Home > Trane > Cooler > Trane Rtaaiom3 Manual

Trane Rtaaiom3 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							41RTAA-IOM-3
    Evaporator Piping
    Figure 22 illustrates typical evaporator
    piping components. Components and
    layout will vary slightly, depending on
    the location of connections and the
    water source.
    Caution: The chilled water
    connections to the evaporator are
    to be “victaulic” type connections.
    Do not attempt to weld these
    connections, as the heat generated
    from welding can cause internal
    damage to the evaporator.
    The chilled water connections are on
    the left side of the unit. If it is necessary
    for the chilled water piping to enter the
    unit from the right side, elbows can be
    used to route the piping 1800 over the
    top of the evaporator, as shown in
    Figure 22, for RTAA 130-200 units only.
    A vent is provided on the top of the
    evaporator at the return end. Be sure to
    provide additional vents at high points
    in the piping to bleed air from the
    chilled water system. Install necessary
    pressure gauges to monitor the
    entering and leaving chilled water
    pressures.
    Caution: To prevent damage to
    chilled water components, do not
    allow evaporator pressure
    (maximum working pressure) to
    exceed 215 psig.
    Provide shutoff valves in lines to the
    gauges to isolate them from the
    system when they are not in use. Use
    rubber vibration eliminators to prevent
    vibration transmission through the
    water lines.
    If desired, install thermometers in the
    lines to monitor entering and leaving
    water temperatures. Install a balancing
    valve in the leaving water line to
    control water flow balance. Install
    shutoff valves on both the entering and
    leaving water lines so that the
    evaporator can be isolated for service.
    A pipe strainer should be installed in
    the entering water line to prevent
    waterborne debris from entering the
    evaporator.
    Figure 22
    Suggested Piping for
    Typical RTAA Evaporator
    VentsValved
    Pressure
    Gauge
    DrainUnion
    Vibration
    EliminatorFlow
    Switch
    (Optional)
    Balancing ValveGate Valve Union
    Water
    Strainer Vibration
    Eliminator
    Gate Valve
    RTAA 130-200
    with Opposite-Side Connections
    (View from end opposite control panel) 
    						
    							42RTAA-IOM-3
    Evaporator Piping
    Components
    “Piping components” include all
    devices and controls used to provide
    proper water system operation and
    unit operating safety. These
    components and their general
    locations are given below.
    Entering Chilled Water Piping
    [  ] Air vents (to bleed air from system).
    [  ] Water pressure gauges with shutoff
    valves.
    [  ] Vibration eliminators.
    [  ] Shutoff (isolation) valves.
    Thermometers (if desired).
    [  ] Clean-out tees.
    [  ] Pipe strainer.
    Caution: To prevent tube damage
    install strainer in evaporator water
    inlet piping.
    Leaving Chilled Water Piping
    [  ] Air vents (to bleed air from system).
    [  ] Water pressure gauges with shutoff
    valves. Vibration eliminators.
    [  ] Shutoff (isolation) valves.
    [  ] Thermometers.
    [  ] Clean-out tees.
    [  ] Balancing valve.
    [  ] Flow Switch (If desired)
    Caution: To prevent evaporator
    damage, do not exceed 215 psig
    (14.6 bar) evaporator water
    pressure.
    Evaporator Drain
    A 3/4 drain connection is located
    under the outlet end of the evaporator.
    This may be connected to a suitable
    drain to permit evaporator drainage
    during unit servicing. A shutoff valve
    must be installed on the drain line.
    Evaporator Flow Switch
    Chilled water flow protection is
    provided by the UCM without the need
    for a chilled water flow switch. A flow
    switch for chilled water is strictly
    discretionary but if not installed, a
    signal still must be sent to the chiller to
    indicate that water flow has been
    established, e.g. chilled water pump
    motor starter auxiliary contacts.
    If additional chilled water flow
    protection is desired, use a field-
    installed flow switch or differential
    pressure switch with the pump
    interlock to sense system water flow.
    Install and wire the flow switch in series
    with the chilled water pump motor
    starter auxiliaries (refer to “Electrical
    Wiring”).
    Specific connection and schematic
    wiring diagrams are shipped with the
    unit. Some piping and control
    schemes, particularly those using a
    single water pump for both chilled and
    hot water, must be analyzed to
    determine how and or if a flow sensing
    device will provide desired operation.
    Follow the manufacturer’s
    recommendations for selection and
    installation procedures. General
    guidelines for flow switch installation
    are outlined below
    1. Mount the switch upright, with a
    minimum of 5 pipe diameters of
    straight horizontal run on each side.
    Do not install close to elbows,
    orifices or valves.
    Note: The arrow on the switch must
    point in the direction of flow.
    2. To prevent switch fluttering, remove
    all air from the water system.
    Note: The UCM provides a 6-second
    time delay after a “loss-of-flow”
    diagnostic before shutting the unit
    down. Contact a qualified service
    representative if nuisance machine
    shutdowns persist. 
    						
    							43RTAA-IOM-3
    3. Adjust the switch to open when
    water flow falls below nominal.
    Evaporator data is shown in Figure
    23. Refer to Table 1 for minimum
    flow recommendations. Flow switch
    contacts are closed on proof of water
    flow.4. Install a pipe strainer in the entering
    evaporator water line to protect
    components from waterborne
    debris.
    Figure 23
    RTAA 130 thru 400
    Evaporator Water Pressure Drop 
    						
    							44RTAA-IOM-3
    Water Treatment
    Using untreated or improperly treated
    water in these units may result in
    inefficient operation and possible tube
    damage. Consult a qualified water
    treatment specialist to determine
    whether treatment is needed. The
    following disclamatory label is
    provided on each RTAA unit:
    Customer Note
    The use of improperly treated or
    untreated water in this equipment may
    result in scaling, erosion, corrosion,
    algae or slime. The services of a
    qualified water treatment specialist
    should be engaged to determine what
    treatment, if any, is advisable. The
    Trane Company warranty specifically
    excludes liability for corrosion, erosion
    or deterioration of Trane equipment.
    Trane assumes no responsibilities for
    the results of the use of untreated or
    improperly treated water, or saline or
    brackish water.
    Caution: Do not use untreated or
    improperly treated water.
    Equipment damage may occur.
    Water Pressure Gauges
    Install field-supplied pressure gauges
    (with manifolds, whenever practical) as
    shown in Figure 22. Locate pressure
    gauges or taps in a straight run of pipe;
    avoid placement near elbows, etc. Be
    sure to install the gauges at the same
    elevation on each shell if the shells
    have opposite-end water connections.
    To read manifolded pressure gauges,
    open one valve and close the other
    (depending upon the reading desired).
    This eliminates errors resulting from
    differently calibrated gauges installed
    at unmatched elevations.
    Water Pressure Relief Valves
    Install a water pressure relief valve in
    the evaporator inlet piping between the
    evaporator and the inlet shutoff valve,
    as shown in Figure 22. Water vessels
    with close-coupled shutoff valves have
    a high potential for hydrostatic
    pressure buildup on a water
    temperature increase. Refer to
    applicable codes for relief valve
    installation guidelines.
    Caution: To prevent shell damage,
    install pressure relief valves in the
    evaporator water system.
    Freeze Protection
    If the unit will remain operational at
    subfreezing ambient temperatures, the
    chilled water system must be protected
    from freezing, following the steps listed
    below
    1. Heat tape is factory-installed on the
    packaged unit evaporator and will
    protect it from freezing in ambient
    temperatures down to -20 F.
    2. Install heat tape on all water piping,
    pumps, and other components that
    may be damaged if exposed to
    freezing temperatures. Heat tape
    must be designed for low ambient
    temperature applications. Heat tape
    selection should be based on the
    lowest expected ambient
    temperature.
    3. Add a non-freezing, low temperature,
    corrosion inhibiting, heat transfer
    fluid to the chilled water system. The
    solution must be strong enough to
    provide protection against ice
    formation at the lowest anticipated
    ambient temperature. Refer to Table
    1 for evaporator water storage
    capacities.
    Note: Use of glycol type antifreeze
    reduces the cooling capacity of the unit
    and must be considered in the design
    of the system specifications. 
    						
    							45RTAA-IOM-3
    Domestic Water Heater
    Piping
    Figure 24 illustrates typical domestic
    water heater piping components.
    Components and layout will vary
    slightly, depending on the location of
    connections and the water source. See
    unit submittals to insure identification
    of water inlet and outlet connections.
    Be sure to provide additional vents at
    high points in the piping to bleed air
    from the water system.
    Caution: To prevent damage to
    components, do not allow
    domestic water heater pressure
    (maximum working pressure) to
    exceed 150 psig.
    Use rubber vibration eliminators to
    prevent vibration transmission through
    the water lines.
    Install a balancing valve in the leaving
    water line to control water flow
    balance. Install shutoff valves on both
    the entering and leaving water lines so
    that the domestic water heater can be
    isolated for service.
    The vent and drain can be used to
    temporarily install gauges and
    determine pressure drop at the heater.
    Water flow rates, as a function of
    pressure drop, are charted in Figure 25,
    or pressure drop can be calculated
    using the following formula:
    Pressure Drop (Ft. H20) = 2.31 (Drain
    psig -Vent psig)
    A pipe strainer should be installed in
    the entering water line to prevent
    waterborne debris from entering the
    domestic water heater.
    Domestic Water Heater
    Piping Components
    “Piping components” include all
    devices and controls used to provide
    proper water system operation and
    unit operating safety. These
    components and their general
    locations are given below.
    Entering Water Piping
    [  ] Drain
    [  ] Vibration eliminators.
    [  ] Shutoff (isolation) valves.
    [  ] Pipe strainer.
    Caution: To prevent tube damage
    install strainer in the water inlet
    piping.
    Leaving Chilled Water Piping
    [  ] Air vents (to bleed air from system)
    [  ] Vibration eliminators.
    [  ] Shutoff (isolation) valves.
    [  ] Balancing valve.
    Caution: To prevent damage, do
    not exceed 215 psig (14.6 bar)
    domestic water heater water
    pressure.
    Water Pressure Relief Valves
    Install a water pressure relief valve in
    the outlet piping between the domestic
    water  heater and the outlet shutoff
    valve, as shown in Figure 24. Water
    vessels with close-coupled shutoff
    valves have a high potential for
    hydrostatic pressure buildup on a
    water temperature increase. Refer to
    applicable codes for relief valve
    installation guidelines.
    Caution: To prevent shell damage,
    install pressure relief valves in the
    evaporator water system.
    Freeze Protection
    If water in the domestic water heater
    will be subjected to subfreezing
    ambient temperatures, the water
    system must be protected from
    freezing, following the steps listed
    below:
    1. Heat tape is factory-installed on the
    domestic water heater and will
    protect it from freezing in ambient
    temperatures down to -20 F Insure
    that electrical power is provided for
    the heat tape.
    2. Install heat tape on all water piping,
    pumps, and other components that
    may be damaged if exposed to
    freezing temperatures. Heat tape
    must be designed for low ambient
    temperature applications. Heat tape
    selection should be based on the
    lowest expected ambient
    temperature. 
    						
    							46RTAA-IOM-3
    Figure 24
    Typical Domestic Water
    Heater Piping
    Figure 25
    Typical Domestic Water
    Heater Piping 
    						
    							47RTAA-IOM-3
    Installation - Mechanical
    Remote Evaporator Interconnecting
    Refrigerant Piping.
    General
    The RTAA outdoor unit with the
    Remote Evaporator option is shipped
    as two pieces: the outdoor unit
    (condensing) and the evaporator. The
    outdoor unit includes a suction
    accumulator line on each circuit and
    has the field connections for the
    refrigerant at the end opposite the
    control panel.
    The evaporator is shipped complete
    with factory-mounted refrigeration
    specialties (electronic expansion
    valves, sight-glasses and removable
    core filter-dryers). All evaporator
    refrigerant line connections are at one
    end of the evaporator. The installing
    contractor need only provide and
    install the refrigerant piping between
    the evaporator and the outdoor unit.
    System Configuration
    The system may be configured in
    either of the two primary arrangements
    as shown in Figures 26 and 27. The
    configuration and its associated
    elevation, along with the total distance
    between the remote evaporator and
    the compressor/condenser section,
    play a critical role in determining
    suction and liquid line sizes. This will
    also affect field refrigerant and oil
    charges. Consequently, there are
    physical limits which must not be
    violated if the system is to operate as
    designed. Please note the following
    restrictions:
    Figure 26
    Remote Evaporator Installation –
    No Elevation Difference 
    						
    							48RTAA-IOM-3
    A. The line sizes established in this
    installation manual are to be used only
    for 40-50 F leaving water temperature
    and full-load ice-making applications.
    B. The evaporator can be mounted
    only on the SAME PLANE OR LOWER
    PLANE than the outdoor unit. Figure 28
    illustrates what not to do. The elevation
    difference is to not exceed 100 feet.C. Piping between evaporator and
    outdoor unit is to not exceed 200
    (linear) feet or an equivalent length
    (includes equivalent length pressure
    drop of fittings) of 300 feet.
    D. The suction line must never cross or
    be above a plane that is 1’8 above the
    bottom of the outdoor unit. Figure 29
    illustrates what not to do.
    Figure 27
    Remote Evaporator Installation –
    Condenser and Compressor
    above Evaporator 
    						
    							49RTAA-IOM-3
    E. Horizontal portions of the suction
    lines must be downward sloping to the
    compressors. Suction lines must be
    insulated.
    F. Install an inverted trap in the liquid
    line when the evaporator is on a lower
    plane than the outdoor unit. The apex
    of the trap should be at a height above
    the top of the condenser coils. See
    Figure 27.
    G. Install a suction line trap at the
    evaporator when the evaporator is on a
    lower plane than the outdoor unit. See
    Figure 27.H. The evaporator MUST be matched
    with its respective outdoor unit. The
    nameplate on the evaporator will have
    a serial number that is matched to the
    outdoor unit’s serial number. See
    Figure 7.
    Also the circuits on the outdoor unit
    must match the circuits on the
    evaporator (I.E. circuit #1 on the
    outdoor units must be connected with
    circuit #1 on the evaporator).
    Caution: If the circuits are crossed,
    serious equipment damage may
    occur.
    See Figure 30 for circuit number
    identification.
    Figure 28
    Restricted Installation –
    Evaporator is on a Higher Plane
    than the Outdoor Unit
    Figure 29 – Restricted Installation -
    Suction Line is More Than 1’8
    Above Base of Outdoor Unit 
    						
    							50
    RTAA-IOM-3
    Figure 30 
    Refrigerant Circuit Identification 
    						
    All Trane manuals Comments (0)

    Related Manuals for Trane Rtaaiom3 Manual