Trane Rtaaiom3 Manual
Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
131RTAA-IOM-3 Periodic Maintenance General Perform all maintenance procedures and inspections at the recommended intervals. This will prolong the life of the equipment and minimize the possibility of costly failures. Use an “Operator’s Log”, such as that shown in Figure 58, to record an operating history for the unit. The log serves as a valuable diagnostic tool for service personnel. By observing trends in operating conditions, an operator can anticipate and prevent problem situations before they occur. If the unit does not operate properly during maintenance inspections, refer to “Diagnostics and Troubleshooting”.
133RTAA-IOM-3 Refrigerant Emission Control Evidence from environmental scientists indicates that the ozone in our upper atmosphere is being reduced, due to the release of CFC fully halogenated compounds. The Trane Company encourages every effort to eliminate, if possible, or vigorously reduce the emission of CFC, HCFC and HFC refrigerants into the atmosphere that result from installation, operation, routine maintenance, or major services on this equipment. Always act in a responsible manner to conserve refrigerants for continued use, even when acceptable alternatives are available. Conservation and emission reduction can be accomplished by following recommended Trane operation, maintenance and service procedures, with specific attention to the following: 1. Refrigerant used in any type of air conditioning or refrigerating equipment should be recovered for reuse, recovered and/or recycled for reuse, reprocessed (reclaimed), or properly destroyed, whenever it is removed from equipment. Never release refrigerant into the atmosphere. 2. Always determine possible recycle or reclaim requirements of the recovered refrigerant before beginning recovery by any method. Questions about recovered refrigerants and acceptable refrigerant quality standards are addressed in ARI Standard 700. 3. Use approved containment vessels and safety standards. Comply with all applicable transportation standards when shipping refrigerant containers. 4. To minimize emissions while recovering refrigerant, use recycling equipment. Always attempt to use methods which will pull the lowest possible vacuum while recovering and condensing refrigerant into containment. 5. When leak checking with trace refrigerant and nitrogen, use HCFC- 22 (R-22), rather than CFC-12 (R-12) or any other fully halogenated refrigerants. Be aware of any new leak test methods which eliminate refrigerant as a trace gas.6. When cleaning system components or parts, avoid using CFC-11 (R-11) or CFC-113 (R-113). Refrigeration system cleanup methods which use filters and dryers are preferred. Do not use solvents which have ozone depletion factors. Properly dispose of used materials. 7. Take extra care to properly maintain all service equipment that directly supports refrigeration service work, such as gauges, hoses, vacuum pumps and recycling equipment. 8. Stay aware of unit enhancements, conversion refrigerants, compatible parts and manufacturer’s recommendations which will reduce refrigerant emissions and increase equipment operating efficiencies. Follow manufacturer’s specific guidelines for conversion of existing systems. 9. In order to assist in reducing power generation emissions, always attempt to improve equipment performance with improved maintenance and operations that will help conserve energy resources. Weekly Maintenance After the unit has been operating for approximately 30 minutes and the system has stabilized, check the operating conditions and complete the procedures below: [ ] Check the evaporator refrigerant pressure (23) and the condenser refrigerant pressure (25) in Menu 2 on the UCM. The pressures are referenced to sea level (114.6960 psia). [ ] Check the liquid line sight glasses. The refrigerant flow past the sight glasses should be clear. Bubbles in the refrigerant indicate either low refrigerant charge or excessive pressure drop in the liquid line. A restriction in the line can sometimes be identified by a noticeable temperature differential between the two sides of the restriction. Frost may often form on the line at this point. Proper refrigerant charges are shown on Table 1. Caution: A clear sight glass alone does not mean that the system properly charged. Also check system superheat, subcooling, and unit operating pressures.
134RTAA-IOM-3 [ ] If operating pressures and sight glass conditions seem to indicate refrigerant shortage, measure the system superheat and system subcooling. Refer to “System Superheat” and “System Subcooling”. [ ] If operating conditions indicate a refrigerant overcharge, remove refrigerant at the liquid line service valve. Allow refrigerant to escape slowly, to minimize oil loss. Do not discharge refrigerant into the atmosphere. WARNING: Do not allow refrigerant to directly contact skin or injury from frostbite may result. [ ] Inspect the entire system for unusual conditions and inspect the condenser coils for dirt and debris. If the coils are dirty, refer to “Coil Cleaning”. Monthly Maintenance [ ] Perform all weekly maintenance procedures. [ ] Measure and record the system superheat. Refer to “System Superheat”. [ ] Measure and record the system subcooling. Refer to “System Subcooling”. [ ] Manually rotate condenser fans to insure proper clearance on the fan openings. WARNING: Position all electrical disconnects in the “OPEN” position and lock them, to prevent injury or death due to electrical shock. Annual Maintenance [ ] Perform all weekly and monthly maintenance procedures. [ ] Check the oil level and refrigerant charge. Refer to “Maintenance Procedures”. [ ] Have a qualified laboratory perform a compressor oil analysis to determine system moisture content and acid level. This analysis is a valuable diagnostic tool. [ ] Contact a qualified service organization to leak test the chiller, to check operating and safety controls, and to inspect electrical components for deficiencies. [ ] Inspect all piping components for leakage and damage. Clean out any inline strainers. [ ] Clean and repaint any areas that show signs of corrosion. [ ] Clean the condenser coils. Refer to “Coil Cleaning”. [ ] Clean the Domestic Water Heater. Refer to Domestic Water Heater tube cleaning procedure. WARNING: Position all electrical disconnects in the “OPEN” position and lock them, to prevent injury or death due to electrical shock. [ ] Clean the condenser fans. Check the fan assemblies for proper clearance in the fan openings and for motor shaft misalignment, abnormal endplay, vibration and noise. WARNING: Position all electrical disconnects in the “OPEN” position and lock them, to prevent injury or death due to electrical shock.
135RTAA-IOM-3 Maintenance General This section describes specific maintenance procedures which must be performed as a part of the normal maintenance program for this unit. Be certain that electrical power to the unit is disconnected before performing these procedures. WARNING: Position all electrical disconnects in the “OPEN” position and lock them, to prevent injury or death due to electrical shock. Coil Cleaning Clean the condenser coils at least once each year, or more frequently if the unit is located in a “dirty” environment. This will maintain proper unit operating efficiencies. Follow the detergent manufacturer’s instructions as closely as possible to avoid damage to the coils. To clean the coils, use a soft brush and a sprayer, either the garden, pump-up type or a high-pressure type. A high- quality detergent, such as “Trane Coil Cleaner, CHM-0002” is recommended for both standard and “Blue-Fin” coils. Note: If the detergent mixture is strongly alkaline (pH value greater than 8.5), an inhibitor must be added. Chemically Cleaning The Evaporator The chilled water system is a closed- loop and therefore should not accumulate scale or sludge. If the chiller becomes fouled, first attempt to dislodge the material by backflushing the system. If unsuccessful after several attempts, chemically clean the evaporator. Caution: Do not use an acid type cleaning agent that will damage steel, galvanized steel, polypropylene, or internal copper components. With this information, water treatment firms will be able to recommend a suitable chemical for use in this system. A typical configuration for chemical cleaning is shown in Figure 59. The supplier of the cleaning chemicals must provide or approve: All of the materials used in this configuration The amount of chemicals used The length of time the chemicals are used Any safety precautions and handling instructions Domestic Water Heater – Tube Cleaning The water tubes may be mechanically cleaned with a wire brush. This can be done by isolating the water supply to the Domestic Water Heater, relieving the water pressure, and removing the access plugs at the rear of the unit. Once the tubes have been brushed and scale has been loosened, flush the water tubes with fresh water, reinstall the access plugs and return to service. The circulator should be shut off during this operation and all air must be bled from the water circuit when returning the unit to operation. Be certain to use an approved pipe sealant on the threaded access plugs when reinstalling to prevent water leaks. Figure 59 Chemical Cleaning Configuration
136RTAA-IOM-3 Water Treatment The use of untreated or improperly treated water in the unit may result in the formation of scale, algae, or slime. It may also cause erosion or corrosion. It is recommended that a qualified water treatment specialist provide recommendations for proper water treatment. The Trane Company assumes no responsibility for equipment failure caused by the use of untreated or improperly treated water. Oil Separator Level Check Follow the steps listed below and refer to the notes listed in Figure 60. 1. Turn off the unit, 2. Attach the hoses and sight glass to the oil separator charging Schrader valve and the compressor discharge line Schrader valve, as shown in Figure 60. Purge to remove non- condensibles. It is advisable to use Schrader quickcoupler isolation valves at the ends of the hoses. These will aid in the installation and removal of the hoses and minimize oil and refrigerant spray. 3. After the unit has been off for 10 minutes, move the sight glass up and down until the level can be seen. 4. After the level has been determined, remove the sight glass and hoses. Note: Routine changing of the oil or the oil filter is not recommended. The oil filter is oversized for this application and should not require replacement. The oil and filter should be replaced only if analysis reveals that the oil is contaminated. Oil type and system capacities are shown in Table 1.
137RTAA-IOM-3 Figure 60 System Oil Level Specifications Caution: Do not check oil level with machine operating. Severe oil loss will occur. Caution: When checking oil level wear protective clothing since oil will spray when discharged. Insure that the apex of the line above the sight glass is as high as possible, to eliminate liquid traps which can give erroneous readings.
139RTAA-IOM-3 UNIT OPERATING STATUS COMPRESSOR OPERATING STATUS CODE DESCRIPTION CODE DESCRIPTION Blank UCM Power Off 00Compressor Stop 888888.8 UCM Paw Up 16 Compressor Lockout 00 Unit Stop 17 Cprsr Service Pumpdown 01 Auto-Local 70 Cprsr Restart Inhibit 02 Auto-Remote 72 Cprsr Start 17 Service Pumpdown 74 Run Normal 70 Unit Restart Inhibit 75 Run:Current Limit 72 Unit Start 76 Run: Condenser Limit 74 Run:Normal 1 77 Run:Evaporator Limit 75 Run :Current Limit 7E Run:Unload 78 Run ;Condenser Limit 77 Run:Evaporator Limit 7E Run:Unload 88 Reset DIAGNOSTIC TYPES100 External Unit Stop 101 Ice Building Complete MMR Machine Shutdown-Manual Reset 118 EXV Test CMR Circuit Shutdown-Man Reset 174 Ice Building; Normal MAR Machine Shutdown-Auto Reset 175 Ice Building: Current Limit CAR Circuit Shutdown-Auto Reset 176 Ice Building: Condenser Limit IFW Informational-Warning 177 Ice Building: Evaporator Limit 200 Low Ambient Run Inhibit UNIT DIAGNOSTICS CONDITIONFLASHING DISPLAY: MEANS: A xxx A New CMR, CAR. or IFW Diagnostic Exists. A xxx « C yyy Operating Code when MMR or MAR occurred. Diagnostic currently inhibiting operation. b yyy Manual reset required to restore full operation. This or other latching diagnostics exist. C yyy Condition creating MAR, CAR or IFW still exists. If MMR or CMR, manual reset required. 10 uu The chilled water setpoint is too close to a cutout setpoint. DASHES: MEANS: d ---- The chiller is in either Ice bldg or ice bldg compl: Ivg chld wtr stpt is not applicable. 33 ---- The chiller is in normal cooling; the active ice termination setpoint is not applicable. Other (e.g. 14----) Option either not installed or not enabled. CODE DESCRIPTION TYPE CODE DESCRIPTION TYPE 87 Chock External Chilled Water Stpt IFW 19F Phase Loss - Cprsr D CMR 89 Check External Current Limit Stpt IFW 1AO Power Loss - Cprsr A CAR 8A Chilled Water Flow (Ent Wtr Temp) MMR 1A1 Power Loss - Cprsr 8 CAR 8E Evap Entering Water Temp Sensor MMR 1A2 Power Loss - Cprsr C CAR 8F Cond Rfgt Tamp Sensor - Ckt I CMR 1A3 Power Loss - Cprsr D CAR 90 Cond Rfgt Temp Sensor - Ckt 2 CMR 1A4 Remote communications Loss IFW 93 Evap Rfgt Temp Sensor - Ckt I CMR 1A5 Oil Flow Control - Cprsr A CMR 94 Evap Rfgt Tamp Sensor - Ckt 2 CMR 1A6 Oil Flow Control - Cprsr B CMR A0 Zone Temp Sensor IFW 1A7 Oil Flow Control - Cprsr C CMR A1 Outdoor Air Temp Sensor IFW 1A8 Oil Flow Control - Cprsr D CMR Ab Evap Leaving Wtr Temp Sensor MMR 1A9 EXV Elec Drive Ckt - Rfgt Ckt I CMR bA Overload Trip - Cprsr A CMR 1AA EXV Elec Drive Ckt - Rfgt Ckt 2 CMR bb Overload Trip - Cprsr 0 CMR 1Ad Memory Error Type I (See Oper Manual) IFW bC Overload Trip - Cprsr C CMR 1AE Low Differential Press - Ckt I CMR bd Overload Trip - Cprsr D CMR 1AF Low Differential Press - Ckt 2 CMR bE High Pressure Cutout - Cprsr C CMR 1b2 Severe Phase Unbalance - Cprsr A CMR bF High Pressure Cutout - Cprsr D CMR 1b3 Severe Phase Unbalance - Cprsr B CMR C5 Low Chilled Water Temp ( U n I t off) IFW 1b4 Severe Phase Unbalance - Cprsr C CMR C6 Low Chilled Water Temp (Unit on) MAR 1b5 Severs Phase Unbalance - Cprsr 0 CMR CA Contactor - Cprsr A MMR 1b6 Compressor Overload Setting - Cprsr A IFW Cb Contactor - Cprsr B MMIR 1b7 Compressor Over load Setting - Cprsr B IFW cc Contactor - Cprsr C MMR 1b8 Compressor Overload Setting - Cprsr C IFW Cd Contactor - Cprsr D MMR 1b9 Compressor Overload Setting - Cprsr D IFW d7 Over Voltage MAR 1bA Phase Unbalance - Cprsr A CMR d8 Under Voltage MAR 1bb Phase Unbalance - Cprsr 8 CMR Ed Chilled Water Flow Interlock MAR 1bC Phase Unbalance - Cprsr C CMR F5 High Pressure Cutout - Cprsr A CMR 1bd Phase Unbalance - Cprsr D CMR F6 High Pressure Cutout - Cprsr B CMR 1bE Winding Temp. - Cprsr A CMR Fd Emergency Stop Input MMR 1bF Winding Temp. - Cprsr B CMR 180 Starter Transition - Cprsr A CMR 1C0 Winding Temp. - Cprsr C CMR 181 Starter Transition - Cprsr B CMR 1C1 Winding Temp. - Cprsr D CMR 182 Starter Transition - Cprsr C CMR 1C2 Discharge Temp. - Cprsr A CMR 183 Starter Transition - Cprsr D CMR 1C3 Discharge Temp. - Cprsr 8 CMR 184 Phase Reversal - Cprsr A CMR 1C4 Discharge Temp. - Cprsr C CMR 185 Phase Reversal - Cprsr 8 CMR 1C5 Discharge Temp. - Cprsr D CMR 186 Phase Reversal - Cprsr C CMR 1C6 High Differential Pressure - Ckt I CMR 187 Phase Reversal - Cprsr D CMR 1C7 High Differential Pressure - Ckt 2 CMR 190 Low Superheat - Ckt I CMR 1d1 Memory Error Type II (See Oper Manual) IFW 191 Low Superheat - Ckt 2 CMR 1d2 Memory Error Type III (See Oper Manual) IFW 194 Low Evap Rfgt Tamp - Ckt I CMR 1d3 Cprsr Suction Temp. Sensor - Ckt 1 CMR 195 Low Evap Rfgt Temp - Ckt 2 CMR 1d4 Cprsr Suction Temp. Sensor - Ckt 2 CMR 198 Low Oil I Flow - Cprsr A CMR 1d7 Phase Reversal Prot. Lost - Cprsr A CMR 199 Low 01 1 Flow - Cprsr B CMR 1d8 Phase Reversal Prot. Lost - Cprsr B CMR 19A Low Oil Flow - Cprsr C CMR 1d9 Phase Reversal Prot. Lost - Cprsr C CMR 19b Low Oil Flow - Cprsr D CMR 1dA Phase Reversal Prot. Lost - Cprsr D CMR 19C Phase Loss - Cprsr A CMR 1db Slave-Exv Elec Drive Ckt - Rfgt Ckt 1 CMR 19d Phase Lose - Cprsr B CMR 1dc Slave-Exv Elec Drive Ckt - Rfgt Ckt 2 CMR 19E Phase Loss - Cprsr C CMR 4xy See Operator’s Manual – – – X3956048201 Rev. B Condition Codes
For further information on this product or other Trane products, refer to the “Trane Service Literature Catalog,” ordering number IDX-IOM-1. This catalog contains listings and prices for all service literature sold by Trane. The catalog may be ordered by sending a $15.00 check to: The Trane Company, Service Literature Sales, 3600 Pammel Creek Road, La Crosse, WI 54601. To help ensure optimum performance, be sure to specify quality Trane parts. Printed by Production Services – La Crosse RTAA-IOM-3