Home > Trane > Cooler > Trane Rtaaiom3 Manual

Trane Rtaaiom3 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							61RTAA-IOM-3
    Figure 35
    Typical Field Wiring for
    RTAA Packaged Unit –
    240-400 Tons(Continued on Next Page) 
    						
    							62RTAA-IOM-3
    Figure 35 (Continued from Previous Page)
    Typical Field Wiring for
    RTAA Packaged Unit –
    240-400 Tons(Continued on Next Page)
    See Notes on Previous Page 
    						
    							63RTAA-IOM-3
    (Continued from Previous Page)
    See Notes on Page 61 
    						
    							64RTAA-IOM-3
    Figure 36
    Typical Field Wiring for
    RTAA With Remote
    Evaporator Option(Continued on Next Page) 
    						
    							65RTAA-IOM-3
    (Continued from Previous Page)
    See Notes on Page 61 
    						
    							66RTAA-IOM-3
    Figure 36 (Continued from Previous Page)
    Typical Field Wiring for
    RTAA With Remote
    Evaporator Option 
    						
    							67RTAA-IOM-3
    Table 10
    Electrical Data
    Unit Wiring Motor DataFans (Ea)Rated MCA (3) Rec Time Comp. (Ea) Qty. Qty.
    Unit Size Voltage Ckt1/Ckt2(1) MOP(2) Delay or RDE4) Qty. RLA(5) LRA(8) (11) (12) kW FLA kW(7)
    RTAA 130 200 383/389 600/600 500/500 2 280/280 1689/1689 10 11 1.3 6.5 0.8
    230 383/389 600/600 500/500 2 280/280 1689/1689 10 11 1.3 6.5 0.8
    460 306 400 350 2 122/122 633/633 10 11 1.3 2.8 0.8
    575 246 300 300 2 98/98 512/512 10 11 1.3 2.3 0.8
    RTAA 140 200 383/389 600/600 500/500 2 280/280 1689/1689 10 11 1.3 6.5 0.8
    230 383/389 600/600 500/500 2 280/280 1689/1689 10 11 1.3 6.5 0.8
    460 306 400 350 2 122/122 633/633 10 11 1.3 2.8 0.8
    575 246 300 300 2 98/98 512/512 10 11 1.3 2.3 0.8
    RTAA 155 200 422/389 700/600 500/500 2 306/280 2044/1689 11 12 1.3 6.5 0.8
    230 422/389 700/600 500/500 2 306/280 2044/1689 11 12 1.3 6.5 0.8
    460 322 450 400 2 133/122 766/633 11 12 1.3 2.8 0.8
    575 260 350 300 2 107/98 611/512 11 12 1.3 2.3 0.8
    RTAA 170 200 515/389 800/600 700/500 2 375/280 2391/1689 12 13 1.3 6.5 0.8
    230 515/389 800/600 700/500 2 375/280 2391/1689 12 13 1.3 6.5 0.8
    460 363 500 450 2 163/122 896/633 12 13 1.3 2.8 0.8
    575 292 400 350 2 131/987 25/512 12 13 1.3 2.3 0.8
    RTAA 185 200 515/428 800/700 700/600 2 375/306 2391/2044 13 14 1.3 6.5 0.8
    230 515/428 800/700 700/600 2 375/306 2391/2044 13 14 1.3 6.5 0.8
    460 376 500 450 2 163/133 896/766 13 14 1.3 2.8 0.8
    575 303 400 350 2 131/107 725/611 13 14 1.3 2.3 0.8
    RTAA 200 200 514/514 800/800 700/700 2 375/375 2391/2391 14 14 1.3 6.5 0.8
    230 514/514 800/800 7001700 2 375/375 2391/2391 14 14 1.3 6.5 0.8
    460 406 500 450 2 163/163 896/896 14 14 1.3 2.8 0.8
    575 327 450 400 2 131/131 725/725 14 14 1.3 2.3 0.8
    RTAA 240 460 303/224 400/350 350/300 3 122-122/163 633-633/896 N/A 17 1.3 2.8 1.0
    575 244/180 300/300 300/225 3 98-98/131 512-512/725 N/A 17 1.3 2.3 1.0
    RTAA 270 460 360/224 500/350 450/300 3 163-122/163 896-633/896 N/A 19 1.3 2.8 1.0
    575 290/180 400/300 350/225 3 131-98/131 725-512/725 N/A 19 1.3 2.3 1.0
    RTAA 300 460 406/224 500/350 450/300 3 163-163/163 896-896/896 N/A 21 1.3 2.8 1.0
    575 327/180 450/300 400/225 3 131-131/131 725-725/725 N/A 21 1.3 2.3 1.0
    RTAA 340 460 303/406 400/500 350/450 4 122-122/163-163 633-633/896-896 N/A 24 1.3 2.8 1.0
    575 244/327 300/450 300/400 4 98-98/131-131 512-512/725-725 N/A 24 1.3 2.3 1.0
    RTAA 370 460 360/406 500/500 450/450 4 163-122/163-163 896-633/896-896 N/A 26 1.3 2.8 1.0
    575 290/327 400/450 350/400 4 131-98/131-131 725-512/725-725 N/A 26 1.3 2.3 1.0
    RTAA 400 460 406/406 500/500. 450/450 4 163-163/163-163 896-896/896-896 N/A 28 1.3 2.8 1.0575 327/327 450/450 400/400 4 131-131/131-131 725-725/725-725 N/A 28 1.3 2.3 1.0
    Notes:
    (1) Low voltage units (200 & 230 volt) require separate power connections for each circuit.
    (2) MOP - Maximum Overcurrent Protection - may be either fused (UL/CSA) or with circuit breakers (CSA only).
    MOP = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA plus the sum of the condenser fans
    FLAs per NEC 440-22.
    (3) MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of second compressor plus the sum of the
    condenser fans FLAs per NEC 440-33.
    (4) RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the
    second compressor RLA and the sum of the condenser tan FLAs.
    (5) RLA - Rated Load Amps - rated in accordance with UL Standard 465.
    (6) Local codes may take precedence.
    (7) Control kW includes operational controls only. Does not include heat tapes.
    (8) LRA - Locked Rotor Amps - based on full winding start units.
    (9) VOLTAGE UTILIZATION RANGE:
    Rated Voltage Utilization Range
    200 180-220
    230 208-254
    460 414-506
    575 516.633
    (10) A 11 5/60/1, 15 amp. customer provided power connection is required to operate the unit controls. A separate 115(60/1, 15 amp. customer
    provided power connection is also needed to power the evaporator heat tape (RTAA 130-200 = 420 watts, RTAA 240-400 = 840 wafts @
    120 volts) and optional Domestic Water Heater (420 watts @ 120 volts.). If the optional control power  is used, the customer needs only to
    provide a power connection for the heat tapes.
    (11) 15 F minimum starting/operating ambient.
    (12) 0 F minimum starting/operating ambient 
    						
    							68RTAA-IOM-3
     CAUTION:
    IT IS IMPERATIVE THAT
    L1-L2-L3 IN THE STARTER BE
    CONNECTED IN THE A-B-C
    PHASE SEQUENCE TO
    PREVENT EQUIPMENT
    DAMAGE DUE TO REVERSE
    ROTATION.
    Installer-Supplied
    Components
    Caution: Customer wiring interface
    connections are shown in the
    electrical schematics and
    connection diagrams that are
    shipped with the unit.
    The installer must provide the
    following components if not ordered
    with the unit:
    [  ] Power supply wiring (in conduit) for
    all field-wired connections.
    [  ] All control (interconnecting) wiring
    (in conduit) for field supplied
    devices.
    [  ] Fused-disconnect switches.
    [  ] Power factor correction capacitors.
    Remote Evaporator Only:Control wiring between the outdoor
    unit and the evaporator terminal box.
    Power Supply Wiring
    General
    All power supply wiring must be sized
    and selected accordingly by the project
    engineer in accordance with NEC Table
    31016.
    WARNING: To prevent injury or
    death, disconnect electrical
    power source before completing
    wiring connections to the unit.
    All wiring must comply with local
    codes and the National Electrical Code.
    The installing (or electrical) contractor
    must provide and install the system
    interconnecting wiring, as well as-the
    power supply wiring. It must be
    properly sized and equipped with the
    appropriate fused disconnect switches.
    The type and installation location(s) of
    the fused disconnects must comply
    with all applicable codes.
    Caution: Use only copper
    conductors for terminal
    connections to avoid corrosion or
    overheating.
    Remove the plate on the lower right
    side of the power connection panel and
    cut holes for the appropriately-sized
    wiring conduits. The wiring is passed
    through these conduits and connected
    to the terminal blocks or optional unit-
    mounted disconnect. Refer to Figure 1
    and Figures 34 thru 36.
    To provide proper phasing of 3-phase
    input, make connections as shown in
    Figures 34 thru 36 and as stated on the
    yellow WARNING label in the starter
    panel. For additional information on
    proper phasing, refer to “Unit Voltage
    Phasing Proper equipment ground
    must be provided to each ground
    connection in the panel (one on 460/
    575 volt units and two on 200/230 volt
    units).
    Control Power Supply
    If the unit is equipped with the optional
    control power transformer, it is not
    necessary to provide control power
    voltage to the unit.
    Caution: 200/230 volt units are
    factory connected as 200 volt units.
    For 230 volt units, the leads must
    be moved to the appropriate
    terminals on the transformer (1T1).
    See Unit Wiring Diagrams.
    If the transformer is not provided,
    connect control power (115V, 750VA, 15
    amp maximum fuse size) to terminals
    1TB3-1 and 1TB3-2, on 130-200 units.
    Use 1TB3-1 and 1TB4-1 on 240-400
    units.
    Heat Tape Power Supply
    (Packaged Units Only)
    Note: Units with the Remote
    Evaporator option do not have heat
    tape.
    The evaporator shell and optional
    Domestic Water Heater are insulated
    from ambient air and protected from
    freezing temperatures by a
    thermostatically-controlled heat tape.
    Whenever the water temperature
    drops to approximately 37 F, the
    thermostat energizes the heat tape. The
    heat tape will provide protection from
    ambient temperatures down to -20 F.
    Provide an independent power source
    (115V, 15 amp), with a fused-
    disconnect. The heat tape is factory
    wired back to the unit control panel.
    Customer connections are made on
    terminal strip 1TB3-11 and 1TB3-12 on
    130-200 units or 1TB3-10 and 1TB4-1 0
    on 240-400 units.
    Water Pump Power Supply
    Provide power supply wiring with
    fused disconnect for the chilled water
    pump(s).
    Auxiliary Heat Tape Power Supply
    Provide power wiring and properly
    sized fused-disconnect for any electrical
    heat tape installed on the system water
    piping. 
    						
    							69RTAA-IOM-3
    Interconnecting Wiring
    Chilled Water Pump Interlock
    and External Auto/Stop for
    Model RTAA Air-Cooled
    Series R CenTraVac
    Caution: The following must be
    adhered to or equipment damage
    may occur.
    The Model RTAA Series R chiller
    requires a minimum of two field-
    supplied control inputs:
    • Chilled water pump interlock (TB3-1, -
    2 on the 1U1 board).
    • External Auto/Stop (T133-3, -4 on the
    1U1 board)
    When there is a command to shut
    down the chilled water system, the
    chilled water pump is required to
    operate for a minimum of one minute
    after the External AUTO/STOP gives
    the shutdown command.
    Normally, when the compressors are
    terminating a cycle (via chiller Stop/
    Reset switch, loss of load, Low
    Ambient Run Inhibit or External Auto/
    Stop), the controller will initiate the
    “Run:Unload” mode. This operating
    mode energizes the unload solenoid
    for 20 seconds, to unload the
    compressor so that it will be unloaded
    for the next start-up. Then the master
    oil solenoid is de-energized and closure
    of the master oil solenoid is verified.
    The entire process may take up to 40
    seconds.
    If the chilled water pump interlock is
    used without the external Auto/Stop
    input, the chiller will shut down
    immediately upon the command for
    shut down, without initiating the
    “Run:Unload” mode. This is
    considered a “non-friendly” shut down
    and a “Machine Auto Reset” diagnostic
    will be displayed on the LICK
    Caution: The method in the
    previous paragraph is not to be
    used as a normal means of cycling
    the chiller off, e.g. time clock,
    building automation system, etc.
    The proper method for cycling the
    chiller off is to open a set of contact
    between TB3-3, -4 on the 1U1 board
    (External Auto/Stop). Then, following a
    one minute delay, the chilled water
    pump is cycled off. Chilled water flow
    indication should be provided between
    TB3-1, -2 on the 1U1 board, e.g. water
    pump motor starter auxiliaries and/or
    flow switch.The wiring for this recommendation is
    shown in the furnished electrical
    schematics and connection diagrams.
    Relay 5DL1 is a normally-open,
    instantaneous close, timed open (1
    min.) time delay relay. An alternative
    solution is to provide proper
    programming in a building automation
    system.
    Chilled Water Pump Interlock
    The installer must provide leads 520
    and 521 from the chilled water pump
    (5B1) starter auxiliary (5K1) to the
    proper terminals of terminal strip 1U1
    TB3 on the UCM, as shown in Figures
    34 thru 36. Circuit requirement is 115
    VAC, with minimum contact rating @
    115 VAC of 6.9 VA inrush, 1.3 VA sealed.
    Refer to the field diagrams which are
    shipped with the unit.
    The auxiliary contact of the chilled
    water pump may be wired in series
    with an optional flow switch, as shown.
    The standard UCM provides internal
    protection for the unit against loss of
    chilled water flow. Also refer to
    “Evaporator Flow Switch.”
    External Auto/Stop Wiring
    If the unit requires the Auto/Stop
    function, the installer must provide
    leads 522 and 523 from the remote
    contacts (5K5, 5K21) to the proper
    terminals of the terminal strip 1U1 TB3
    on the UCM, as shown in Figures 34
    thru 36.
    The chiller will run normally when the
    contacts are closed. When either
    contact opens, the compressor(s), if
    operating, will go to the RUN:UNLOAD
    operating mode and cycle off. Unit
    operation will be inhibited. Re-closure
    of the contacts will permit the unit to
    automatically return to normal
    operation.
    Circuit requirements are 2-wire, 115
    VAC, with minimum contact rating @
    115 VAC of 6.9 VA inrush, 1.3 VA sealed.
    Refer to the field diagrams which are
    shipped with the unit. 
    						
    							70RTAA-IOM-3
    Alarm/Running/Maximum
    Capacity Outputs
    Terminals 1 to 8 on terminal strip TB4
    of the 1U1 board provide a variety of
    contact outputs. These are dependent
    upon the setting of Menu Item 4E and
    its relationship to diagnostics,
    compressors operating and the system
    operating at full capacity.
    Table 11
    Alarm/Running/Maximum
    Capacity Relay Output
    Configurations
    Relay Output Configuration1: RLY 1 = Alarm
    RLY 2 = Compressor Running
    RLY 3 = Maximum Capacity
    2: RLY 1 = Circuit I Alarm
    RLY 2 = Circuit 2 Alarm
    RLY 3 = Maximum Capacity
    3: RLY 1 = Alarm
    RLY 2 = Circuit 1 Running
    RLY 3 = Circuit 2 Running
    As shown in Figure 37, there are three
    relays. Relays 1 and 2 have SPDT
    contacts. Relay 3 has SPST normally
    open contacts. The relays can provide
    three different output configurations, as
    shown in Table 11, and each
    configuration offers four choices as to
    how the alarm relay is to respond to a
    set of diagnostics.
    Table 12 shows the twelve settings
    available in Menu Item 4E and the
    diagnostics which are issued for each
    set of conditions.
    Figure 37
    Alarm/Running/Maximum
    Capacity Contact Outputs
    Table 12
    Alarm/Running/Maximum Capacity Menu Settings
    Diagnostics that the
    Relays Output Alarm Relay(s) is Active
    Menu Item 4E Configuration MMR/ MAR/
    Setting (Table 11) CMR diag. CAR diag. IFW diag.
    1 1 YES NO NO
    2 1 YES YES NO
    3 1 YES YES YES
    4 1 YES NO YES
    5 2 YES NO NO
    6 2 YES YES NO
    7 2 YES YES YES
    8 2 YES NO YES
    9 3 YES NO NO
    10 3 YES YES NO
    11 3 YES YES YES
    12 3 YES NO YES
    Notes:
    MMR = Machine Manual Reset
    CMR = Circuit Manual Reset
    MAR = Machine Auto Reset
    CAR = Circuit Auto Reset
    IFW = Informational Warnings 
    						
    All Trane manuals Comments (0)