Home > Trane > Cooler > Trane Rtaaiom3 Manual

Trane Rtaaiom3 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							21RTAA-IOM-3
    Nameplates
    The RTAA outdoor unit nameplates are
    applied to the exterior and interior
    surface of the Control Panel door
    (Figure 1). A compressor nameplate is
    located on each compressor. On
    remote evaporators, the nameplate is
    located on the Terminal Box.
    Outdoor Unit Nameplate
    The outdoor unit nameplate provides
    the following information:
    – Unit model and size description.
    – Unit serial number.
    – Identifies unit electrical requirements.– Lists correct operating charges of
     R-22 and refrigerant oil.
    – Lists unit test pressures.
    – Identifies installation, operation and
     maintenance and service data
     literature
    – Lists drawing numbers for unit wiring
     diagrams.
    Compressor Nameplate
    The “compressor’ nameplate provides
    following information:
    – Compressor model number.
    – Compressor serial number.– Compressor electrical characteristics.
    – Utilization Range.
    – Recommended refrigerant.
    Remote Evaporator
    Nameplate
    The “evaporator” nameplate provides
    the following information:
    – RTAA outdoor unit to which the
     remote evaporator is designed to
     be connected.
    – Evaporator serial number. This
     number and the serial number of the
     outdoor RTAA unit to which it is
     connected will be identical.
    Figure 7
    Nameplates 
    						
    							22RTAA-IOM-3
    Figure 8
    Model Number Coding System
    RTAA200GXB01A0D0BDEG01 2
    123 4 567 8 9 01 2 3 4 5 6 7 8 9 0 (Digit position for above)
    Where digits are assigned the following meanings:
    Digit Character
    No. Value Description
    1, 2, 3 Unit  Type/Function
    RTA Rotary (Series “R”)
    Air Cooled Chiller
    4 Development Sequence
    A “A” Dev. Sequence
    5, 6, 7 Unit Nominal Tons
    130 130 Tons
    140 140 Tons
    155 155 Tons
    170 170 Tons
    185 185 Tons
    200 200 Tons
    240 240 Tons
    270 270 Tons
    300 300 Tons
    340 340 Tons
    370 370 Tons
    400 400 Tons
    8 Unit Voltage
    D 380/60/3
    G 200-230/60/3 Dual
    Voltage
    1 346/50/3
    K 380-415/50/3
    4 460/60/3
    5 575/60/3
    S Special Customer Option
    9 Compressor Starter Type
    Y Y-Delta
    (Closed Transition)
    X X-Line
    (Across the line)
    S Special Customer Option
    10, 11 Design  Sequence
    BO Second design.
    Increment when parts
    are affected for
    service purposes.
    12 Evaporator Leaving Temp.
    1 Standard 40-60 F
    2 Low 20-40 F
    3 Ice making 20-60 F
    S Special Customer Option
    13 Condenser Coil Fin
    Material
    A Aluminum
    B Aluminum with
    corrosion protection
    S Special Customer Option
    Digit Character
    No. Value Description
    14 Agency Listing
    0 No agency listing
    1 U.L. listed - Standard
    where  applicable
    2 C.S.A. listed
    3 *U.L./C.S.A. listed
    S Special Customer Option
    15 Control Interface
    A Standard Control
    No communication
    module
    B Standard Control
    With communication
    module
    C Deluxe Control
    No communication
    module
    D Deluxe Control
    With communication module
    Deluxe control option consists
    of the following:
    A - Cycle counter and
    hour meter
    B - Under/over  voltage
    protection
    C - Remote alarm contacts
    and compressor run
    indication
    D - % volts
    16 Chilled Water Reset
    0 None
    1 Return water temperature
    2 Outside air temperature
    3 Zone temperature
    S Special Customer Option
    17+ Add on Options
    A Architectural louvered
    panels
    B Control power transformer
    C Heat recovery
    D Low ambient lockout
    sensor
    E Suction service valves
    F Power disconnect
    G Low ambient operation
    H *Unit sound attenuator
    I Remote evaporator
    S Special Customer Option
    Note:
    1. Digits 17 and on may be multiple,
    independent add on options.
    2. * Denotes that this option assignment has
    been made but is not available now
    Model Number
    Coding System
    The model numbers for the outdoor
    unit and the compressors are
    comprised of numbers and letter which
    represent features of the equipment.
    Shown on the chart in Figure 8 are
    samples of typical unit and compressor
    model numbers, followed by the
    coding system for each.
    Each position, or group of positions, in
    the number is used to represent a
    feature. For example, in Figure 8,
    position 08 of the unit model number,
    Unit Voltage, contains the letter “G”.
    From the chart, it can be seen that a
    “G” in this position means that the unit
    voltage is 200-230/60/3 dual voltage. 
    						
    							23RTAA-IOM-3
    Storage
    Extended storage of the outdoor unit
    prior to installation requires the
    following precautionary measures:
    1. Store the outdoor unit in a secure
    area.
     2. At least every three months
    (quarterly), check the pressure in the
    refrigerant circuits to verify that the
    refrigerant charge is intact. If it is not,
    contact a qualified service
    organization and the appropriate
    Trane sales off ice. 
    						
    							25RTAA-IOM-3
    General
    The following instructions are, for the
    most part, applicable to both packaged
    units and units with the remote
    evaporator option. Specific exceptions
    are noted.
    The most significant difference in the
    installation of the two systems is the
    requirement for interconnecting piping
    with the remote evaporator option. For
    this reason, these installation
    procedures are covered separately in
    the following section, Installation -
    Mechanical, Remote Evaporator
    Interconnecting Piping.
    Pre-installation
    Report any damage incurred during
    handling or installation to the Trane
    sales office immediately. An Installation
    Check Sheet is provided.
    Location Requirements
    Noise Considerations
    Locate the outdoor unit away from
    sound sensitive areas. If required,
    install rubber vibration isolators in all
    water piping and use flexible electrical
    conduit. Refer to “Unit Isolation”.
    Consult an acoustical engineer for
    critical applications. Also refer to Trane
    Engineering Bulletins for application
    information on RTAA chillers.
    Installation - Mechanical
    Packaged Unit and Units with
    Remote Evaporator Option
    Foundation
    Provide rigid, non-warping mounting
    pads or a concrete foundation of
    sufficient strength and mass to support
    the outdoor unit operating weight (i.e.,
    including completed piping, and full
    operating charges of refrigerant, oil and
    water). Refer to Figures 18 thru 21 for
    unit operating weights. Once in place,
    the outdoor unit must be level within 1/
    4 (6.4 mm) over its length and width.
    The Trane Company is not responsible
    for equipment problems resulting from
    an improperly designed or constructed
    foundation.
    Clearances
    Provide enough space around the
    outdoor unit to allow the installation
    and maintenance personnel
    unrestricted access to all service points.
    Refer to submittal drawings for the unit
    dimensions. A minimum of four feet is
    recommended for compressor service.
    Provide sufficient clearance for the
    opening of control panel doors. Refer
    to Figures 9 thru 12 for minimum
    clearances.
     In all cases, local codes
    which require additional clearances willtake precedence over theserecommendations.
    Note: If the outdoor unit configuration
    requires a variance to the clearance
    dimensions, contact your Trane Sales
    Office Representative. Also refer to
    Trane Engineering Bulletins for
    application information on RTAA
    chillers. 
    						
    							26
    RTAA-IOM-3
    Figure 9 
    Dimensions and Clearances for 
    RTAA Packaged Unit – 130 to 200 Ton
    RTAA-SU-1000E 
    						
    							27
    RTAA-IOM-3
    Figure 10 
    Dimensions and Clearances for 
    RTAA Packaged Unit – 240 - 300 Ton
    RTAA-SU-1001C 
    						
    							28
    RTAA-IOM-3
    Figure 11 
    Dimensions and Clearances for 
    RTAA Packaged Unit – 340 to 400 Ton
    RTAA-SU-1002C 
    						
    							29
    RTAA-IOM-3
    Figure 12 
    Dimensions and Clearances for 
    RTAA Outdoor Unit with Remote Evaporator Option
    RTAA-SU-1003A 
    						
    							30
    RTAA-IOM-3
    Figure 13 
    Dimensions and Weights for 
    Remote Evaporator Option
    RTAA-SU-1004A
    NOTES: 
    1. TOLERANCE ± 1/8” UNLESS OTHERWISE SPECIFIED. 
    2. ALLOW 8’-8” ON EITHER END FOR TUBE REMOVAL. 
    						
    All Trane manuals Comments (0)

    Related Manuals for Trane Rtaaiom3 Manual