Home
>
Panasonic
>
Air Conditioner
>
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
1-65 1. Specifications 3. SELECTING THE INSTALLATION SITE 3-1. Outdoor Unit AVOID: heat sources, exhaust fans, etc. (Fig. 1-3) damp, humid or uneven locations DO: choose a place as cool as possible. choose a place that is well ventilated and outside air temperature does not exceed maximum 115°F constantly. allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig. 1-4) use lug bolts or equal to bolt down unit, reducing vibration and noise. if cooling operation is to be used when the outdoor air temperature is 23°F or below, install a duct on the outdoor unit. Installation space Distance between obstructions and the unit air inlet and outlet must be as shown below. Installation requirements provide a solid base (concrete block, 4×16 beams or equal), a minimum of 6 above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 1-6) use lug bolts or equal to bolt down unit, reducing vibration and noise.Fig. 1-5 Out- door unitHeat source Hot airExhaust fan *4 *2*3 *1 More than 1/2 More than 3.3 ft.More than 1/2 Inlet side C Outlet side *1Inlet side More than 8 (field supply) AB (Ground) Air direction chamber(Obstruction above unit) (Obstruction on inlet side) Anchor bolts (4 pieces) Fig. 1-4Fig. 1-3 Fig. 1-6 CAUTION Concerning inlet-side distance “C” (Fig. 1-4) The minimum for distance “C” is 6 if there are no obstructions on the outlet side (wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance “C” is 8. If the unit is installed with the outlet side facing wall *1, then there must be no obstructions on 2 of the remaining 3 sides: *2, *3, *4. If wall *1 is on the outlet side (Fig. 1-4), or if obstructions are present on all 3 sides *2, *3, and *4 (Fig. 1-4), then the minimum distance for “A” and “B” is 80 (Fig. 1-5). Even if there is no wall on the outlet side, a minimum of 3.3 ft. is required. 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-66 1. Specifications 3-2. Air-Discharge Chamber for Top Discharge Be sure to install an air discharge chamber in the field when: it is difficult to keep a space of min. 20 between the air discharge outlet and an obstacle. the air discharge outlet is facing a sidewalk and discharged hot air may bother passers-by. Refer to Fig. 1-7. 3-3. Installing the Unit in Heavy Snow Areas In locations with strong wind, snow-proof ducting should be fitted and direct exposure to the wind should be avoided as much as possible. Countermeasures against snow and wind In regions with snow and strong wind, the following problems may occur when the outdoor unit is not provided with a platform and snow-proof ducting: a) unit may occur. b) c) d)The outdoor fan may not run and damage to the There may be no air flow. The tubing may freeze and burst. The condenser pressure may drop because of strong wind, and the indoor unit may freeze. 3-4. Precautions for Installation in Heavy Snow Areas (1) depth. (Fig. 1-8) (2) used for the platform, and the platform should be installed beneath the air intake side of outdoor unit. (3) must be secured with anchor bolts. (4)The platform should be higher than the max. snow The 2 anchoring feet of the outdoor unit should be The platform foundation must be firm and the unit In case of installation on a roof subject to strong wind, countermeasures must be taken to prevent the unit from being blown over.Fig. 1-7 Fig. 1-8 Fig. 1-9 In regions with significant snowfall, the outdoor unit should be provided with a platform and snow-proof duct. Air discharge Air discharge Without snow- proof ducting (Low platform)With snow- proof ducting (High platform) Outdoor Duct Air Unit Intake 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-67 1. Specifications 3-5. Dimensions of Wind Ducting Reference diagram for air-discharge chamber ( eld supply) For U-26PE(S)1U6 / U-36PE(S)1U6 unit ƒAir discharge chamber „Air discharge chamber (base) For U-42PE(S)1U6 unit ƒUnit front, air discharge chamber „Unit left side, air discharge chamber …Unit right side, air discharge chamber †Reinforcement brackets, 4 locations Note: In snowy regions, if there is concern that snow may enter the air discharge chamber, remove the base of the chamber (10 screws) before using. 1 2(25/32)(25/32) (25/32) (25/32)21-13/16 9-7/8 22-7/16 23-15/32 1-1/165-5/32 5-3/16 9-27/32 9-27/32 21-13/1615/16 17/32 21-39/64 2 Rectangular hole (both sides) 6-ø15/64 hole 3-ø5/32 hole Unit: inch 9-7/16 1-1/8 1-1/8 1-3/8 21-5/32 12-15/32 2-3/4 Rectangular holeRectangular hole Rectangular holeRectangular hole 11-13/162 143 9-7/161-3/8 12-15/32 21-5/32 2-3/4 21-13/32 1 122-13/32 42-29/3239-1/49-27/32 9-27/32 12-7/32 9-27/32 Unit: inch 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-68 1. Specifications Dimensions of Outdoor Unit with air-discharge chamber ( eld supply) U-26PE(S)1U6 / U-36PE(S)1U6 unit U-42PE(S)1U6 unit 13-3/8 2-17/32 21-13/161/2 6-11/16 25-31/324-5/16 2 / 1 2 / 1 14-31/32 15-15/16 19/322 3 / 5 2 2 3 / 5 2 13/32 Wind direction Wind direction Wind direction Wind direction Wind direction 37 30-23/32 23/32 9-7/8 21-5/8 4-1/16 5-3/16 Wind direction Unit: inch 4-5/16 25-31/32 6-11/16 1/2 1/2 13-3/8 15-15/16 14-31/32 13/32 19/3225/32 25/32 1/2 2-11/36 21-13/32 11 - 1 3 / 1 6 Wind direction Wind direction 37 23/3248-7/16 Wind direction Wind directionWind direction Wind direction 11-13/16 4-1/4 39-1/4Wind direction Wind direction Unit: inch 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-69 1. Specifications Reference diagram for air-discharge chamber ( eld supply) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 Required space around outdoor unit If the air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating. (1) Single-unit installation (2) Multiple-unit installation Installation in lateral rows Installation in front-rear rows CAUTIONThe top and both sides must remain open. If there are obstacles to the front and rear of the outdoor unit, the obstacle at either the front or rear must be no taller than the height of the outdoor unit. CAUTIONThe front and top must remain open. The obstacles must be no taller than the height of the outdoor unit. CAUTIONThe front and both sides must remain open. Min. 39-3/8 Min. 7-7/8 Unit: inch More than 15-3/4 6 1 / 3 1 - 1 1 n a h t e r o M 6 1 / 3 1 - 1 1 n a h t e r o M More than 7-7/8 Unit: inch Installation with intakes facing outlets Installation with intakes facing intakes or outlets facing outlets More than 78-3/4 More than 15-3/4 More than 59-1/16 Unit: inch 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-70 1. Specifications 3-6. Dimensions of Snow Ducting Reference diagram for snow-proof vents ( eld supply) For U-26PE(S)1U6 / U-36PE(S)1U6 unit ƒUnit top, snow-proof vent „Unit left side …Unit right side †Unit reverse side ‡Unit reverse side ˆUnit sides, reinforcement brackets for snow-proof vent For U-42PE(S)1U6 unit ƒUnit top, snow-proof vent „Unit left side …Unit right side †Unit reverse side ‡Unit reverse side ˆUnit sides, reinforcement brackets for snow-proof vent 25-13/32 17-15/32 9-3/16 16-25/32 27-29/32 3-31/3211-29/32 16-25/329-3/16 27-29/32 30-3/32 1 4 56 2 1-21/32 25/325-3/32 19-11/16 9-3/8 30-11/1628-3/4 19-11/16 5/8 13-25/32 3-3/4 Fastened by screws at 13 locations Fastened by screws at 3 locations (also on reverse side) Fastened by screw at 1 location (also on reverse side)Unit anchor hole (6 – ø7 hole) Unit: inch 17-15/32 25-13/32 9-3/16 28-13/16 15-9/32 47-19/32 2 311-7/8 3-31/32 9-3/16 28-13/16 1-13/16 47-19/32 30-3/32 1 4 5-29/32 17-23/32 19-11/16 25-32 13-5/16 19-11/16 1-5/8 28-3/4 30-5/85/8 3-3/4 19-11/16 Fastened by screws at 13 locations Fastened by screws at 3 locations (also on reverse side) Fastened by screw at 1 location (also on reverse side) Unit anchor hole (7 – ø7 hole) Unit: inch 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-71 1. Specifications Dimensions of outdoor unit with snow-proof vents ( eld supply) U-26PE(S)1U6 / U-36PE(S)1U6 unit U-42PE(S)1U6 unit 11-57/64 16-47/6415-15/16 14-61/64 25/64 19/3225/32 30-5/64 25-25/64 7-3/64 3/4 30-45/64 37-1/64 Wind direction Wind direction Wind direction Wind direction Wind direction Wind direction Unit: inch 11-57/64 28-13/16 Wind direction Wind direction Wind direction Wind direction Wind direction Wind direction 48-27/64 47-19/32 37-1/64 24-7/8 15-15/1614-61/64 25/64 19/3225/32 25/32 30-5/64 25-25/64 7-3/64 Unit: inch 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-72 1. Specifications Reference diagram for snow-proof vents – 1 Space requirements for setting – (1) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 ] t i n u f o t n o r f e h t o t e l c a t s b O [ ] t i n u f o r a e r e h t o t e l c a t s b O [ : n e p o s i p o T : n e p o s i p o T Top is blocked by an obstacle: Top is blocked by an obstacle: Unit: inch Min. C Min. E Min. FMin. E Min. EMin. B Min. A Min. D Min. G (1) Single-unit installation (3) Multiple-unit installation (2 or more units) Note: In cases 2 and 3 the height of the obstacle must be no taller than the height of the outdoor unit. (2) Obstacles on both sides A B C D E F G5-29/32 5-29/32 11-13/16 7-7/8 11-13/16 5-29/32 7-7/8 Min. I Min. I Min. H Min. J (1) Single-unit installation (2) Multiple-unit installation (2 or more units) H 19-11/16I 11-13/16J 39-3/8 Min. L Min. K L 19-11/16K 5-29/32 Min. MMin. N M 39-3/8N 39-3/8 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-73 1. Specifications Reference diagram for snow-proof vents – 2 Space requirements for setting – (2) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit. [Installation in front-rear rows] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit. Unit: inch Min. 11-13/36Min. 11-13/16 Min. 39- 3/8 Min . 7-7/8 Q Q Min . P Min. O (1) Single-unit installation (2) Obstacles on both sidesDimension Q If a snow protection duct is attached after the unit is installed, verify that dimension Q is 19-11/16 in. or more. O 39-3/8P 5-29/32 Min. 11-13/16 Min. 39-3/8Min. 7-7/8 Min. 59-1/16 Min. 78-3/4Q Dimension Q If a snow protection duct is attached after the unit is installed, verify that dimension Q is 19-11/16 in. or more. 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-74 1. Specifications 4. HOW TO INSTALL THE OUTDOOR UNIT 4-1. Installing the Outdoor Unit Use concrete or a similar material to create the base, and ensure good drainage. Ordinarily, ensure a base height of 2. or more. If a drain pipe is used, or for use in cold-weather regions, ensure a height of 6. or more at the feet on both sides of the unit. (In this case, leave clearance below the unit for the drain pipe, and to prevent freezing of drainage water in cold-weather regions.) Refer to the Fig. 1-10 for the anchor bolt dimensions. Be sure to anchor the feet with the anchor bolts (M10). In addition, use anchoring washers on the top side. (Use large square 32×32 SUS washers with diameters of 10.) (Field supply) 4-2. Drainage Work Follow the procedure below to ensure adequate draining for the outdoor unit. For the drain port dimensions, refer to the gure at right. Ensure a base height of 6 in. or more at the feet on both sides of the unit. 4-3. Routing the Tubing and Wiring The tubing and wiring can be extended out in 4 directions: front, rear, right, and down. The service valves are housed inside the unit. To access them, remove the inspection panel. (To remove the inspection panel, remove the 3 screws, then slide the panel downward and pull it toward you.) (1) If the routing direction is through the front, rear, or right, use a nipper or similar tool to cut out the knockout holes for the inter-unit control wiring outlet, power wiring outlet, and tubing outlet from the appropriate covers A and B. (2) If the routing direction is down, use a nipper or similar tool to cut out the lower ange from cover A. CAUTION Route the tubing so that it does not contact the compressor, panel, or other parts inside the unit. Increased noise will result if the tubing contacts these parts. When routing the tubing, use a tube bender to bend the tubes.Fig. 1-10 Fig. 1-11 37-1/64 11-21/32 5-29/32 8-5/8 33/64 33/64 25/3225/32 19/3225/64 14-61/64 15-15/1613-25/64 33/64 33/64 6-11/16 4-21/64 25-63/64 Drain port (2 locations) Drain port Anchor bolt (M10) Unit: inch Inter-unit control wiring outlet Inspection panel Cover ACover B Power wiring outlet Tubing outlet Down FrontRear Right 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC