Trane Rtaaiom3 Manual
Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
111RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE NONE Outdoor Air Temperature None All Open or Short Sensor (Both Outdoor Air a. Display dashes e.g. 14 - - - - -”, Reset or Low Ambient Lockout Not Selected) Ab Evap. Leaving Water Temp. Sensor MMR All Open or Short bA Overload Trip - Compressor A CMR Compressor Energized Compressor current exceeded overload time vs. trip characteristic. bb Overload Trip - Compressor B CMR Compressor Energized Compressor current exceeded overload time vs. trip characteristic. bC Overload Trip - Compressor C CMR Compressor Energized Compressor current exceeded overload time vs. trip characteristic. bd Overload Trip - Compressor D CMR Compressor Energized Compressor current exceeded overload time vs. trip characteristic. bE High Pressure Cutout - Compressor C CMR All a. A high pressure cutout was detected on Compressor C; trip at 405 + or - 7 PSIG. BF High Pressure Cutout - Compressor D CMR All a. A high pressure cutout was detected on Compressor D; trip at 405 + or - 7 PSIG. NONE CWS/Leaving Water Temp. None All No diagnostic, display to flash and Cutout Setpoint Overlap limit value to last legal value. NOTE: The above is not a diagnostic because you don’t want the display vectoring you to a different display state when you are trying to set either the chilled water setpoint or the leaving water temp. cutout setpoint as it will in the case of a diagnostic. C5 Low Chilled Water Temperature IFW No Circuits Energized a. The chilled water temp. fell below (Unit Off) the cutout setpoint while the compressors were not running. C6 Low Chilled Water Temperature MAR Any Circuit Energized a. The chilled water temp. fell below (Unit On) the cutout setpoint while the compressors were running for 30 F - sec. CA Contactor - Compressor A MMR Compressor a. Welded compressor contactor. Not Energized b. Detected a welded compressor contactor off but the current does not go to zero. Detection time shall be 5 second minimum and 10 seconds maximum. On detection, generate the diagnostic, energize the appropriate alarm relay, continue to command the affected compressor off, energize the affected compressors oil line solenoid, stop all other compressors, unload the running compressor with the welded contactor, open the EXV to it’s maximum open position, and continue to do fan control. Do not exit this condition until the controller is manually reset. Cb Contactor - Compressor B MMR Same as CA Same as diagnostic CA CC Contactor - Compressor C MMR Same as CA Same as diagnostic CA Cd Contactor - Compressor D MMR Same as CA Same as diagnostic CA d7 Over Voltage MAR Pre-start and a. Line voltage above +10% of nominal. Any Circuit(s) (Must hold = +10% of nominal. Energized Must trip = +15% of nominal.)
112RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE d8 Under Voltage MAR Pre-start and a. Line voltage below -10% of nominal Any Circuit(s) Energized the Under/Over transformer is not connected. (Must hold = -10% of nominal Must trip = -15% of nominal). Ed Chilled Water Flow Interlock MAR All Modes Except a. The chilled water flow switch input STOP (00) and was open for more than 6 seconds. EXTERNAL STOP (100) F5 High Pressure Cutout - CMR All a. A high pressure cutout was detected Compressor A on Compressor A; trip at 405 + or - 7 PSIG. F6 High Pressure Cutout - CMR All a. A high pressure cutout was detected Compressor B on Compressor B; trip at 405 + or - 7 PSIG. Fd Emergency Stop MMR All a. EMERGENCY STOP input is open. An external interlock has tripped. Time to trip from input opening to unit stop shall be 0.1 to 1.0 sec. 180 Starter Transition CMR a. The UCM did not receive a Compressor A transition complete signal in the designated time from the UCM command to transition. The must hold time from the UCM transition command is 1 second. The Must trip time from the transition time is 6 seconds. b. The Transition Complete input was found to be shorted before the compressor was started. c. Active only if Reduced Inrush Starting is enabled. 181 Starter Transition - Compressor B CMR Same as 180 Same as diagnostic 180. 182 Starter Transition - Compressor C CMR Same as 180 Same as diagnostic 180. 183 Starter Transition - Compressor D CMR Same as 180 Same as diagnostic 180. 184 Phase Reversal - Compressor A CMR a. A phase reversal was detected on the incoming current. On a compressor start-up the phase reversal logic must detect and trip in a maximum of 1.0 second from compressor start. 185 Phase Reversal - Compressor B CMR Same as diagnostic 184. 186 Phase Reversal - Compressor C CMR Same as diagnostic 184. 187 Phase Reversal CMR Same as diagnostic 184. Compressor D
113RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 190 Low Superheat Circuit 1 CMR All Running Modes a. A low superheat condition existed for an extended period of time. If a superheat less than or equal to 2 F is detected for more than 2400 F seconds, the circuit shall be shut down. The integrated area (2400 F seconds) shall be only below 2 F superheat. 191 Low Superheat - Circuit 2 CMR All Running Modes Same as diagnostic 190. 194 Low Evap. Rfgt. Temp. - Circuit 1 CMR Compressor Energized a. The Saturated Evaporator Refrigerant Temp.- Circuit 1 dropped below the Low Refrigerant Temp. Cutout Setpoint when the circuit was running for 30 F seconds. b. See the low ambient ignore time on start-up. 195 Low Evap. Rfgt. Temp. CMR Compressor Energized Same as diagnostic 194, but for Ckt 2. 198 Low Oil Flow - Compressor A CMR Compressor Energized a. The differential oil pressure switch remained open for more than 20 contiguous seconds on Compressor A. 199 Low Oil Flow - Compressor B CMR Compressor Energized Same as diagnostic 198, but for Cprsr B. 19A Low Oil Flow - Compressor C CMR Compressor Energized Same as diagnostic 198, but for Cprsr C. 19b Low Oil Flow - Compressor D CMR Compressor Energized Same as diagnostic 198, but for Cprsr D. 19C Phase Loss Compressor A CMR Compressor Energized a. No current was sensed on one or more of the current transformer inputs. (Must hold = 20% RLA. Must trip = 5% RLA.) Time to trip shall be I second minimum and 3 seconds maximum. 19d Phase Loss Compressor B CMR Same as 19C Same as diagnostics 19C 19E Phase Loss Compressor C CMR Same as 19C Same as diagnostics 19C 19F Phase Loss Compressor D CMR Same as 19C Same as diagnostics 19C 1A0 Power Loss Compressor A CAR All Running Modes a. The compressor was running and all three phases of current were lost. b. There was an open Transition input after transition had been previously proven to have been complete. c. There was an incomplete Transition on the first check after transition and all three phases of current here not present. 1A1 Power Loss - Compressor B CAR Same as 1A0 Same as diagnostic 1A0. 1A2 Power Loss - Compressor C CAR Same as 1A0 Same as diagnostic 1A0. 1A3 Power Loss - Compressor D CAR Same as 1A0 Same as diagnostic 1A0.
114RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 1A4 Remote Communications Loss IFW All AUTO/REMOTE Modes a. While the chiller switch was in the AUTO/REMOTE the communication between the CSR and the connected remote device, e.g. a Tracer or Remote Display, had either never been established for more than 15 minutes after power up or was lost for more than 15 minutes after it had been established; use the Front Panel Setpoints and the Default Chiller Auto/ Stop. All AUTO/LOCAL and all b. In AUTO/LOCAL communications had STOP/RESET modes been established and was then lost for more than 15 minutes. Regardless of the remote communication status the UCM uses Front Panel setpoints. NOTE: The active modes for diagnostic 1A4 follows the positions of the chiller switch which account for other chiller codes. 1A5 Oil Flow Control - Compressor A CMR Pre-Stop a. At the time the 20 second Run: Unload time times out, the UCM will de-energize the oil line solenoid and set a 10+ or -1 second timer. As soon as the differential pressure switch opens (0.8 to 1.2 sec.) the compressor will be de-energized and the sequence ended. If the differential pressure switch does not open within 10 seconds, the compressor shall be de- energized and a CMR diagnostic generated not permitting the compressor to restart. Whenever the fan control pressure differential is below 70 PSID, or if a diagnostic shutdown occurs, the above shutdown test will not be executed. The above test will serve to check the differential pressure switch, the switch wiring to the UCM, and closure of the oil line solenoid. 1A6 Oil Flow Control - CMR Pre-Stop Same as diagnostic 1A5. Compressor B 1A7 Oil Flow Control - CMR Pre-Stop Same as diagnostic 1A5. Compressor C 1A8 Oil Flow Control - CMR Pre-Stop Same as diagnostic 1A5. Compressor D 1A9 EXV Electrical Drive Circuit CMR Pre-Start and On Demand a. Wiring between the EXV and the UCM (Rfgt. Circuit 1) is “Open”. Check the connector for proper termination. b. EXV motor is faulty. c. EXV drive circuits on Module 1U3 are faulty. 1AA EXV Electrical Drive Circuit CMR Pre-Start and On Demand Same as diagnostic 1A9. (Rfgt. Circuit 2) NOTE: For similar diagnostics for the Slaved EXV Drive Circuits see Codes 1 db and 1 dC.
115RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 1Ad Memory Error Type I IFW UCM Power Up or a. On UCM power up or following a Following a Type II Type II Memory Error a NOVRAM Memory Error memory error was detected. The UCM is operating on all Engineering ROM defaults for all setup parameters. Check all I setup parameters and continue to run chiller. Replace the Chiller Module as soon as a replacement is available. 1AE Low Diff. Pressure - Circuit 1 CMR Compressor Energized a. The fan control algorithm detected a low differential temperature/ pressure condition that existed for more than 180 contiguous seconds. The trip- point is 40 PSID. 1AF Low Diff. Pressure - Circuit 2 CMR Compressor Energized Same as diagnostic 1AE. 1b2 Severe Phase Unbalance - CMR All Running Modes a. A 30% Phase Unbalance diagnostic Compressor A has been detected. The 15% Phase Unbalance criteria has been defeated. Items to check are the Current Transformer Part Numbers (they should all match), The Current Transformer resistances, line voltage phase balance, all power wiring connections, the contactor pole faces, and the motor. 1b3 Severe Phase Unbalance - CMR All Running Modes Same as diagnostic 1b2. Compressor B 1b4 Severe Phase Unbalance - CMR All Running Modes Same as diagnostic 1b2. Compressor C 1b5 Severe Phase Unbalance - CMR All Running Modes Same as diagnostic 1b2. Compressor D 1b6 Overload Setting - IFW All a. The CPM NovRam Based overload Compressor A setting did not agree with the MCSP Dip Switch overload setting for 30 contiguous seconds. The affected MCSP shall use the minimum (00000 binary, 00 decimal) overload setting as a default until the UCM is reset when this diagnostic occurs. 1b8 Overload Setting - IFW All Same as diagnostic 1b6. Compressor C 1b9 Overload Setting - IFW All Same as diagnostic 1b6. Compressor D 1bA Phase Unbalance - CMR All Running Modes a. A 15% phase unbalance has been Compressor A detected. Menu Item “47” is enabled. 1bb Phase Unbalance - CMR All Running Modes Same as diagnostic 1bA. Compressor B 1bC Phase Unbalance - CMR All Running Modes Same as diagnostic 1bA. Compressor C 1bd Phase Unbalance - CMR All Running Modes Same as diagnostic 1bA. Compressor D
116RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 1bE Winding Temp.- Compressor A CMR All a. The motor winding temperature thermostat opened; nominally 221 F. b. The motor temperature thermostat or wiring is open. c. Time to trip from input open to compressor shutdown shall be 0.5 to 2.0 seconds. 1bF Winding Temp.- Compressor B CMR All Same as diagnostic 1bE. 1C0 Winding Temp.- Compressor C CMR All Same as diagnostic 1bE. 1C1 Winding Temp.- Compressor D CMR All Same as diagnostic 1bE. 1C2 Discharge Temp.- Compressor A CMR All a. The discharge temperature exceeded the trip value of 275 F. b. The discharge temperature PTC or wiring is open. Note: on units built in 1992 and later, the discharge temp sensor will not be present. 1C3 Discharge Temp. - Compressor B CMR All Same as diagnostic 1C2. 1C4 Discharge Temp. - Compressor C CMR All Same as diagnostic 1C2. IC5 Discharge Temp. - Compressor D CMR All Same as diagnostic 1C2. 1C6 High Diff. Pressure - Circuit 1 CMR Compressor Energized a. The difference between the condenser pressure and the evaporator pressure exceeded 350 PSID for 0.8 to 5.0 seconds. 320 PSID must hold, 320+ to trip for 1 hour. 1C7 High Diff. Pressure - Circuit 2 CMR Compressor Energized Same as diagnostic 1C6. 1d1 Memory Error Type II IFW All a. A Shadow RAM memory error was detected. The UCM is operating on all last valid values (pulled from NOVRAM) for all setup parameters. No setup parameter changes were pending to be loaded into NOVRAM, a complete recovery of all setup parameters was made and there is no need to check unit setup parameters. Compressor starts and hours were lost for not more than the last 24 hours. This is expected to be an isolated event and repair or replacement is not required. 1d2 Memory Error Type III IFW All a. A Shadow RAM memory error was detected. The UCM is operating on all last valid values (pulled from NOVRAM) for all setup parameters. Setup parameter changes less than 24 hours old pending to be loaded into NOVRAM were lost. Check all setup parameters made in last 24 hours. Compressor starts and hours were lost for not more than 24 hours. This is expected to be an isolated event and repair or replacement is not required.
117RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 1d3 Comp. Suction Temp. Sensor - CMR All a . Open or Short in sensor electrical Circuit 1 circuitry. 1d4 Comp. Suction Temp. Sensor - CMR All a. Open or Short in sensor electrical Circuit 2 circuitry. 1d7 Phase Reversal Protection Lost - CMR Compressor Energized to a. The phase reversal protection Compressor A To Transition Command Compressor A has become inoperative. The phase rotation protection system failed to detect two in a row of one of the four phase circuit states; Phase reversal, Phase Rotation OK, Phase A lost, Phase B lost. 1d8 Phase Reversal Protection Lost - CMR Compressor Energized to Same as diagnostic 1d7. Compressor B Transition Command 1d9 Phase Reversal Protection Lost - CMR Compressor Energized to Same as diagnostic 1d7. Compressor C Transition Command 1dA Phase Reversal Protection Lost - CMR Compressor Energized to Same as diagnostic 1d7. Compressor D Transition Command 1db Slaved EXV Elec. Drive Circuit - CMR On Demand and a. Wiring between the EXV and the UCM Refrigerant Circuit I Pre-Start is “Open”. Check the connector for proper termination. b. EXV motor is faulty. c. EXV drive circuits on Module 1U3 are faulty 1dC Slaved EXV Elec. Drive Circuit CMR On Demand and Same as diagnostic 1db. Also refer to Refrigerant Circuit 2 Pre-Start diagnostics 1A9 and 1AA. 412 1U1 Indicating IFW All The 1U1 Module has detected a loss of 1U2 Communications inter-processor communications from the 1U2 Module. 413 1U1 Indicating MMR All The 1U1 Module has detected a loss of 1U3 Communications inter-processor communications from the 1U3 Module. 414 1U1 Indicating CMR All The 1U1 Module has detected a loss of 1U4 Communications inter-processor communications from the 1U4 Module. 415 1U1 Indicating CMR All The 1U1 Module has detected a loss of 1U5 Communications inter-processor communications from the 1U5 Module. 416 1U1 Indicating CMR All The 1U1 Module has detected a loss of 1U6 Communications inter-processor communications from the 1U6 Module. 417 1U1 Indicating CMR All The 1U1 Module has detected a loss of 1U7 Communications inter-processor communications from the 1U7 Module. 418 1U1 Indicating CMR All The 1U1 Module has detected a loss of 1U8 Communications inter-processor communications from the 1U8 Module. 431 1U3 Indicating MMR All The 1U3 Module has detected a loss of 1U1 Communications inter-processor communications from the 1U1 Module. 434 1U3 Indicating CMR All The 1U3 Module has detected a loss of 1U4 communications inter-processor communications from the 1U4 Module.
118RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 435 1U3 Indicating CMR All The 1U3 Module has detected a loss of 1U5 Communications inter-processor communications from the 1U5 Module. 436 1U3 Indicating CMR All The 1U3 Module has detected a loss of 1U6 Communications inter-processor communications from the 1U6 Module. 437 1U3 Indicating CMR All The 1U3 Module has detected a loss of 1U7 Communications. inter-processor communications from .the 1U7 Module. 441 1U4 Indicating CMR All The 1U4 Module has detected a loss of 1U1 Communications inter-processor communications from the 1U1 Module. 443 1U4 Indicating CMR All The 1U4 Module has detected a loss of 1U3 Communications inter-processor communications from the 1U3 Module. 445 1U4 Indicating CMR All The 1U4 Module has detected a loss of 1U5 Communications . inter-processor communications from the 1U5 Module. 451 1U5 Indicating CMR All The 1U5 Module has detected a loss of 1U1 Communications inter-processor communications from the 1U1 Module. 453 1U5 Indicating CMR All The 1U5 Module has detected a loss of 1U3 Communications inter-processor communications from the 1U3 Module. 454 1U5 Indicating CMR All The 1U5 Module has detected a loss of 1U4 Communications inter-processor communications from the 1U4 Module. 461 1U6 Indicating CMR All The 1U6 Module has detected a loss of 1U1 Communications inter-processor communications from the 1U1 Module. 463 1U6 Indicating CMR All The 1U6 Module has detected a loss of 1U3 Communications inter-processor communications from the 1U3 Module. 467 1U6 Indicating CMR All The 1U6 Module has detected a loss of 1U7 Communications inter-processor communications from the 1U7 Module. 471 1U7 Indicating CMR All The 1U7 Module has detected a loss of 1U1 Communications inter-processor communications from the 1U1 Module. 473 1U7 Indicating CMR All The 1U7 Module has detected a loss of 1U3 Communications inter-processor communications from the 1U3 Module. 476 1U7 Indicating CMR All The 1U7 Module has detected a loss of 1U6 Communications inter-processor communications from the 1U6 Module.
119RTAA-IOM-3 Table 18 Diagnostics and Troubleshooting Chart (Continued) DIAG. ACTIVE CODE DIAGNOSTIC DESCRIPTION TYPE MODES CAUSE 481 1U8 Indicating MMR All The 1U8 Module has detected a loss of 1U1 Communications inter-processor communications from the 1U1 Module. 483 1U8 Indicating CMR* All The 1U8 Module has detected a loss of 1U3 Communications inter-processor communications from the 1U3 Module. 484 1U8 Indicating CMR All The 1U8 Module has detected a loss of 1U4 Communications inter-processor communications from the 1U4 Module. 485 1U8 Indicating CMR All The 1U8 Module has detected a loss of 1U5 Communications inter-processor communications from the 1U5 Module. 486 1U8 Indicating CMR All The 1U8 Module has detected a loss of 1U6 Communications inter-processor communications from the 1U6 Module. 487 1U8 Indicating CMR All The 1U8 Module has detected a Ioss of 1U7 Communications inter-processor communications from the 1U7 Module. *In the event of this communication diagnostic, CMR(s) will be generated for the circuit(s) which are using the Slaved EXV (i.e. those circuits which are employing a parallel valve arrangement).