installation - Suction Line is More Than 1’8 Above Base of Outdoor Unit
50 RTAA-IOM-3 Figure 30 Refrigerant Circuit Identification