Trane Rtaaiom3 Manual
Have a look at the manual Trane Rtaaiom3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
121RTAA-IOM-3 Pre-Start Checkout General When installation is complete, but prior to putting the unit into service, the following pre-start procedures must be reviewed and verified correct: [ ] Inspect all wiring connections to be sure they are clean and tight. WARNING: Disconnect all electric power including remote disconnects before servicing’ Failure to disconnect power before servicing can cause severe personal injury or death. Caution: Check the tightness of all connections in the compressor power circuits (disconnects, terminal block, contactors, compressor junction box terminals, etc.). Loose connections can cause overheating at the connections and undervoltage conditions at the compressor motor. [ ] Verify that all refrigerant valves, as shown in Figure 37, are “OPEN”. Caution: Do not operate the unit with the compressor, oil discharge and liquid line service valves “CLOSED”. Failure to have these “OPEN” may cause serious compressor damage. [ ] Check the power supply voltage to the unit at the main power fused disconnect switch. Voltage must be within the voltage utilization range, given in Table 10 and also stamped on the unit nameplate. Voltage imbalance must not exceed 2 percent. Refer to “Unit Voltage Imbalance”, below. WARNING: Disconnect all electric power including remote disconnects before servicing. Failure to disconnect power before servicing can cause severe personal injury or death. [ ] Check the unit power phasing to be sure that it has been installed in an “ABC” sequence. Refer to “Unit Voltage Phasing”, below. WARNING: It is imperative that L1 -L2-L3 in the starter be connected in the A-B-C phase sequence to prevent equipment damage due to reverse rotation. [ ] Check the condenser fans to be sure that they rotate freely in the fan openings and that each is securely attached to its fan motor shaft. WARNING: Disconnect all electric power Including remote disconnects before servicing. Failure to disconnect power before servicing can cause severe personal injury or death. [ ] Energize the compressor sump heaters by closing the unit main disconnects. If unit-mounted disconnects are used, they must also be closed. If the unit does not have the optional control power transformer, 115 VAC power must be field supplied to terminals 1TB3-1 AND 1TB3-2. The Chiller Switch must be in the STOP/RESET position. Caution: The compressor sump heaters must be energized for a minimum of 24 hours prior to unit operation, to prevent compressor damage caused by liquid refrigerant in the compressor at start-up.
122RTAA-IOM-3 [ ] Energize the evaporator and Domestic Water Heater heat tape. [ ] Fill the evaporator chilled water circuit. Refer to Table 1 for evaporator liquid capacities. Vent the system while it is being filled. Open the vent on the top of the evaporator during filling and close when filling is completed. Customer Note The use of improperly treated or untreated water in this equipment may result in scaling, erosion, corrosion, algae or slime. The services of a qualified water treatment specialist should be engaged to determine what treatment, if any, is advisable. The Trane Company warranty specifically excludes liability for corrosion, erosion or deterioration of Trane equipment. Trane assumes no responsibilities for the results of the use of untreated or improperly treated water, or saline or brackish water. Caution: Do not used untreated or improperly treated water. Equipment damage may occur. Caution: Do not fill the water systems unless the evaporator and Domestic Water Heater heat tapes have been energized. [ ] Close the fused-disconnect switch(es) that supplies power to the chilled water pump starter. [ ] Start the chilled water pump to begin circulation of the chilled water. Inspect all piping for leakage and make any necessary repairs. [ ] With chilled water circulating through the system, adjust water flow and check water pressure drop through the evaporator. Refer to Figure 23. [ ] Adjust the chilled water flow switch (if installed) for proper operation. [ ] Prove Chilled Water Pump Interlock and External Auto/Stop as described in Interconnecting Wiring: Chilled Water Pump Interlock and External Auto/Stop. Caution: Chilled Water Pump Interlock and External Auto/Stop information must be adhered to or equipment damage may occur. [ ] Check and set, as required, all UCM Menu items. [ ] Stop the chilled water pump. Unit Voltage Power Supply Voltage to the unit must meet the criteria given in Table 10. Measure each leg of the supply voltage at the unit main power fused-disconnect. If the measured voltage on any leg is not within specified range, notify the supplier of the power and correct the situation before operating the unit. Caution: Inadequate voltage to the unit can cause control components to malfunction and shorten the life of relay contact, compressor motors and contactors. Unit Voltage Imbalance Excessive voltage imbalance between the phases of a three-phase system can cause Motors to overheat and eventually fail. The maximum allowable imbalance is 2 percent. Voltage imbalance is determined using the following calculations: % Imbalance = (V x - V ave) x 100 V ave V ave = (V 1 + V 2 + V 3) / 3 V x = phase with greatest difference from V ave (without regard to sign) For example, if the three measured voltages are 221, 230, and 227 volts, the average would be: 221 +230 +227 = 226 3 The percentage of imbalance is then: 100 (221 - 226) = 2.2% 226 This exceeds the maximum allowable (2%) by 0.2 percent.
123RTAA-IOM-3 Unit Voltage Phasing It is important that proper rotation of the compressors be established before the unit is started. Proper motor rotation requires confirmation of the electrical phase sequence of the power supply. The motor is internally connected for clockwise rotation with the incoming power supply phased A, B, C. Basically, voltages generated in each phase of a polyphase alternator or circuit are called phase voltages. In a three-phase circuit, three sine wave voltages are generated, differing in phase by 120 electrical degrees. The order in which the three voltages of a three-phase system succeed one another is called phase sequence or phase rotation. This is determined by the direction of rotation of the alternator. When rotation is clockwise phase sequence is usually called “‘ABC”, when counterclockwise, “CBA”.This direction may be reversed outside the alternator by interchanging any two of the line wires. It is this possible interchange of wiring that makes a phase sequence indicator necessary if the operator is to quickly determine the phase rotation of the motor. Proper compressor motor electrical phasing can be quickly determined and corrected before starting the unit. Use a quality instrument, such as the Associated Research Model 45 Phase Sequence Indicator shown in Figure 55, and follow this procedure. WARNING IT IS IMPERATIVE THAT L1-L2-L3 IN THE STARTER BE CONNECTED IN THE A-B-C PHASE SEQUENCE TO PREVENT EQUIPMENT DAMAGE DUE TO REVERSE ROTATION. Figure 55 Associated Research Model 45 Phase Sequence Indicator
124RTAA-IOM-3 1. Turn the Chiller Switch on the UCM to the STOP/RESET position. 2. Open the electrical disconnect or circuit protection switch that provides line power to the line power terminal block(s) in the starter panel (or to the unit-mounted disconnect). 3. Connect the phase sequence indicator leads to the line power terminal block, as follows: Phase Seq. LeadTerminal Black (Phase A).................. L1 Red (Phase B).................... L2 Yellow (Phase C)................ L3 4. Turn power on by closing the unit supply power fused- disconnect switch. 5. Read the phase sequence on the indicator. The “ABC” LED on the face of the phase indicator will glow if phase is “ABC”. WARNING: To prevent injury or death due to electrocution, take extreme care when performing service procedures with electrical power energized. 6. If the “CBA” indicator glows instead, open the unit main power disconnect and switch two line leads on the line power terminal block(s) (or the unit mounted disconnect). Reclose the main power disconnect and recheck the phasing. Caution: Do not interchange any load leads that are from the unit contactors or the motor terminals. 7. Reopen the unit disconnect and disconnect the phase indicator. Water System Flow Rates Establish a balanced chilled water flow through the evaporator. The flow rates should fall between the minimum and maximum values given in Table 1. Chilled water flow rates below the minimum values will result in laminar flow, which reduces heat transfer and causes either loss of EXV control or repeated nuisance, low temperature cutouts. Flow rates that are too high can cause tube erosion and damage to the tube supports and baffles in the evaporator. Caution: Once the evaporator and Domestic Water Heater (optional) are filled with water, the heat tapes must be energized to protect the evaporator from freezing and bursting if the outdoor air temperature drops below freezing. Water System Pressure Drop Measure chilled water pressure drop through the evaporator at the field- installed pressure taps on the system water piping. See Figure 22. Use the same gauge for each measurement. Do not include valves, strainers fittings in the pressure drop readings. Measure the water pressure drop through the Domestic Water Heater at the field installed vent and drain connections. See Figure 24. Use the same gauge for each measurement. Do not include valves, strainers, fittings in pressure drop readings. Pressure drop readings should be approximately those shown in the Pressure Drop Charts, Figure 23 for the evaporator and Figure 25 for the Domestic Water Heater (optional). UCM Set-up Refer to “Menu Function Descriptions and Selection” for instruction on the set-up of the UCM.
125RTAA-IOM-3 Start-Up Procedures General If the pre-start checkout, as discussed above, has been completed, the unit is ready to start. UCM controls are shown in Figure 51 and UCM Sequence of Operation is shown in Figures 56 and 57. Complete each step, in sequence, as follows: [ ] Move the Chiller Switch on the UCM to the STOP/RESET position. [ ] As necessary, adjust the setpoint values in the UCM menus, as described in “Menu Function Descriptions and Selections”. [ ] Close the fused-disconnect switch for the chilled water pump. Energize the pump to start chilled water circulation. [ ] Check the service valves on the discharge line, suction line, oil line and liquid line for each circuit. These valves must be open (backseated) before starting the compressors. Caution: To prevent compressor damage, do not operate the unit until all refrigerant and oil line service valves are opened. [ ] Energize the compressor sump heaters, if not already energized. Also close the unit-mounted disconnect, if used. Caution: The compressor sump heaters must be energized for a minimum of 24 hours prior to unit operation, to prevent compressor damage caused by liquid refrigerant in the compressor at start-up. [ ] Verify that the evaporator heat tape is energized. [ ] Verify that the chilled water pump runs for one minute after the chiller is commanded to stop (for normal chilled water systems). See page [ ] Move the Chiller Switch to AUTO LOCAL. If the chiller control 1 U 1 calls for cooling and all safety interlocks are closed, the unit will start. The compressor(s) will load and unload in response to the temperature of the leaving chilled water temperature.If optional low-ambient is installed, outside air temperature must be above the minimum starting ambients, as shown in Table 1, for continued unit operation. Use Table 1 to determine proper setpoints for the optional low ambient lockout setpoint, if used. Also refer to the wiring diagrams in Figures 34 thru 36. Once the system has been operating for approximately 30 minutes and has become stabilized, complete the start- up procedures, as follows: [ ] Check the evaporator refrigerant pressure (23) and the condenser refrigerant pressure (25) in Menu 2 on the UCM. The pressures are referenced to sea level (14.6960 psia) [ ] Check the liquid line sight glasses. The refrigerant flow past the sight glasses should be clear. Bubbles in the refrigerant indicate either low refrigerant charge or excessive pressure drop in the liquid line. A restriction in the line can sometimes be identified by a noticeable temperature differential between the two sides of the restriction. Frost may often form on the line at this point. Proper refrigerant charges are shown in Table 1. Caution: A clear sight glass alone does not mean that the system is properly charged. Also check system superheat, subcooling, and unit operating pressures. [ ] Measure the system superheat. Refer to “System Superheat, below. [ ] Measure the system subcooling. Refer to “System Subcooling”, below. [ ] A shortage of refrigerant is indicated if operating pressures are low and subcooling is also low. If the operating pressures, sight glass, superheat and subcooling readings indicate a refrigerant shortage, gas- charge refrigerant into each circuit, as required. With the unit running, add refrigerant vapor by connecting the charging line to the suction service valve and charging through the backseat port until operating conditions become normal. Caution: If both suction and discharge pressures are low but subcooling is normal, a problem other than refrigerant shortage exists. Do not add refrigerant, as this may result in overcharging the circuit. Caution: Use only refrigerants specified on the unit nameplate, to prevent compressor damage and insure full system capacity. [ ] If operating conditions indicate a refrigerant overcharge, remove refrigerant at the liquid line service valve. Allow refrigerant to escape slowly, to minimize oil loss. Do not discharge refrigerant into the atmosphere. WARNING: Do not allow refrigerant to directly contact skin or injury from frostbite may result. System Superheat Normal superheat for each circuit is approximately 8 F at full operating load. Superheat temperature can be expected to be moving around the 8 F setpoint when the chiller is pulling down, the compressor slide valve is being modulated, or the fans are staging on either the same or opposite circuits. Superheat can be expected to settle out at approximately 8 F when the above items stabilize. System Subcooling Normal subcooling for each circuit ranges from 11 F to 20 F, depending on the unit. If subcooling for either circuit does not approximate these figures, check the superheat for the circuit and adjust, if required. If superheat is normal but subcooling is not, contact a qualified service technician.
126 RTAA-IOM-3 Figure 56 Unit Sequence of Operation – RTAA 240 to 400 Tons (Continued on Next Page)
127RTAA-IOM-3 (Continued from Previous Page) 2307-1566C
128 RTAA-IOM-3 Figure 57 Unit Sequence of Operation – RTAA 130 to 200 Tons 2306-9122A
129RTAA-IOM-3 Unit Shutdown Procedures Temporary Shutdown and Restart To shut the unit down for a short time, use the following procedure: 1. Move the Chiller Switch to STOP/ RESET. The compressors will continue to operate and, after unloading for 20 seconds, will stop when the compressor contactors de- energize. The condenser fans will be de-energized at this time. 2. The unit disconnect switch and unit mounted disconnect (if installed) should remain closed to keep the compressor sump heaters energized. 3. Maintain power to keep the evaporator and Domestic Water Heater heat tape(s) energized. 4. Stop the chilled water circulation by turning off the chilled water pump. To restart the unit after a temporary shutdown, restart the chilled water pump and move the Chiller Switch to either of the AUTO positions. The unit will start normally, provided the following conditions exist: 1. The UCM must receive a call for cooling and the differential- to-start must be above the setpoint. 2. All system operating interlocks and safety circuits must be satisfied. Extended Shutdown Procedure The following procedure is to be followed if the system is to be taken out of service for an extended period of time, e.g. seasonal shutdown: 1. Test the condenser and high-side piping for refrigerant leakage. 2. Open the electrical disconnect switches for the chilled water pump. Lock the switch in the “OPEN” position. Caution: Lock the chilled water pump disconnect open to prevent pump damage. 3. Close all chilled water supply valves. Drain the chilled water from the evaporator. If the unit will be exposed to freezing ambient conditions, flush the evaporator with an antifreeze solution and energize the evaporator heat tape. Caution: To prevent damage to the evaporator by freezing, flush the evaporator with an antifreeze solution and energize the evaporator heat tape. 4. Drain the Domestic Water Heater and any exposed system piping to prevent the possibility of freeze-up. Use the pressure tap on the water outlet to force compressed air through the water coils of the unit and assure that no water blocks any of the tubes. Be certain that the drain valve on the water inlet is open before applying compressed air to the water coils. Energize the Domestic Water Heater heat tape. Caution: To prevent damage to the Domestic Water Heater by freezing, blow out water from coils and energize the Domestic Water Heater heat tape. 5. Open the unit main electrical disconnect and unit-mounted disconnect (if installed) and lock on the “OPEN” position. If optional control power transformer is not installed, open and lock the 115 V disconnect. Caution: Lock the disconnects on the “OPEN” position to prevent accidental start-up and damage to the system when it has been setup for extended shutdown. 6. At least every three months (quarterly), check the pressure in the unit to verify that the refrigerant charge is intact.
130RTAA-IOM-3 System Restart After Extended Shutdown. Follow the procedures below to restart the unit after extended shutdown: 1. Verify that the liquid line service valves, oil line, compressor discharge service valves and suction service valves (if installed) are open (backseated). Caution: To prevent damage to the compressor, be sure that all refrigerant valves are open before starting the unit. 2. Close the main disconnect and unit mounted disconnect (if installed) to energize the compressor sump heaters. If the optional control transformer is not installed, it will be necessary to close the disconnect for 115 VAC power to 1TB3-1 and 1TB3-2. Caution: The compressor sump heaters must be energized for a minimum of 24 hours prior to unit operation, to prevent compressor damage caused by liquid refrigerant in the compressor at start-up. 3. Maintain power to the evaporator heat tape connections. 4. Check the oil separator oil level. See “Oil Separator Level Check”. 5. Fill the evaporator chilled water circuit. Refer to Table I for evaporator liquid capacities. Vent the system while it is being filled. Open the vent on the top of the evaporator during filling and close when filling is completed. Caution: Do not use untreated or improperly treated water. Equipment damage may occur. 6. Close the fused-disconnect switch that provides power to the chilled water pump. 7. Start the chilled water pump and, while chilled water is circulating, inspect all piping for leakage. Make any necessary repairs before starting the unit. 8. While the chilled water is circulating, adjust the chilled water flow and check the chilled water pressure drop through the evaporator. Refer to “Water System Flow Rates” and “Water System Pressure Drop”. 9. Adjust the flow switch on the evaporator piping (if installed) for proper operation. 10. Stop the chilled water pump. The unit is now ready for start-up as described in “Start-Up Procedures”.