Trane Rtaaiom3 Manual
Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
61RTAA-IOM-3 Figure 35 Typical Field Wiring for RTAA Packaged Unit – 240-400 Tons(Continued on Next Page)
62RTAA-IOM-3 Figure 35 (Continued from Previous Page) Typical Field Wiring for RTAA Packaged Unit – 240-400 Tons(Continued on Next Page) See Notes on Previous Page
63RTAA-IOM-3 (Continued from Previous Page) See Notes on Page 61
64RTAA-IOM-3 Figure 36 Typical Field Wiring for RTAA With Remote Evaporator Option(Continued on Next Page)
65RTAA-IOM-3 (Continued from Previous Page) See Notes on Page 61
66RTAA-IOM-3 Figure 36 (Continued from Previous Page) Typical Field Wiring for RTAA With Remote Evaporator Option
67RTAA-IOM-3 Table 10 Electrical Data Unit Wiring Motor DataFans (Ea)Rated MCA (3) Rec Time Comp. (Ea) Qty. Qty. Unit Size Voltage Ckt1/Ckt2(1) MOP(2) Delay or RDE4) Qty. RLA(5) LRA(8) (11) (12) kW FLA kW(7) RTAA 130 200 383/389 600/600 500/500 2 280/280 1689/1689 10 11 1.3 6.5 0.8 230 383/389 600/600 500/500 2 280/280 1689/1689 10 11 1.3 6.5 0.8 460 306 400 350 2 122/122 633/633 10 11 1.3 2.8 0.8 575 246 300 300 2 98/98 512/512 10 11 1.3 2.3 0.8 RTAA 140 200 383/389 600/600 500/500 2 280/280 1689/1689 10 11 1.3 6.5 0.8 230 383/389 600/600 500/500 2 280/280 1689/1689 10 11 1.3 6.5 0.8 460 306 400 350 2 122/122 633/633 10 11 1.3 2.8 0.8 575 246 300 300 2 98/98 512/512 10 11 1.3 2.3 0.8 RTAA 155 200 422/389 700/600 500/500 2 306/280 2044/1689 11 12 1.3 6.5 0.8 230 422/389 700/600 500/500 2 306/280 2044/1689 11 12 1.3 6.5 0.8 460 322 450 400 2 133/122 766/633 11 12 1.3 2.8 0.8 575 260 350 300 2 107/98 611/512 11 12 1.3 2.3 0.8 RTAA 170 200 515/389 800/600 700/500 2 375/280 2391/1689 12 13 1.3 6.5 0.8 230 515/389 800/600 700/500 2 375/280 2391/1689 12 13 1.3 6.5 0.8 460 363 500 450 2 163/122 896/633 12 13 1.3 2.8 0.8 575 292 400 350 2 131/987 25/512 12 13 1.3 2.3 0.8 RTAA 185 200 515/428 800/700 700/600 2 375/306 2391/2044 13 14 1.3 6.5 0.8 230 515/428 800/700 700/600 2 375/306 2391/2044 13 14 1.3 6.5 0.8 460 376 500 450 2 163/133 896/766 13 14 1.3 2.8 0.8 575 303 400 350 2 131/107 725/611 13 14 1.3 2.3 0.8 RTAA 200 200 514/514 800/800 700/700 2 375/375 2391/2391 14 14 1.3 6.5 0.8 230 514/514 800/800 7001700 2 375/375 2391/2391 14 14 1.3 6.5 0.8 460 406 500 450 2 163/163 896/896 14 14 1.3 2.8 0.8 575 327 450 400 2 131/131 725/725 14 14 1.3 2.3 0.8 RTAA 240 460 303/224 400/350 350/300 3 122-122/163 633-633/896 N/A 17 1.3 2.8 1.0 575 244/180 300/300 300/225 3 98-98/131 512-512/725 N/A 17 1.3 2.3 1.0 RTAA 270 460 360/224 500/350 450/300 3 163-122/163 896-633/896 N/A 19 1.3 2.8 1.0 575 290/180 400/300 350/225 3 131-98/131 725-512/725 N/A 19 1.3 2.3 1.0 RTAA 300 460 406/224 500/350 450/300 3 163-163/163 896-896/896 N/A 21 1.3 2.8 1.0 575 327/180 450/300 400/225 3 131-131/131 725-725/725 N/A 21 1.3 2.3 1.0 RTAA 340 460 303/406 400/500 350/450 4 122-122/163-163 633-633/896-896 N/A 24 1.3 2.8 1.0 575 244/327 300/450 300/400 4 98-98/131-131 512-512/725-725 N/A 24 1.3 2.3 1.0 RTAA 370 460 360/406 500/500 450/450 4 163-122/163-163 896-633/896-896 N/A 26 1.3 2.8 1.0 575 290/327 400/450 350/400 4 131-98/131-131 725-512/725-725 N/A 26 1.3 2.3 1.0 RTAA 400 460 406/406 500/500. 450/450 4 163-163/163-163 896-896/896-896 N/A 28 1.3 2.8 1.0575 327/327 450/450 400/400 4 131-131/131-131 725-725/725-725 N/A 28 1.3 2.3 1.0 Notes: (1) Low voltage units (200 & 230 volt) require separate power connections for each circuit. (2) MOP - Maximum Overcurrent Protection - may be either fused (UL/CSA) or with circuit breakers (CSA only). MOP = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA plus the sum of the condenser fans FLAs per NEC 440-22. (3) MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of second compressor plus the sum of the condenser fans FLAs per NEC 440-33. (4) RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the second compressor RLA and the sum of the condenser tan FLAs. (5) RLA - Rated Load Amps - rated in accordance with UL Standard 465. (6) Local codes may take precedence. (7) Control kW includes operational controls only. Does not include heat tapes. (8) LRA - Locked Rotor Amps - based on full winding start units. (9) VOLTAGE UTILIZATION RANGE: Rated Voltage Utilization Range 200 180-220 230 208-254 460 414-506 575 516.633 (10) A 11 5/60/1, 15 amp. customer provided power connection is required to operate the unit controls. A separate 115(60/1, 15 amp. customer provided power connection is also needed to power the evaporator heat tape (RTAA 130-200 = 420 watts, RTAA 240-400 = 840 wafts @ 120 volts) and optional Domestic Water Heater (420 watts @ 120 volts.). If the optional control power is used, the customer needs only to provide a power connection for the heat tapes. (11) 15 F minimum starting/operating ambient. (12) 0 F minimum starting/operating ambient
68RTAA-IOM-3 CAUTION: IT IS IMPERATIVE THAT L1-L2-L3 IN THE STARTER BE CONNECTED IN THE A-B-C PHASE SEQUENCE TO PREVENT EQUIPMENT DAMAGE DUE TO REVERSE ROTATION. Installer-Supplied Components Caution: Customer wiring interface connections are shown in the electrical schematics and connection diagrams that are shipped with the unit. The installer must provide the following components if not ordered with the unit: [ ] Power supply wiring (in conduit) for all field-wired connections. [ ] All control (interconnecting) wiring (in conduit) for field supplied devices. [ ] Fused-disconnect switches. [ ] Power factor correction capacitors. Remote Evaporator Only:Control wiring between the outdoor unit and the evaporator terminal box. Power Supply Wiring General All power supply wiring must be sized and selected accordingly by the project engineer in accordance with NEC Table 31016. WARNING: To prevent injury or death, disconnect electrical power source before completing wiring connections to the unit. All wiring must comply with local codes and the National Electrical Code. The installing (or electrical) contractor must provide and install the system interconnecting wiring, as well as-the power supply wiring. It must be properly sized and equipped with the appropriate fused disconnect switches. The type and installation location(s) of the fused disconnects must comply with all applicable codes. Caution: Use only copper conductors for terminal connections to avoid corrosion or overheating. Remove the plate on the lower right side of the power connection panel and cut holes for the appropriately-sized wiring conduits. The wiring is passed through these conduits and connected to the terminal blocks or optional unit- mounted disconnect. Refer to Figure 1 and Figures 34 thru 36. To provide proper phasing of 3-phase input, make connections as shown in Figures 34 thru 36 and as stated on the yellow WARNING label in the starter panel. For additional information on proper phasing, refer to “Unit Voltage Phasing Proper equipment ground must be provided to each ground connection in the panel (one on 460/ 575 volt units and two on 200/230 volt units). Control Power Supply If the unit is equipped with the optional control power transformer, it is not necessary to provide control power voltage to the unit. Caution: 200/230 volt units are factory connected as 200 volt units. For 230 volt units, the leads must be moved to the appropriate terminals on the transformer (1T1). See Unit Wiring Diagrams. If the transformer is not provided, connect control power (115V, 750VA, 15 amp maximum fuse size) to terminals 1TB3-1 and 1TB3-2, on 130-200 units. Use 1TB3-1 and 1TB4-1 on 240-400 units. Heat Tape Power Supply (Packaged Units Only) Note: Units with the Remote Evaporator option do not have heat tape. The evaporator shell and optional Domestic Water Heater are insulated from ambient air and protected from freezing temperatures by a thermostatically-controlled heat tape. Whenever the water temperature drops to approximately 37 F, the thermostat energizes the heat tape. The heat tape will provide protection from ambient temperatures down to -20 F. Provide an independent power source (115V, 15 amp), with a fused- disconnect. The heat tape is factory wired back to the unit control panel. Customer connections are made on terminal strip 1TB3-11 and 1TB3-12 on 130-200 units or 1TB3-10 and 1TB4-1 0 on 240-400 units. Water Pump Power Supply Provide power supply wiring with fused disconnect for the chilled water pump(s). Auxiliary Heat Tape Power Supply Provide power wiring and properly sized fused-disconnect for any electrical heat tape installed on the system water piping.
69RTAA-IOM-3 Interconnecting Wiring Chilled Water Pump Interlock and External Auto/Stop for Model RTAA Air-Cooled Series R CenTraVac Caution: The following must be adhered to or equipment damage may occur. The Model RTAA Series R chiller requires a minimum of two field- supplied control inputs: • Chilled water pump interlock (TB3-1, - 2 on the 1U1 board). • External Auto/Stop (T133-3, -4 on the 1U1 board) When there is a command to shut down the chilled water system, the chilled water pump is required to operate for a minimum of one minute after the External AUTO/STOP gives the shutdown command. Normally, when the compressors are terminating a cycle (via chiller Stop/ Reset switch, loss of load, Low Ambient Run Inhibit or External Auto/ Stop), the controller will initiate the “Run:Unload” mode. This operating mode energizes the unload solenoid for 20 seconds, to unload the compressor so that it will be unloaded for the next start-up. Then the master oil solenoid is de-energized and closure of the master oil solenoid is verified. The entire process may take up to 40 seconds. If the chilled water pump interlock is used without the external Auto/Stop input, the chiller will shut down immediately upon the command for shut down, without initiating the “Run:Unload” mode. This is considered a “non-friendly” shut down and a “Machine Auto Reset” diagnostic will be displayed on the LICK Caution: The method in the previous paragraph is not to be used as a normal means of cycling the chiller off, e.g. time clock, building automation system, etc. The proper method for cycling the chiller off is to open a set of contact between TB3-3, -4 on the 1U1 board (External Auto/Stop). Then, following a one minute delay, the chilled water pump is cycled off. Chilled water flow indication should be provided between TB3-1, -2 on the 1U1 board, e.g. water pump motor starter auxiliaries and/or flow switch.The wiring for this recommendation is shown in the furnished electrical schematics and connection diagrams. Relay 5DL1 is a normally-open, instantaneous close, timed open (1 min.) time delay relay. An alternative solution is to provide proper programming in a building automation system. Chilled Water Pump Interlock The installer must provide leads 520 and 521 from the chilled water pump (5B1) starter auxiliary (5K1) to the proper terminals of terminal strip 1U1 TB3 on the UCM, as shown in Figures 34 thru 36. Circuit requirement is 115 VAC, with minimum contact rating @ 115 VAC of 6.9 VA inrush, 1.3 VA sealed. Refer to the field diagrams which are shipped with the unit. The auxiliary contact of the chilled water pump may be wired in series with an optional flow switch, as shown. The standard UCM provides internal protection for the unit against loss of chilled water flow. Also refer to “Evaporator Flow Switch.” External Auto/Stop Wiring If the unit requires the Auto/Stop function, the installer must provide leads 522 and 523 from the remote contacts (5K5, 5K21) to the proper terminals of the terminal strip 1U1 TB3 on the UCM, as shown in Figures 34 thru 36. The chiller will run normally when the contacts are closed. When either contact opens, the compressor(s), if operating, will go to the RUN:UNLOAD operating mode and cycle off. Unit operation will be inhibited. Re-closure of the contacts will permit the unit to automatically return to normal operation. Circuit requirements are 2-wire, 115 VAC, with minimum contact rating @ 115 VAC of 6.9 VA inrush, 1.3 VA sealed. Refer to the field diagrams which are shipped with the unit.
70RTAA-IOM-3 Alarm/Running/Maximum Capacity Outputs Terminals 1 to 8 on terminal strip TB4 of the 1U1 board provide a variety of contact outputs. These are dependent upon the setting of Menu Item 4E and its relationship to diagnostics, compressors operating and the system operating at full capacity. Table 11 Alarm/Running/Maximum Capacity Relay Output Configurations Relay Output Configuration1: RLY 1 = Alarm RLY 2 = Compressor Running RLY 3 = Maximum Capacity 2: RLY 1 = Circuit I Alarm RLY 2 = Circuit 2 Alarm RLY 3 = Maximum Capacity 3: RLY 1 = Alarm RLY 2 = Circuit 1 Running RLY 3 = Circuit 2 Running As shown in Figure 37, there are three relays. Relays 1 and 2 have SPDT contacts. Relay 3 has SPST normally open contacts. The relays can provide three different output configurations, as shown in Table 11, and each configuration offers four choices as to how the alarm relay is to respond to a set of diagnostics. Table 12 shows the twelve settings available in Menu Item 4E and the diagnostics which are issued for each set of conditions. Figure 37 Alarm/Running/Maximum Capacity Contact Outputs Table 12 Alarm/Running/Maximum Capacity Menu Settings Diagnostics that the Relays Output Alarm Relay(s) is Active Menu Item 4E Configuration MMR/ MAR/ Setting (Table 11) CMR diag. CAR diag. IFW diag. 1 1 YES NO NO 2 1 YES YES NO 3 1 YES YES YES 4 1 YES NO YES 5 2 YES NO NO 6 2 YES YES NO 7 2 YES YES YES 8 2 YES NO YES 9 3 YES NO NO 10 3 YES YES NO 11 3 YES YES YES 12 3 YES NO YES Notes: MMR = Machine Manual Reset CMR = Circuit Manual Reset MAR = Machine Auto Reset CAR = Circuit Auto Reset IFW = Informational Warnings