Home > Trane > Cooler > Trane Rtaaiom3 Manual

Trane Rtaaiom3 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							121RTAA-IOM-3
    Pre-Start
    Checkout
    General
    When installation is complete, but prior
    to putting the unit into service, the
    following pre-start procedures must be
    reviewed and verified correct:
    [  ] Inspect all wiring connections to be
    sure they are clean and tight.
    WARNING: Disconnect all electric
    power including remote
    disconnects before servicing’
    Failure to disconnect power
    before servicing can cause severe
    personal injury or death.
    Caution: Check the tightness of all
    connections in the compressor
    power circuits (disconnects,
    terminal block, contactors,
    compressor junction box terminals,
    etc.). Loose connections can cause
    overheating at the connections and
    undervoltage conditions at the
    compressor motor.
    [  ] Verify that all refrigerant valves, as
    shown in Figure 37, are “OPEN”.
    Caution: Do not operate the unit
    with the compressor, oil discharge
    and liquid line service valves
    “CLOSED”. Failure to have these
    “OPEN” may cause serious
    compressor damage.
    [  ] Check the power supply voltage to
    the unit at the main power fused
    disconnect switch. Voltage must be
    within the voltage utilization range,
    given in Table 10 and also stamped
    on the unit nameplate. Voltage
    imbalance must not exceed 2
    percent. Refer to “Unit Voltage
    Imbalance”, below.
    WARNING: Disconnect all electric
    power including remote
    disconnects before servicing.
    Failure to disconnect power
    before servicing can cause severe
    personal injury or death.
    [  ] Check the unit power phasing to be
    sure that it has been installed in an
    “ABC” sequence. Refer to “Unit
    Voltage Phasing”, below.
    WARNING: It is imperative that
    L1 -L2-L3 in the starter be
    connected in the A-B-C phase
    sequence to prevent equipment
    damage due to reverse rotation.
    [  ] Check the condenser fans to be sure
    that they rotate freely in the fan
    openings and that each is securely
    attached to its fan motor shaft.
    WARNING: Disconnect all electric
    power Including remote
    disconnects before servicing.
    Failure to disconnect power
    before servicing can cause severe
    personal injury or death.
    [  ] Energize the compressor sump
    heaters by closing the unit main
    disconnects. If unit-mounted
    disconnects are used, they must
    also be closed. If the unit does not
    have the optional control power
    transformer, 115 VAC power must
    be field supplied to terminals 1TB3-1
    AND 1TB3-2. The Chiller Switch
    must be in the STOP/RESET
    position.
    Caution: The compressor sump
    heaters must be energized for a
    minimum of 24 hours prior to unit
    operation, to prevent compressor
    damage caused by liquid
    refrigerant in the compressor at
    start-up. 
    						
    							122RTAA-IOM-3
    [  ] Energize the evaporator and
    Domestic Water Heater heat tape.
    [  ] Fill the evaporator chilled water
    circuit. Refer to Table 1 for
    evaporator liquid capacities. Vent
    the system while it is being filled.
    Open the vent on the top of the
    evaporator during filling and close
    when filling is completed.
    Customer Note
    The use of improperly treated or
    untreated water in this equipment may
    result in scaling, erosion, corrosion,
    algae or slime. The services of a
    qualified water treatment specialist
    should be engaged to determine what
    treatment, if any, is advisable. The
    Trane Company warranty specifically
    excludes liability for corrosion, erosion
    or deterioration of Trane equipment.
    Trane assumes no responsibilities for
    the results of the use of untreated or
    improperly treated water, or saline or
    brackish water.
    Caution: Do not used untreated or
    improperly treated water.
    Equipment damage may occur.
    Caution: Do not fill the water
    systems unless the evaporator and
    Domestic Water Heater heat tapes
    have been energized.
    [  ] Close the fused-disconnect
    switch(es) that supplies power to
    the chilled water pump starter.
    [  ] Start the chilled water pump to
    begin circulation of the chilled water.
    Inspect all piping for leakage and
    make any necessary repairs.
    [  ] With chilled water circulating
    through the system, adjust water
    flow and check water pressure drop
    through the evaporator. Refer to
    Figure 23.
    [  ] Adjust the chilled water flow switch
    (if installed) for proper operation.
    [  ] Prove Chilled Water Pump Interlock
    and External Auto/Stop as described
    in Interconnecting Wiring: Chilled
    Water Pump Interlock and External
    Auto/Stop.
    Caution: Chilled Water Pump
    Interlock and External Auto/Stop
    information must be adhered to or
    equipment damage may occur.
    [  ] Check and set, as required, all UCM
    Menu items.
    [  ] Stop the chilled water pump.
    Unit Voltage
    Power Supply
    Voltage to the unit must meet the
    criteria given in Table 10. Measure each
    leg of the supply voltage at the unit
    main power fused-disconnect. If the
    measured voltage on any leg is not
    within specified range, notify the
    supplier of the power and correct the
    situation before operating the unit.
    Caution: Inadequate voltage to the
    unit can cause control components
    to malfunction and shorten the life
    of relay contact, compressor
    motors and contactors.
    Unit Voltage Imbalance
    Excessive voltage imbalance between
    the phases of a three-phase system can
    cause Motors to overheat and
    eventually fail. The maximum
    allowable imbalance is 2 percent.
    Voltage imbalance is determined using
    the following calculations:
    % Imbalance = (V
    x - V
    ave) x 100
    V
    ave
    V
    ave = (V
    1 + V
    2 + V
    3) 
    / 3
    V
    x = phase with greatest difference
    from V
    ave (without regard to sign)
    For example, if the three measured
    voltages are 221, 230, and 227 volts, the
    average would be:
    221 +230 +227 
    = 226
    3
    The percentage of imbalance is then:
    100 (221 - 226) 
    = 2.2%
    226
    This exceeds the maximum allowable
    (2%) by 0.2 percent. 
    						
    							123RTAA-IOM-3
    Unit Voltage Phasing
    It is important that proper rotation of
    the compressors be established before
    the unit is started. Proper motor
    rotation requires confirmation of the
    electrical phase sequence of the power
    supply. The motor is internally
    connected for clockwise rotation with
    the incoming power supply phased
    A, B, C.
    Basically, voltages generated in each
    phase of a polyphase alternator or
    circuit are called phase voltages. In a
    three-phase circuit, three sine wave
    voltages are generated, differing in
    phase by 120 electrical degrees. The
    order in which the three voltages of a
    three-phase system succeed one
    another is called phase sequence or
    phase rotation. This is determined by
    the direction of rotation of the
    alternator. When rotation is clockwise
    phase sequence is usually called
    “‘ABC”, when counterclockwise,
    “CBA”.This direction may be reversed outside
    the alternator by interchanging any two
    of the line wires. It is this possible
    interchange of wiring that makes a
    phase sequence indicator necessary if
    the operator is to quickly determine the
    phase rotation of the motor.
    Proper compressor motor electrical
    phasing can be quickly determined and
    corrected before starting the unit. Use a
    quality instrument, such as the
    Associated Research Model 45 Phase
    Sequence Indicator shown in Figure 55,
    and follow this procedure.
     WARNING
    IT IS IMPERATIVE THAT L1-L2-L3
    IN THE STARTER BE
    CONNECTED IN THE A-B-C
    PHASE SEQUENCE TO PREVENT
    EQUIPMENT DAMAGE DUE TO
    REVERSE ROTATION.
    Figure 55
    Associated Research Model 45
    Phase Sequence Indicator 
    						
    							124RTAA-IOM-3
    1. Turn the Chiller Switch on the UCM
    to the STOP/RESET position.
    2. Open the electrical disconnect or
    circuit protection switch that
    provides line power to the line power
    terminal block(s) in the starter panel
    (or to the unit-mounted disconnect).
    3. Connect the phase sequence
    indicator leads to the line power
    terminal block, as follows:
    Phase Seq. LeadTerminal
    Black (Phase A).................. L1
    Red (Phase B).................... L2
    Yellow (Phase C)................ L3
    4. Turn power on by closing the unit
    supply power fused- disconnect
    switch.
    5. Read the phase sequence on the
    indicator. The “ABC” LED on the face
    of the phase indicator will glow if
    phase is “ABC”.
    WARNING: To prevent injury or
    death due to electrocution, take
    extreme care when performing
    service procedures with electrical
    power energized.
    6. If the “CBA” indicator glows instead,
    open the unit main power disconnect
    and switch two line leads on the line
    power terminal block(s) (or the unit
    mounted disconnect). Reclose the
    main power disconnect and recheck
    the phasing.
    Caution: Do not interchange any
    load leads that are from the unit
    contactors or the motor terminals.
    7. Reopen the unit disconnect and
    disconnect the phase indicator.
    Water System
    Flow Rates
    Establish a balanced chilled water flow
    through the evaporator. The flow rates
    should fall between the minimum and
    maximum values given in Table 1.
    Chilled water flow rates below the
    minimum values will result in laminar
    flow, which reduces heat transfer and
    causes either loss of EXV control or
    repeated nuisance, low temperature
    cutouts. Flow rates that are too high
    can cause tube erosion and damage to
    the tube supports and baffles in the
    evaporator.
    Caution: Once the evaporator and
    Domestic Water Heater (optional)
    are filled with water, the heat tapes
    must be energized to protect the
    evaporator from freezing and
    bursting if the outdoor air
    temperature drops below freezing.
    Water System
    Pressure Drop
    Measure chilled water pressure drop
    through the evaporator at the field-
    installed pressure taps on the system
    water piping. See Figure 22. Use the
    same gauge for each measurement. Do
    not include valves, strainers fittings in
    the pressure drop readings.
    Measure the water pressure drop
    through the Domestic Water Heater at
    the field installed vent and drain
    connections. See Figure 24. Use the
    same gauge for each measurement. Do
    not include valves, strainers, fittings in
    pressure drop readings.
    Pressure drop readings should be
    approximately those shown in the
    Pressure Drop Charts, Figure 23 for the
    evaporator and Figure 25 for the
    Domestic Water Heater (optional).
    UCM Set-up
    Refer to “Menu Function Descriptions
    and Selection” for instruction on the
    set-up of the UCM. 
    						
    							125RTAA-IOM-3
    Start-Up
    Procedures
    General
    If the pre-start checkout, as discussed
    above, has been completed, the unit is
    ready to start. UCM controls are shown
    in Figure 51 and UCM Sequence of
    Operation is shown in Figures 56
    and 57. Complete each step, in
    sequence, as follows:
    [  ] Move the Chiller Switch on the UCM
    to the STOP/RESET position.
    [  ] As necessary, adjust the setpoint
    values in the UCM menus, as
    described in “Menu Function
    Descriptions and Selections”.
    [  ] Close the fused-disconnect switch
    for the chilled water pump. Energize
    the pump to start chilled water
    circulation.
    [  ] Check the service valves on the
    discharge line, suction line, oil line
    and liquid line for each circuit. These
    valves must be open (backseated)
    before starting the compressors.
    Caution: To prevent compressor
    damage, do not operate the unit
    until all refrigerant and oil line
    service valves are opened.
    [  ] Energize the compressor sump
    heaters, if not already energized.
    Also close the unit-mounted
    disconnect, if used.
    Caution: The compressor sump
    heaters must be energized for a
    minimum of 24 hours prior to unit
    operation, to prevent compressor
    damage caused by liquid
    refrigerant in the compressor at
    start-up.
    [  ] Verify that the evaporator heat tape
    is energized.
    [  ] Verify that the chilled water pump
    runs for one minute after the chiller
    is commanded to stop (for normal
    chilled water systems). See page
    [  ] Move the Chiller Switch to AUTO
    LOCAL. If the chiller control 1 U 1
    calls for cooling and all safety
    interlocks are closed, the unit will
    start. The compressor(s) will load
    and unload in response to the
    temperature of the leaving chilled
    water temperature.If optional low-ambient is installed,
    outside air temperature must be
    above the minimum starting
    ambients, as shown in Table 1, for
    continued unit operation. Use Table
    1 to determine proper setpoints for
    the optional low ambient lockout
    setpoint, if used. Also refer to the
    wiring diagrams in Figures 34
    thru 36.
    Once the system has been operating
    for approximately 30 minutes and has
    become stabilized, complete the start-
    up procedures, as follows:
    [  ] Check the evaporator refrigerant
    pressure (23) and the condenser
    refrigerant pressure (25) in Menu 2
    on the UCM. The pressures are
    referenced to sea level (14.6960
    psia)
    [  ] Check the liquid line sight glasses.
    The refrigerant flow past the sight
    glasses should be clear. Bubbles in
    the refrigerant indicate either low
    refrigerant charge or excessive
    pressure drop in the liquid line. A
    restriction in the line can sometimes
    be identified by a noticeable
    temperature differential between
    the two sides of the restriction. Frost
    may often form on the line at this
    point. Proper refrigerant charges are
    shown in Table 1.
    Caution: A clear sight glass alone
    does not mean that the system is
    properly charged. Also check
    system superheat, subcooling, and
    unit operating pressures.
    [  ] Measure the system superheat.
    Refer to “System Superheat, below.
    [  ] Measure the system subcooling.
    Refer to “System Subcooling”,
    below.
    [  ] A shortage of refrigerant is indicated
    if operating pressures are low and
    subcooling is also low. If the
    operating pressures, sight glass,
    superheat and subcooling readings
    indicate a refrigerant shortage, gas-
    charge refrigerant into each circuit,
    as required. With the unit running,
    add refrigerant vapor by connecting
    the charging line to the suction
    service valve and charging through
    the backseat port until operating
    conditions become normal.
    Caution: If both suction and
    discharge pressures are low but
    subcooling is normal, a problem
    other than refrigerant shortage
    exists. Do not add refrigerant, as
    this may result in overcharging the
    circuit.
    Caution: Use only refrigerants
    specified on the unit nameplate, to
    prevent compressor damage and
    insure full system capacity.
    [  ] If operating conditions indicate a
    refrigerant overcharge, remove
    refrigerant at the liquid line service
    valve. Allow refrigerant to escape
    slowly, to minimize oil loss. Do not
    discharge refrigerant into the
    atmosphere.
    WARNING: Do not allow
    refrigerant to directly contact
    skin or injury from frostbite may
    result.
    System Superheat
    Normal superheat for each circuit is
    approximately 8 F at full operating
    load. Superheat temperature can be
    expected to be moving around the 8 F
    setpoint when the chiller is pulling
    down, the compressor slide valve is
    being modulated, or the fans are
    staging on either the same or opposite
    circuits. Superheat can be expected to
    settle out at approximately 8 F when
    the above items stabilize.
    System Subcooling
    Normal subcooling for each circuit
    ranges from 11 F to 20 F, depending on
    the unit. If subcooling for either circuit
    does not approximate these figures,
    check the superheat for the circuit and
    adjust, if required. If superheat is
    normal but subcooling is not, contact a
    qualified service technician. 
    						
    							126
    RTAA-IOM-3
    Figure 56 
    Unit Sequence of Operation – RTAA 240 to 400 Tons
    (Continued on Next Page) 
    						
    							127RTAA-IOM-3
    (Continued from Previous Page)
    2307-1566C 
    						
    							128
    RTAA-IOM-3
    Figure 57 
    Unit Sequence of Operation – RTAA 130 to 200 Tons
    2306-9122A 
    						
    							129RTAA-IOM-3
    Unit Shutdown
    Procedures
    Temporary Shutdown
    and Restart
    To shut the unit down for a short time,
    use the following procedure:
    1. Move the Chiller Switch to STOP/
    RESET. The compressors will
    continue to operate and, after
    unloading for 20 seconds, will stop
    when the compressor contactors de-
    energize. The condenser fans will be
    de-energized at this time.
    2. The unit disconnect switch and unit
    mounted disconnect (if installed)
    should remain closed to keep the
    compressor sump heaters energized.
    3. Maintain power to keep the
    evaporator and Domestic Water
    Heater heat tape(s) energized.
    4. Stop the chilled water circulation by
    turning off the chilled water pump.
    To restart the unit after a temporary
    shutdown, restart the chilled water
    pump and move the Chiller Switch to
    either of the AUTO positions. The unit
    will start normally, provided the
    following conditions exist:
    1. The UCM must receive a call for
    cooling and the differential- to-start
    must be above the setpoint.
    2. All system operating interlocks and
    safety circuits must be satisfied.
    Extended Shutdown
    Procedure
    The following procedure is to be
    followed if the system is to be taken out
    of service for an extended period of
    time, e.g. seasonal shutdown:
    1. Test the condenser and high-side
    piping for refrigerant leakage.
    2. Open the electrical disconnect
    switches for the chilled water pump.
    Lock the switch in the “OPEN”
    position.
    Caution: Lock the chilled water
    pump disconnect open to prevent
    pump damage.
    3. Close all chilled water supply valves.
    Drain the chilled water from the
    evaporator. If the unit will be
    exposed to freezing ambient
    conditions, flush the evaporator with
    an antifreeze solution and energize
    the evaporator heat tape.
    Caution: To prevent damage to the
    evaporator by freezing, flush the
    evaporator with an antifreeze
    solution and energize the
    evaporator heat tape.
    4. Drain the Domestic Water Heater and
    any exposed system piping to
    prevent the possibility of freeze-up.
    Use the pressure tap on the water
    outlet to force compressed air
    through the water coils of the unit
    and assure that no water blocks any
    of the tubes. Be certain that the drain
    valve on the water inlet is open
    before applying compressed air to
    the water coils. Energize the
    Domestic Water Heater heat tape.
    Caution: To prevent damage to the
    Domestic Water Heater by
    freezing, blow out water from coils
    and energize the Domestic Water
    Heater heat tape.
    5. Open the unit main electrical
    disconnect and unit-mounted
    disconnect (if installed) and lock on
    the “OPEN” position. If optional
    control power transformer is not
    installed, open and lock the 115 V
    disconnect.
    Caution: Lock the disconnects on
    the “OPEN” position to prevent
    accidental start-up and damage to
    the system when it has been setup
    for extended shutdown.
    6. At least every three months
    (quarterly), check the pressure in the
    unit to verify that the refrigerant
    charge is intact. 
    						
    							130RTAA-IOM-3
    System Restart After
    Extended Shutdown.
    Follow the procedures below to restart
    the unit after extended shutdown:
    1. Verify that the liquid line service
    valves, oil line, compressor
    discharge service valves and suction
    service valves (if installed) are open
    (backseated).
    Caution: To prevent damage to the
    compressor, be sure that all
    refrigerant valves are open before
    starting the unit.
    2. Close the main disconnect and unit
    mounted disconnect (if installed) to
    energize the compressor sump
    heaters. If the optional control
    transformer is not installed, it will be
    necessary to close the disconnect for
    115 VAC power to 1TB3-1 and
    1TB3-2.
    Caution: The compressor sump
    heaters must be energized for a
    minimum of 24 hours prior to unit
    operation, to prevent compressor
    damage caused by liquid
    refrigerant in the compressor at
    start-up.
    3. Maintain power to the evaporator
    heat tape connections.
    4. Check the oil separator oil level. See
    “Oil Separator Level Check”.
    5. Fill the evaporator chilled water
    circuit. Refer to Table I for evaporator
    liquid capacities. Vent the system
    while it is being filled. Open the vent
    on the top of the evaporator during
    filling and close when filling is
    completed.
    Caution: Do not use untreated or
    improperly treated water.
    Equipment damage may occur.
    6. Close the fused-disconnect switch
    that provides power to the chilled
    water pump.
    7. Start the chilled water pump and,
    while chilled water is circulating,
    inspect all piping for leakage. Make
    any necessary repairs before starting
    the unit.
    8. While the chilled water is circulating,
    adjust the chilled water flow and
    check the chilled water pressure drop
    through the evaporator. Refer to
    “Water System Flow Rates” and
    “Water System Pressure Drop”.
    9. Adjust the flow switch on the
    evaporator piping (if installed) for
    proper operation.
    10. Stop the chilled water pump. The
    unit is now ready for start-up as
    described in “Start-Up Procedures”. 
    						
    All Trane manuals Comments (0)

    Related Manuals for Trane Rtaaiom3 Manual