Trane Rtaaiom3 Manual
Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
21RTAA-IOM-3 Nameplates The RTAA outdoor unit nameplates are applied to the exterior and interior surface of the Control Panel door (Figure 1). A compressor nameplate is located on each compressor. On remote evaporators, the nameplate is located on the Terminal Box. Outdoor Unit Nameplate The outdoor unit nameplate provides the following information: – Unit model and size description. – Unit serial number. – Identifies unit electrical requirements.– Lists correct operating charges of R-22 and refrigerant oil. – Lists unit test pressures. – Identifies installation, operation and maintenance and service data literature – Lists drawing numbers for unit wiring diagrams. Compressor Nameplate The “compressor’ nameplate provides following information: – Compressor model number. – Compressor serial number.– Compressor electrical characteristics. – Utilization Range. – Recommended refrigerant. Remote Evaporator Nameplate The “evaporator” nameplate provides the following information: – RTAA outdoor unit to which the remote evaporator is designed to be connected. – Evaporator serial number. This number and the serial number of the outdoor RTAA unit to which it is connected will be identical. Figure 7 Nameplates
22RTAA-IOM-3 Figure 8 Model Number Coding System RTAA200GXB01A0D0BDEG01 2 123 4 567 8 9 01 2 3 4 5 6 7 8 9 0 (Digit position for above) Where digits are assigned the following meanings: Digit Character No. Value Description 1, 2, 3 Unit Type/Function RTA Rotary (Series “R”) Air Cooled Chiller 4 Development Sequence A “A” Dev. Sequence 5, 6, 7 Unit Nominal Tons 130 130 Tons 140 140 Tons 155 155 Tons 170 170 Tons 185 185 Tons 200 200 Tons 240 240 Tons 270 270 Tons 300 300 Tons 340 340 Tons 370 370 Tons 400 400 Tons 8 Unit Voltage D 380/60/3 G 200-230/60/3 Dual Voltage 1 346/50/3 K 380-415/50/3 4 460/60/3 5 575/60/3 S Special Customer Option 9 Compressor Starter Type Y Y-Delta (Closed Transition) X X-Line (Across the line) S Special Customer Option 10, 11 Design Sequence BO Second design. Increment when parts are affected for service purposes. 12 Evaporator Leaving Temp. 1 Standard 40-60 F 2 Low 20-40 F 3 Ice making 20-60 F S Special Customer Option 13 Condenser Coil Fin Material A Aluminum B Aluminum with corrosion protection S Special Customer Option Digit Character No. Value Description 14 Agency Listing 0 No agency listing 1 U.L. listed - Standard where applicable 2 C.S.A. listed 3 *U.L./C.S.A. listed S Special Customer Option 15 Control Interface A Standard Control No communication module B Standard Control With communication module C Deluxe Control No communication module D Deluxe Control With communication module Deluxe control option consists of the following: A - Cycle counter and hour meter B - Under/over voltage protection C - Remote alarm contacts and compressor run indication D - % volts 16 Chilled Water Reset 0 None 1 Return water temperature 2 Outside air temperature 3 Zone temperature S Special Customer Option 17+ Add on Options A Architectural louvered panels B Control power transformer C Heat recovery D Low ambient lockout sensor E Suction service valves F Power disconnect G Low ambient operation H *Unit sound attenuator I Remote evaporator S Special Customer Option Note: 1. Digits 17 and on may be multiple, independent add on options. 2. * Denotes that this option assignment has been made but is not available now Model Number Coding System The model numbers for the outdoor unit and the compressors are comprised of numbers and letter which represent features of the equipment. Shown on the chart in Figure 8 are samples of typical unit and compressor model numbers, followed by the coding system for each. Each position, or group of positions, in the number is used to represent a feature. For example, in Figure 8, position 08 of the unit model number, Unit Voltage, contains the letter “G”. From the chart, it can be seen that a “G” in this position means that the unit voltage is 200-230/60/3 dual voltage.
23RTAA-IOM-3 Storage Extended storage of the outdoor unit prior to installation requires the following precautionary measures: 1. Store the outdoor unit in a secure area. 2. At least every three months (quarterly), check the pressure in the refrigerant circuits to verify that the refrigerant charge is intact. If it is not, contact a qualified service organization and the appropriate Trane sales off ice.
25RTAA-IOM-3 General The following instructions are, for the most part, applicable to both packaged units and units with the remote evaporator option. Specific exceptions are noted. The most significant difference in the installation of the two systems is the requirement for interconnecting piping with the remote evaporator option. For this reason, these installation procedures are covered separately in the following section, Installation - Mechanical, Remote Evaporator Interconnecting Piping. Pre-installation Report any damage incurred during handling or installation to the Trane sales office immediately. An Installation Check Sheet is provided. Location Requirements Noise Considerations Locate the outdoor unit away from sound sensitive areas. If required, install rubber vibration isolators in all water piping and use flexible electrical conduit. Refer to “Unit Isolation”. Consult an acoustical engineer for critical applications. Also refer to Trane Engineering Bulletins for application information on RTAA chillers. Installation - Mechanical Packaged Unit and Units with Remote Evaporator Option Foundation Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the outdoor unit operating weight (i.e., including completed piping, and full operating charges of refrigerant, oil and water). Refer to Figures 18 thru 21 for unit operating weights. Once in place, the outdoor unit must be level within 1/ 4 (6.4 mm) over its length and width. The Trane Company is not responsible for equipment problems resulting from an improperly designed or constructed foundation. Clearances Provide enough space around the outdoor unit to allow the installation and maintenance personnel unrestricted access to all service points. Refer to submittal drawings for the unit dimensions. A minimum of four feet is recommended for compressor service. Provide sufficient clearance for the opening of control panel doors. Refer to Figures 9 thru 12 for minimum clearances. In all cases, local codes which require additional clearances willtake precedence over theserecommendations. Note: If the outdoor unit configuration requires a variance to the clearance dimensions, contact your Trane Sales Office Representative. Also refer to Trane Engineering Bulletins for application information on RTAA chillers.
26 RTAA-IOM-3 Figure 9 Dimensions and Clearances for RTAA Packaged Unit – 130 to 200 Ton RTAA-SU-1000E
27 RTAA-IOM-3 Figure 10 Dimensions and Clearances for RTAA Packaged Unit – 240 - 300 Ton RTAA-SU-1001C
28 RTAA-IOM-3 Figure 11 Dimensions and Clearances for RTAA Packaged Unit – 340 to 400 Ton RTAA-SU-1002C
29 RTAA-IOM-3 Figure 12 Dimensions and Clearances for RTAA Outdoor Unit with Remote Evaporator Option RTAA-SU-1003A
30 RTAA-IOM-3 Figure 13 Dimensions and Weights for Remote Evaporator Option RTAA-SU-1004A NOTES: 1. TOLERANCE ± 1/8” UNLESS OTHERWISE SPECIFIED. 2. ALLOW 8’-8” ON EITHER END FOR TUBE REMOVAL.