Home > Panasonic > Air Conditioner > Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual

Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							1-65
    1. Specifications
    3. SELECTING THE INSTALLATION SITE
    3-1. Outdoor Unit
    AVOID:
     
    heat sources, exhaust fans, etc. (Fig. 1-3)
     
    damp, humid or uneven locations
    DO:
    choose a place as cool as possible.
     
    choose a place that is well ventilated and outside
    air temperature does not exceed maximum 115°F 
    constantly.
    allow enough room around the unit for air intake/ 
    exhaust and possible maintenance. (Fig. 1-4)
     
    use lug bolts or equal to bolt down unit, reducing 
    vibration and noise.
    if cooling operation is to be used when the outdoor air 
    temperature is 23°F or below, install a duct on
    the outdoor unit.
    Installation space
    Distance between obstructions and the unit air inlet
    and outlet must be as shown below.
    Installation requirements
    provide a solid base (concrete block, 4×16
    beams or equal), a minimum of 6 above ground
    level to reduce humidity and protect the unit against
    possible water damage and decreased service life.
    (Fig. 1-6)
    use lug bolts or equal to bolt down unit, reducing 
    vibration and noise.Fig. 1-5
    Out-
    door
    unitHeat source Hot airExhaust fan
    *4 *2*3
    *1
    More than 1/2
    More than
    3.3 ft.More than 1/2 Inlet side C
    Outlet side
    *1Inlet side 
    More than 8
    (field supply)
    AB
    (Ground)
    Air direction chamber(Obstruction above unit)
    (Obstruction on 
    inlet side)
    Anchor bolts
    (4 pieces)
    Fig. 1-4Fig. 1-3
    Fig. 1-6
    CAUTION
    Concerning inlet-side distance “C” (Fig. 1-4)
    The minimum for distance “C” is 6 if there are no obstructions on the outlet side
    (wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance
    “C” is 8.
     
    If the unit is installed with the outlet side facing wall *1, then there must be no obstructions
    on 2 of the remaining 3 sides: *2, *3, *4.
    If wall *1 is on the outlet side (Fig. 1-4), or if obstructions are present on all 3 sides *2,
    *3, and *4 (Fig. 1-4), then the minimum distance for “A” and “B” is 80 (Fig. 1-5). Even
    if there is no wall on the outlet side, a minimum of 3.3 ft. is required.
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-66
    1. Specifications
    3-2. Air-Discharge Chamber for Top Discharge
    Be sure to install an air discharge chamber in the
    field when:
     
    it is difficult to keep a space of min. 20 between
    the air discharge outlet and an obstacle.
     
    the air discharge outlet is facing a sidewalk and
    discharged hot air may bother passers-by.
    Refer to Fig. 1-7.
    3-3. Installing the Unit in Heavy Snow Areas
    In locations with strong wind, snow-proof ducting
    should be fitted and direct exposure to the wind
    should be avoided as much as possible.
     Countermeasures against snow and wind
    In regions with snow and strong wind, the following
    problems may occur when the outdoor unit is not provided
    with a platform and snow-proof ducting:
    a)
    unit may occur.
    b)
    c)
    d)The outdoor fan may not run and damage to the
    There may be no air flow.
    The tubing may freeze and burst.
    The condenser pressure may drop because of
    strong wind, and the indoor unit may freeze.
    3-4. Precautions for Installation in Heavy Snow Areas
    (1)
    depth. (Fig. 1-8)
    (2)
    used for the platform, and the platform should be
    installed beneath the air intake side of outdoor unit.
    (3)
    must be secured with anchor bolts.
    (4)The platform should be higher than the max. snow
    The 2 anchoring feet of the outdoor unit should be
    The platform foundation must be firm and the unit
    In case of installation on a roof subject to strong
    wind, countermeasures must be taken to prevent
    the unit from being blown over.Fig. 1-7
    Fig. 1-8
    Fig. 1-9
    In regions with significant snowfall, the outdoor unit should
    be provided with a platform and snow-proof duct.
    Air discharge
    Air discharge
    Without snow-
    proof ducting
    (Low platform)With snow-
    proof ducting
    (High platform)
    Outdoor
    Duct
    Air Unit
    Intake
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-67
    1. Specifications
    3-5. Dimensions of Wind Ducting
    Reference diagram for air-discharge chamber ( eld supply)
    For U-26PE(S)1U6 / U-36PE(S)1U6 unit
    ƒAir discharge chamber
    „Air discharge chamber (base)
    For U-42PE(S)1U6 unit
    ƒUnit front, air discharge chamber
    „Unit left side, air discharge chamber
    …Unit right side, air discharge chamber
    †Reinforcement brackets, 4 locations
    Note: In snowy regions, if there is concern that snow may enter the air discharge
    chamber, remove the base of the chamber (10 screws) before using.
    1
    2(25/32)(25/32) (25/32)
    (25/32)21-13/16
    9-7/8
    22-7/16
    23-15/32
    1-1/165-5/32
    5-3/16
    9-27/32 9-27/32
    21-13/1615/16 17/32
    21-39/64
    2
    Rectangular hole
     (both sides)
    6-ø15/64 hole
    3-ø5/32 hole
    Unit: inch
    9-7/16 1-1/8
    1-1/8
    1-3/8
    21-5/32 12-15/32
    2-3/4
    Rectangular
    holeRectangular
    hole
    Rectangular
    holeRectangular
    hole
    11-13/162
    143
    9-7/161-3/8 12-15/32 21-5/32
    2-3/4
    21-13/32 1 122-13/32
    42-29/3239-1/49-27/32
    9-27/32
    12-7/32
    9-27/32
    Unit: inch
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-68
    1. Specifications
    Dimensions of Outdoor Unit with air-discharge chamber ( eld supply)
    U-26PE(S)1U6 / U-36PE(S)1U6 unit
    U-42PE(S)1U6 unit
    13-3/8
    2-17/32
    21-13/161/2 6-11/16
    25-31/324-5/16
    2 / 1 2 / 1
    14-31/32
    15-15/16 19/322
    3 / 5 2 2 3 / 5 2
    13/32
    Wind direction
    Wind
    direction
    Wind direction
    Wind direction
    Wind direction
    37
    30-23/32
    23/32
    9-7/8
    21-5/8 4-1/16
    5-3/16
    Wind direction
    Unit: inch
    4-5/16
    25-31/32 6-11/16
    1/2 1/2
    13-3/8
    15-15/16 14-31/32 13/32 19/3225/32 25/32
    1/2
    2-11/36 21-13/32
    11 - 1 3 / 1 6
    Wind
    direction
    Wind direction
    37
    23/3248-7/16
    Wind
    direction Wind
    directionWind
    direction Wind
    direction
    11-13/16
    4-1/4 39-1/4Wind direction
    Wind direction
    Unit: inch
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-69
    1. Specifications
    Reference diagram for air-discharge chamber ( eld supply)
    U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6
    Required space around outdoor unit
    If the air discharge chamber is used, the space shown below must be secured around the outdoor unit.
    If the unit is used without the required space, a protective device may activate, preventing the unit from operating.
    (1) Single-unit installation
    (2) Multiple-unit installation
       Installation in lateral rows
       Installation in front-rear rows
    CAUTIONThe top and both sides must remain open. If there are obstacles to the front and rear of
    the outdoor unit, the obstacle at either the front or rear must be no taller than the height of
    the outdoor unit.
    CAUTIONThe front and top must remain open.
    The obstacles must be no taller than the height of the outdoor unit.
    CAUTIONThe front and both sides must remain open.
    Min. 39-3/8
    Min. 7-7/8
    Unit: inch
    More than 15-3/4
    6 1 / 3 1 - 1 1 n a h t e r o M 6 1 / 3 1 - 1 1 n a h t e r o M
    More than 7-7/8
    Unit: inch
    Installation with intakes facing outlets Installation with intakes facing
    intakes or outlets facing outlets
    More than 78-3/4 More than 15-3/4
    More than 59-1/16
    Unit: inch
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-70
    1. Specifications
    3-6. Dimensions of Snow Ducting
    Reference diagram for snow-proof vents ( eld supply)
    For U-26PE(S)1U6 / U-36PE(S)1U6 unit
    ƒUnit top, snow-proof vent
    „Unit left side
    …Unit right side
    †Unit reverse side
    ‡Unit reverse side
    ˆUnit sides, reinforcement brackets for snow-proof vent
    For U-42PE(S)1U6 unit
    ƒUnit top, snow-proof vent
    „Unit left side
    …Unit right side
    †Unit reverse side
    ‡Unit reverse side
    ˆUnit sides, reinforcement brackets for snow-proof vent
    25-13/32
    17-15/32
    9-3/16 16-25/32 27-29/32
    3-31/3211-29/32
    16-25/329-3/16
    27-29/32
    30-3/32
    1
    4
    56
    2
    1-21/32
    25/325-3/32
    19-11/16
    9-3/8
    30-11/1628-3/4 19-11/16
    5/8
    13-25/32
    3-3/4
    Fastened by screws at 13 locations
    Fastened by screws at 3 locations 
    (also on reverse side)
    Fastened by screw at 1 
    location (also on reverse side)Unit anchor hole 
    (6 – ø7 hole)
    Unit: inch
    17-15/32 25-13/32
    9-3/16 28-13/16
    15-9/32
    47-19/32
    2 311-7/8
    3-31/32
    9-3/16
    28-13/16
    1-13/16
    47-19/32
    30-3/32
    1
    4
    5-29/32
    17-23/32 19-11/16
    25-32
    13-5/16
    19-11/16
    1-5/8 28-3/4
    30-5/85/8 3-3/4 19-11/16
    Fastened by screws at 13 locations
    Fastened by screws at 
    3 locations (also on reverse side)
    Fastened by screw at 
    1 location (also on reverse side)
    Unit anchor hole 
    (7 – ø7
     hole)
    Unit: inch
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-71
    1. Specifications
    Dimensions of outdoor unit with snow-proof vents ( eld supply)
    U-26PE(S)1U6 / U-36PE(S)1U6 unit
    U-42PE(S)1U6 unit
    11-57/64
    16-47/6415-15/16 14-61/64 25/64 19/3225/32
    30-5/64
    25-25/64
    7-3/64
    3/4 30-45/64
    37-1/64 Wind direction
    Wind direction Wind direction
    Wind direction
    Wind direction
    Wind direction
    Unit: inch
    11-57/64
    28-13/16
    Wind direction
    Wind direction
    Wind direction
    Wind direction
    Wind direction Wind direction
    48-27/64
    47-19/32
    37-1/64
    24-7/8
    15-15/1614-61/64 25/64 19/3225/32 25/32
    30-5/64
    25-25/64
    7-3/64
    Unit: inch
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-72
    1. Specifications
    Reference diagram for snow-proof vents – 1
    Space requirements for setting – (1)
    U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6
    ] t i n u   f o   t n o r f   e h t   o t   e l c a t s b O [ ] t i n u   f o   r a e r   e h t   o t   e l c a t s b O [
    : n e p o   s i   p o T     : n e p o   s i   p o T  
     Top is blocked by an obstacle:
    Top is blocked by an obstacle:
    Unit: inch
    Min. C
    Min. E
    Min. FMin. E Min. EMin. B
    Min. A
    Min. D Min. G
    (1) Single-unit installation
    (3) Multiple-unit installation (2 or more units)
    Note:
    In cases 2 and 3 the 
    height of the obstacle 
    must be no taller than 
    the height of the 
    outdoor unit. (2) Obstacles on both sides
    A
    B
    C
    D
    E
    F
    G5-29/32
    5-29/32
    11-13/16
    7-7/8
    11-13/16
    5-29/32
    7-7/8
    Min. I Min. I
    Min. H
    Min. J
    (1) Single-unit installation
    (2) Multiple-unit installation (2 or more units)
    H
    19-11/16I
    11-13/16J
    39-3/8
    Min. L
    Min. K
    L
    19-11/16K
    5-29/32
    Min. MMin. N
    M
    39-3/8N
    39-3/8
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-73
    1. Specifications
    Reference diagram for snow-proof vents – 2
    Space requirements for setting – (2)
    U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6
    [Obstacles to the front and rear of unit]
     The top and both sides must remain open. Either the obstacle to the front or
        the obstacle to the rear must be no taller than the height of the outdoor unit.
    [Installation in front-rear rows]
       The top and both sides must remain open. Either the obstacle to the front or the obstacle
        to the rear must be no taller than the height of the outdoor unit.
    Unit: inch
    Min. 11-13/36Min. 11-13/16
    Min. 39-
    3/8
    Min
    . 7-7/8
    Q
    Q Min
    . P Min. O
     (1) Single-unit installation
    (2) Obstacles on both sidesDimension Q
    If a snow protection duct is attached after the unit is
    installed, verify that dimension Q is 19-11/16 in. or more.
    O
    39-3/8P
    5-29/32
    Min. 11-13/16
    Min. 39-3/8Min. 7-7/8
    Min. 59-1/16 Min. 78-3/4Q
    Dimension Q
    If a snow protection duct is
    attached after the unit is
    installed, verify that dimension
    Q is 19-11/16 in. or more.
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-74
    1. Specifications
    4. HOW TO INSTALL THE OUTDOOR UNIT
    4-1. Installing the Outdoor Unit
     Use concrete or a similar material to create the base, 
    and ensure good drainage.
     Ordinarily, ensure a base height of 2. or more. If a 
    drain pipe is used, or for use in cold-weather regions, 
    ensure a height of 6. or more at the feet on both sides 
    of the unit. (In this case, leave clearance below the unit 
    for the drain pipe, and to prevent freezing of drainage 
    water in cold-weather regions.)
     Refer to the Fig. 1-10 for the anchor bolt dimensions.
     Be sure to anchor the feet with the anchor bolts (M10). 
    In addition, use anchoring washers on the top side. (Use 
    large square 32×32 SUS washers with diameters of 
    10.) (Field supply)
    4-2. Drainage Work
    Follow the procedure below to ensure adequate draining 
    for the outdoor unit.
     For the drain port dimensions, refer to the  gure at 
    right.
       Ensure a base height of 6 in. or more at the feet on 
    both sides of the unit.
    4-3. Routing the Tubing and Wiring
     The tubing and wiring can be extended out in 4 
    directions: front, rear, right, and down.
       The service valves are housed inside the unit. To 
    access them, remove the inspection panel. (To remove 
    the inspection panel, remove the 3 screws, then slide 
    the panel downward and pull it toward you.)
    (1) If the routing direction is through the front, rear, 
    or right, use a nipper or similar tool to cut out the 
    knockout holes for the inter-unit control wiring outlet, 
    power wiring outlet, and tubing outlet from the 
    appropriate covers A and B.
    (2) If the routing direction is down, use a nipper or similar 
    tool to cut out the lower  ange from cover A.
    CAUTION
     Route the tubing so that it does 
    not contact the compressor, 
    panel, or other parts inside the 
    unit. Increased noise will result if 
    the tubing contacts these parts.
       When routing the tubing, use a 
    tube bender to bend the tubes.Fig. 1-10
    Fig. 1-11
    37-1/64
    11-21/32
    5-29/32 8-5/8
    33/64 33/64
    25/3225/32
    19/3225/64 14-61/64
    15-15/1613-25/64
    33/64 33/64 6-11/16
    4-21/64
    25-63/64
    Drain port (2 locations)
    Drain port Anchor bolt (M10)
    Unit: inch
    Inter-unit control wiring outlet
    Inspection panel
    Cover ACover B
    Power wiring outlet
    Tubing outlet Down FrontRear
    Right
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual