Home > Trane > Cooler > Trane Rtaaiom3 Manual

Trane Rtaaiom3 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							131RTAA-IOM-3
    Periodic
    Maintenance
    General
    Perform all maintenance procedures
    and inspections at the recommended
    intervals. This will prolong the life of
    the equipment and minimize the
    possibility of costly failures.
    Use an “Operator’s Log”, such as that
    shown in Figure 58, to record an
    operating history for the unit. The log
    serves as a valuable diagnostic tool for
    service personnel. By observing trends
    in operating conditions, an operator
    can anticipate and prevent problem
    situations before they occur.
    If the unit does not operate properly
    during maintenance inspections, refer
    to “Diagnostics and Troubleshooting”. 
    						
    							132RTAA-IOM-3
    Figure 58
    Operator’s Log 
    						
    							133RTAA-IOM-3
    Refrigerant Emission
    Control
    Evidence from environmental scientists
    indicates that the ozone in our upper
    atmosphere is being reduced, due to
    the release of CFC fully halogenated
    compounds.
    The Trane Company encourages every
    effort to eliminate, if possible, or
    vigorously reduce the emission of CFC,
    HCFC and HFC refrigerants into the
    atmosphere that result from
    installation, operation, routine
    maintenance, or major services on this
    equipment. Always act in a responsible
    manner to conserve refrigerants  for
    continued use, even when acceptable
    alternatives are available.
    Conservation and emission reduction
    can be accomplished by following
    recommended Trane operation,
    maintenance and service procedures,
    with specific attention to the following:
    1. Refrigerant used in any type of air
    conditioning or refrigerating
    equipment should be recovered for
    reuse, recovered and/or recycled for
    reuse, reprocessed (reclaimed), or
    properly destroyed, whenever it is
    removed from equipment. Never
    release refrigerant into the
    atmosphere.
    2. Always determine possible recycle or
    reclaim requirements of the
    recovered refrigerant before
    beginning recovery by any method.
    Questions about recovered
    refrigerants and acceptable
    refrigerant quality standards are
    addressed in ARI Standard 700.
    3. Use approved containment vessels
    and safety standards. Comply with
    all applicable transportation
    standards when shipping refrigerant
    containers.
    4. To minimize emissions while
    recovering refrigerant, use recycling
    equipment. Always attempt to use
    methods which will pull the lowest
    possible vacuum while recovering
    and condensing refrigerant into
    containment.
    5. When leak checking with trace
    refrigerant and nitrogen, use HCFC-
    22 (R-22), rather than CFC-12 (R-12)
    or any other fully halogenated
    refrigerants. Be aware of any new
    leak test methods which eliminate
    refrigerant as a trace gas.6. When cleaning system components
    or parts, avoid using CFC-11 (R-11) or
    CFC-113 (R-113). Refrigeration
    system
    cleanup methods which use filters and
    dryers are preferred. Do not use
    solvents which have ozone depletion
    factors. Properly dispose of used
    materials.
    7. Take extra care to properly maintain
    all service equipment that directly
    supports refrigeration service work,
    such as gauges, hoses, vacuum
    pumps and recycling equipment.
    8. Stay aware of unit enhancements,
    conversion refrigerants, compatible
    parts and manufacturer’s
    recommendations which will reduce
    refrigerant emissions and increase
    equipment operating efficiencies.
    Follow manufacturer’s specific
    guidelines for conversion of existing
    systems.
    9. In order to assist in reducing power
    generation emissions, always
    attempt to improve equipment
    performance with improved
    maintenance and operations that will
    help conserve energy resources.
    Weekly Maintenance
    After the unit has been operating for
    approximately 30 minutes and the
    system has stabilized, check the
    operating conditions and complete the
    procedures below:
    [  ] Check the evaporator refrigerant
    pressure (23) and the condenser
    refrigerant pressure (25) in Menu 2
    on the UCM. The pressures are
    referenced to sea level (114.6960
    psia).
    [  ] Check the liquid line sight glasses.
    The refrigerant flow past the sight
    glasses should be clear. Bubbles in
    the refrigerant indicate either low
    refrigerant charge or excessive
    pressure drop in the liquid line. A
    restriction in the line can sometimes
    be identified by a noticeable
    temperature differential between
    the two sides of the restriction. Frost
    may often form on the line at this
    point. Proper refrigerant charges are
    shown on Table 1.
    Caution: A clear sight glass alone
    does not mean that the system
    properly charged. Also check
    system superheat, subcooling, and
    unit operating pressures. 
    						
    							134RTAA-IOM-3
    [  ] If operating pressures and sight
    glass conditions seem to indicate
    refrigerant shortage, measure the
    system superheat and system
    subcooling. Refer to “System
    Superheat” and “System
    Subcooling”.
    [  ] If operating conditions indicate a
    refrigerant overcharge, remove
    refrigerant at the liquid line service
    valve. Allow refrigerant to escape
    slowly, to minimize oil loss. Do not
    discharge refrigerant into the
    atmosphere.
    WARNING: Do not allow
    refrigerant to directly contact
    skin or injury from frostbite may
    result.
    [  ] Inspect the entire system for
    unusual conditions and inspect the
    condenser coils for dirt and debris. If
    the coils are dirty, refer to “Coil
    Cleaning”.
    Monthly Maintenance
    [  ] Perform all weekly maintenance
    procedures.
    [  ] Measure and record the system
    superheat. Refer to “System
    Superheat”.
    [  ] Measure and record the system
    subcooling. Refer to “System
    Subcooling”.
    [  ] Manually rotate condenser fans to
    insure proper clearance on the fan
    openings.
    WARNING: Position all electrical
    disconnects in the “OPEN”
    position and lock them, to
    prevent injury or death due to
    electrical shock.
    Annual Maintenance
    [  ] Perform all weekly and monthly
    maintenance procedures.
    [  ] Check the oil level and refrigerant
    charge. Refer to “Maintenance
    Procedures”.
    [  ] Have a qualified laboratory perform
    a compressor oil analysis to
    determine system moisture content
    and acid level. This analysis is a
    valuable diagnostic tool.
    [  ] Contact a qualified service
    organization to leak test the chiller,
    to check operating and safety
    controls, and to inspect electrical
    components for deficiencies.
    [  ] Inspect all piping components for
    leakage and damage. Clean out any
    inline strainers.
    [  ] Clean and repaint any areas that
    show signs of corrosion.
    [  ] Clean the condenser coils. Refer to
    “Coil Cleaning”.
    [  ] Clean the Domestic Water Heater.
    Refer to Domestic Water Heater tube
    cleaning procedure.
    WARNING: Position all electrical
    disconnects in the “OPEN”
    position and lock them, to
    prevent injury or death due to
    electrical shock.
    [  ] Clean the condenser fans. Check the
    fan assemblies for proper clearance
    in the fan openings and for motor
    shaft misalignment, abnormal
    endplay, vibration and noise.
    WARNING: Position all electrical
    disconnects in the “OPEN”
    position and lock them, to
    prevent injury or death due to
    electrical shock. 
    						
    							135RTAA-IOM-3
    Maintenance
    General
    This section describes specific
    maintenance procedures which must
    be performed as a part of the normal
    maintenance program for this unit. Be
    certain that electrical power to the unit
    is disconnected before performing
    these procedures.
    WARNING: Position all electrical
    disconnects in the “OPEN”
    position and lock them, to
    prevent injury or death due to
    electrical shock.
    Coil Cleaning
    Clean the condenser coils at least once
    each year, or more frequently if the unit
    is located in a “dirty” environment.
    This will maintain proper unit operating
    efficiencies. Follow the detergent
    manufacturer’s instructions as closely
    as possible to avoid damage to the
    coils.
    To clean the coils, use a soft brush and
    a sprayer, either the garden, pump-up
    type or a high-pressure type. A high-
    quality detergent, such as “Trane Coil
    Cleaner, CHM-0002” is recommended
    for both standard and “Blue-Fin” coils.
    Note: If the detergent mixture is
    strongly alkaline (pH value greater than
    8.5), an inhibitor must be added.
    Chemically Cleaning
    The Evaporator
    The chilled water system is a closed-
    loop and therefore should not
    accumulate scale or sludge. If the
    chiller becomes fouled, first attempt to
    dislodge the material by backflushing
    the system. If unsuccessful after several
    attempts, chemically clean the
    evaporator.
    Caution: Do not use an acid type
    cleaning agent that will damage
    steel, galvanized steel,
    polypropylene, or internal copper
    components.
    With this information, water treatment
    firms will be able to recommend a
    suitable chemical for use in this
    system.
    A typical configuration for chemical
    cleaning is shown in Figure 59. The
    supplier of the cleaning chemicals must
    provide or approve:
    All of the materials used in this
    configuration
    The amount of chemicals used
    The length of time the chemicals are
    used
    Any safety precautions and
    handling instructions
    Domestic Water
    Heater – Tube Cleaning
    The water tubes may be mechanically
    cleaned with a wire brush. This can be
    done by isolating the water supply to
    the Domestic Water Heater, relieving
    the water pressure, and removing the
    access plugs at the rear of the unit.
    Once the tubes have been brushed and
    scale has been loosened, flush the
    water tubes with fresh water, reinstall
    the access plugs and return to service.
    The circulator should be shut off during
    this operation and all air must be bled
    from the water circuit when returning
    the unit to operation. Be certain to use
    an approved pipe sealant on the
    threaded access plugs when
    reinstalling to prevent water leaks.
    Figure 59
    Chemical Cleaning Configuration 
    						
    							136RTAA-IOM-3
    Water Treatment
    The use of untreated or improperly
    treated water in the unit may result in
    the formation of scale, algae, or slime.
    It may also cause erosion or corrosion.
    It is recommended that a qualified
    water treatment specialist provide
    recommendations for proper water
    treatment. The Trane Company
    assumes no responsibility for
    equipment failure caused by the use of
    untreated or improperly treated water.
    Oil Separator Level
    Check
    Follow the steps listed below and refer
    to the notes listed in Figure 60.
    1. Turn off the unit,
    2. Attach the hoses and sight glass to
    the oil separator charging Schrader
    valve and the compressor discharge
    line Schrader valve, as shown in
    Figure 60. Purge to remove non-
    condensibles. It is advisable to use Schrader
    quickcoupler isolation valves at the
    ends of the hoses. These will aid in
    the installation and removal of the
    hoses and minimize oil and
    refrigerant spray.
    3. After the unit has been off for 10
    minutes, move the sight glass up
    and down until the level can be seen.
    4. After the level has been determined,
    remove the sight glass and hoses.
    Note: Routine changing of the oil or
    the oil filter is not recommended. The
    oil filter is oversized for this application
    and should not require replacement.
    The oil and filter should be replaced
    only if analysis reveals that the oil is
    contaminated. Oil type and system
    capacities are shown in Table 1. 
    						
    							137RTAA-IOM-3
    Figure 60
    System Oil Level Specifications
    Caution: Do not check oil level with
    machine operating. Severe oil loss
    will occur.
    Caution: When checking oil level
    wear protective clothing since oil
    will spray when discharged.
    Insure that the apex of the line above
    the sight glass is as high as possible, to
    eliminate liquid traps which can give
    erroneous readings. 
    						
    							139RTAA-IOM-3 UNIT OPERATING  STATUS COMPRESSOR  OPERATING  STATUS
    CODE DESCRIPTION CODE DESCRIPTION
    Blank UCM Power Off 00Compressor Stop
    888888.8 UCM Paw Up 16 Compressor  Lockout
    00 Unit Stop 17 Cprsr Service Pumpdown
    01 Auto-Local 70 Cprsr Restart Inhibit
    02 Auto-Remote 72 Cprsr Start
    17 Service Pumpdown 74 Run Normal
    70 Unit Restart Inhibit 75 Run:Current Limit
    72 Unit Start 76 Run: Condenser Limit
    74 Run:Normal 1 77 Run:Evaporator Limit
    75 Run :Current Limit 7E Run:Unload
    78 Run ;Condenser Limit
    77 Run:Evaporator Limit
    7E Run:Unload
    88 Reset
    DIAGNOSTIC TYPES100 External Unit Stop
    101 Ice Building Complete MMR Machine Shutdown-Manual Reset
    118 EXV Test CMR Circuit Shutdown-Man Reset
    174 Ice Building; Normal MAR Machine Shutdown-Auto Reset
    175 Ice  Building: Current Limit CAR Circuit Shutdown-Auto Reset
    176 Ice  Building: Condenser Limit IFW Informational-Warning
    177 Ice Building: Evaporator Limit
    200 Low Ambient Run Inhibit
    UNIT DIAGNOSTICS CONDITIONFLASHING DISPLAY: MEANS:
    A xxx A New CMR, CAR. or IFW Diagnostic Exists.
    A xxx « C yyy Operating Code when MMR or MAR occurred. Diagnostic currently inhibiting operation.
    b yyy Manual reset required to restore full operation. This or other latching diagnostics exist.
    C yyy Condition creating MAR, CAR or IFW still exists. If MMR or CMR, manual reset required.
    10 uu The chilled water setpoint is too close to a cutout setpoint.
    DASHES: MEANS:
    d ---- The chiller is in either Ice bldg or ice bldg compl: Ivg chld wtr stpt is not applicable.
    33 ---- The chiller is in normal cooling; the active ice termination setpoint is not applicable.
    Other (e.g. 14----) Option either not installed or not enabled.
    CODE DESCRIPTION TYPE CODE DESCRIPTION TYPE
    87 Chock External Chilled Water Stpt IFW 19F Phase Loss - Cprsr D CMR
    89 Check External Current Limit Stpt IFW 1AO Power Loss - Cprsr A CAR
    8A Chilled Water Flow (Ent Wtr Temp) MMR 1A1 Power Loss - Cprsr 8 CAR
    8E Evap Entering Water Temp Sensor MMR 1A2 Power Loss - Cprsr C CAR
    8F Cond Rfgt Tamp Sensor - Ckt I CMR 1A3 Power Loss - Cprsr D CAR
    90 Cond Rfgt Temp Sensor - Ckt 2 CMR 1A4 Remote communications Loss IFW
    93 Evap Rfgt Temp Sensor - Ckt I CMR 1A5 Oil Flow Control - Cprsr A CMR
    94 Evap Rfgt Tamp Sensor - Ckt 2 CMR 1A6 Oil Flow Control - Cprsr B CMR
    A0 Zone Temp Sensor IFW 1A7 Oil Flow Control - Cprsr C CMR
    A1 Outdoor Air Temp Sensor IFW 1A8 Oil Flow Control - Cprsr D CMR
    Ab Evap Leaving Wtr Temp Sensor MMR 1A9 EXV Elec Drive Ckt - Rfgt Ckt I CMR
    bA Overload Trip - Cprsr A CMR 1AA EXV Elec Drive Ckt - Rfgt Ckt 2 CMR
    bb Overload Trip - Cprsr 0 CMR 1Ad Memory Error Type I (See Oper Manual) IFW
    bC Overload Trip - Cprsr C CMR 1AE Low Differential Press - Ckt I CMR
    bd Overload Trip - Cprsr D CMR 1AF Low Differential Press - Ckt 2 CMR
    bE High Pressure Cutout - Cprsr C CMR 1b2 Severe Phase Unbalance - Cprsr A CMR
    bF High Pressure Cutout - Cprsr D CMR 1b3 Severe Phase Unbalance - Cprsr B CMR
    C5 Low Chilled Water Temp ( U n I t off) IFW 1b4 Severe Phase Unbalance - Cprsr C CMR
    C6 Low Chilled Water Temp (Unit on) MAR 1b5 Severs Phase Unbalance - Cprsr 0 CMR
    CA Contactor - Cprsr A MMR 1b6 Compressor Overload Setting - Cprsr A IFW
    Cb Contactor - Cprsr B MMIR 1b7 Compressor Over load Setting - Cprsr B IFW
    cc Contactor - Cprsr C MMR 1b8 Compressor Overload  Setting - Cprsr C IFW
    Cd Contactor - Cprsr D MMR 1b9 Compressor Overload  Setting - Cprsr D IFW
    d7 Over Voltage MAR 1bA Phase Unbalance - Cprsr  A CMR
    d8 Under Voltage MAR 1bb Phase Unbalance - Cprsr  8 CMR
    Ed Chilled Water Flow Interlock MAR 1bC Phase Unbalance - Cprsr  C CMR
    F5 High Pressure Cutout - Cprsr A CMR 1bd Phase Unbalance - Cprsr  D CMR
    F6 High Pressure Cutout - Cprsr B CMR 1bE Winding Temp. - Cprsr A CMR
    Fd Emergency Stop Input MMR 1bF Winding Temp. - Cprsr B CMR
    180 Starter Transition - Cprsr A CMR 1C0 Winding Temp. - Cprsr C CMR
    181 Starter Transition - Cprsr B CMR 1C1 Winding Temp. - Cprsr D CMR
    182 Starter Transition - Cprsr C CMR 1C2 Discharge Temp. - Cprsr  A CMR
    183 Starter Transition - Cprsr D CMR 1C3 Discharge Temp. - Cprsr  8 CMR
    184 Phase Reversal - Cprsr A CMR 1C4 Discharge Temp. - Cprsr  C CMR
    185 Phase Reversal - Cprsr 8 CMR 1C5 Discharge Temp. - Cprsr  D CMR
    186 Phase Reversal - Cprsr C CMR 1C6 High Differential Pressure - Ckt I CMR
    187 Phase Reversal - Cprsr D CMR 1C7 High Differential Pressure - Ckt 2 CMR
    190 Low Superheat - Ckt I CMR 1d1 Memory Error Type II (See Oper Manual) IFW
    191 Low Superheat - Ckt 2 CMR 1d2 Memory Error Type III (See Oper Manual) IFW
    194 Low Evap Rfgt Tamp - Ckt I CMR 1d3 Cprsr Suction Temp. Sensor - Ckt 1 CMR
    195 Low Evap Rfgt Temp - Ckt 2 CMR 1d4 Cprsr Suction Temp. Sensor - Ckt 2 CMR
    198 Low Oil I Flow - Cprsr A CMR 1d7 Phase Reversal Prot. Lost - Cprsr A CMR
    199 Low 01 1 Flow - Cprsr B CMR 1d8 Phase Reversal Prot. Lost - Cprsr B CMR
    19A Low Oil Flow - Cprsr C CMR 1d9 Phase Reversal Prot. Lost - Cprsr C CMR
    19b Low Oil Flow - Cprsr D CMR 1dA Phase Reversal Prot. Lost - Cprsr D CMR
    19C  Phase Loss - Cprsr A CMR 1db Slave-Exv Elec Drive Ckt - Rfgt Ckt 1 CMR
    19d Phase Lose - Cprsr B CMR  1dc Slave-Exv Elec Drive Ckt - Rfgt Ckt 2 CMR
    19E Phase Loss - Cprsr C CMR  4xy See Operator’s Manual – – –
    X3956048201 Rev. B
    Condition Codes 
    						
    							For further information on this product or other Trane products, refer to the “Trane Service Literature
    Catalog,” ordering number IDX-IOM-1. This catalog contains listings and prices for all service literature
    sold by Trane. The catalog may be ordered by sending a $15.00 check to:
    The Trane Company, Service Literature Sales, 3600 Pammel Creek Road, La Crosse, WI 54601.
    To help ensure optimum performance, be sure to specify quality Trane parts.
    Printed by Production Services – La Crosse
    RTAA-IOM-3 
    						
    All Trane manuals Comments (0)