Home
>
Panasonic
>
Air Conditioner
>
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
4-7 4. Service procedures Judgment condition Clear condition F31 L02 L04 L07 L10 L13 E07 E06 E14 E15 E16 E20 E31 H01 Remote controller alarm displayAlarm contentsJudgment and correction Automatic recovery EEPROM trouble Reading/writing failure Recovery at power reset1. Check EEPROM (IC007). 2. Check outdoor unit control PCB. Mismatch of indoor and outdoor unit types (Espacio, Multi )Indoor unit judges that type does not match outdoor unit type.Recovery at power reset1. Check indoor unit EEPROM. 2. Check indoor unit control PCB. Settings failure Settings failure Settings failureDuplicated outdoor unit address (system address)1. Check outdoor unit system address. 2. Check inter-unit control wiring. Group control wiring is connected to an independent-control indoor Recovery at power reset1. Check inter-unit control wiring. 2. Check indoor unit EEPROM. Outdoor unit capacity not set. Recovery at power resetCheck outdoor unit EEPROM. Indoor-outdoor unit typesOutdoor unit judges that type does not match indoor unit type.Recovery at power reset1. Check indoor unit EEPROM. 2. Check outdoor unit control PCB. Outdoor unit detected abnormal signal from indoor unit.Serial signal receiving failure (including failure to verify No. of units) Automatic recovery Automatic recovery1. Check inter-unit control wiring. 2. Check outdoor unit Outdoor unit sending failure to indoor unitl o r t n o c t i n u - r e t n i k c e h C . 1 e r u l i a f g n i d n e s l a n g i s l a i r e S wiring. 2. Check outdoor unit control PCB. Settings failure Duplicated master unit in simultaneous-operation multi control (Detected by outdoor unit)Recovery at power reset1. Check inter-unit control wiring. 2. Check indoor unit combination. Automatic address setting failure Automatic address setting failure Automatic address setting failureIndoor unit capacity too low. Recovery at power reset Recovery at power reset Recovery at power reset1. Check inter-unit control wiring. 2. Check outdoor unit control PCB. l o r t n o c t i n u - r e t n i k c e h C . 1 . h g i h o o t y t i c a p a c t i n u r o o d n I wiring. 2. Check outdoor unit control PCB. Outdoor unit cannot receive any serial signals from indoor units.1. Check inter-unit control wiring. 2. Check outdoor unit control PCB. Communications trouble within unitNo communication possible with MDC for 3 minutes or longer.Automatic recover y Check outdoor unit control PCB. Overcurrent Inverter stops after alarm is detected.Recovery at restart 1. Refrigerant cycle trouble, overload operation 2. Loose screws between HIC control PCB and radiating plate 3. Cooling failure of radiating plate 4. Check outdoor unit PCB wiring. 4 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
4-8 4. Service procedures No No No No NoNo No No No Ye s Ye s Ye sYe s Ye s Ye s Ye s Ye s Ye s [Alarm “P29”] (MDC trouble) (1) Input power detection circuit trouble Compressor does not run. Breakdown Motor current detection circuit trouble Is power OK? Correct power line. Is current detection circuit wiring OK?Check and correct wiring. Are wiring and connector connections OK?Check and correct wiring. Is compressor OK? Ground fault?Replace compressor. Coil resistor short circuit? Coil open circuit? Is there abnormal refrigerant accumulation?Replace compressor. Is operation of electronic control valve OK? Replace outdoor unit control PCB. Are C1 and TS sensors OK? Replace C1 and TS sensors. Replace electronic control valve. Is there overload? Remove the cause. 4-3. Details of Alarm Messages 4 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
4-9 4. Service procedures No No No NoNo No No Ye s Ye s Ye s Ye s Ye s Ye s Ye s Replace outdoor unit control PCB. (2) [Alarm “P26”] HIC PCB trouble)IGBT short-circuit protection on inverter control (IPDU) PCB Is power OK? Correct power line. Are circuit wiring, connector connections, and reactor connections OK? Correct. Has filter PCB RY001 or RY002 relay activated? Has filter PCB AC fuse blown? Replace filter PCB. Disconnect U.V.W. output terminal on HIC PCB and start operation. Does alarm “P26” occur? Replace HIC PCB. Is compressor OK? (Check for layer short circuit.) Replace compressor. Is resistance between each terminal on HIC PCB OK? (See following page.) Check HIC PCB. Replace if PCB has failed. 4 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
4-10 4. Service procedures HIC +Between terminals Resistance HIC + HIC + HIC + HIC – HIC – HIC –HIC – U V W U V W Resistance 200 kΩ or more 300 kΩ or more 300 kΩ or more 300 kΩ or more 200 kΩ or more 200 kΩ or more 200 kΩ or more No Ye s Replace outdoor unit control PCB. (3) [Alarm “E31”] (communications trouble within unit)IGBT short-circuit protection Is “E31” displayed even after the power voltage is reset?Normal HIC-CH4872R (42 Type)HIC-CH2672R (26, 36 Type) 4 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
4-11 4. Service procedures No No No No Ye s Ye s Ye s Ye s (4) [Alarm P22]Outdoor unit fan motor drive circuit trouble Are connectors CN003 and CN004 connected correctly to the outdoor unit control PCB? Correct the connector connections. Disconnect connectors CN003 and CN004 from outdoor unit control PCB, and rotate fan by hand. Does it rotate easily? Outdoor unit fan motor coil resistance is OK if it is as shown below. (1) Red – white: 30 – 40 Ω (2) White – black: 30 – 40 Ω (3) Black – red: 30 – 40 Ω * Disconnect connector CN004 and measure on the plug side. Motor position detection circuit resis- tance is OK if it is as shown below. * Disconnect connector CN003 and measure on the plug side. (1) Grey – yellow: 100 kΩ or more, or ∞ (open) (2) Grey – blue: 100 kΩ or more, or ∞ (open) (3) Grey – orange: 100 kΩ or more, or ∞ (open) Fan motor is OK; outdoor unit control PCB has failed. → Replace.Fan motor trouble → Replace. Note: In the case of a GND circuit failure inside the motor, the results of the above check may be OK. If operation is not OK after the outdoor unit control PCB has been replaced, then replace the outdoor unit fan motor. 4 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
4-12 4. Service procedures No No Ye s Ye s Check the outdoor unit control PCB. Replace if PCB has failed. Sensor trouble (5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”] Are connectors CN020, 021, 022, 023, and 024 (TD, TO, C1, C2, and TS sensors) connected correctly to the outdoor unit control PCB? Correct the connector connections. Are the TD, TO, C1, C2, and TS sensor resistance* characteristics OK? Replace the TD, TO, C1, C2, or TS sensor. * Refer to “4-4. Table of Thermistor Characteristics.” 4 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
4-13 4. Service procedures Sensor installation Sensor Sensor typeSensor Sensor type s s e r d d a s s e r d d a n o i t a c o l 00 Room temp. 05 – (temp. used for control)* 01 Remote controller temp. 06 Discharge temp. Indoor unit 02 Indoor intake temp. 07 – 03 Indoor heat exchanger temp. (E1 ) 08 – 04 Indoor heat exchanger temp. (E2 ) 09 – 0A Discharge temp. (TD ) 12 – – 3 1 – b 0 t n e r r u C 4 1 – C 0 (AC current) Outdoor unit 0d Intake temp. (TS ) 15 Outdoor electronic control valve position 0E Outdoor heat exchanger temp. (C1 ) 16 – 0F Outdoor heat exchanger temp. (C2 ) 17 – – 8 1 – 0 1 11 Outdoor air temp. 19 – Sensor Temperature Correlation Table * Main unit only when group control is enabled Figure: Sample display when discharge temperature at unit No. 1-1 is 185F Sensor Temperature Display Function (Displayed both when operating and stopped) The below check procedure can be used to display all remote controller, indoor unit, and outdoor unit sensor temperatures. (1) Press and hold the button and button simultaneously for 4 seconds or longer. (2) Unit No. X-X (main unit No.), item code XX (sensor address), and service monitor 00XX (sensor tem- perature) appear on the remote controller LCD. (See figure.) (3) Press the temperature setting and buttons and change the item code to the sensor address of the sensor that you want to monitor. (For the relationship between the sensor address and the sensor type, refer to the below Sensor Tempera- ture Correlation Table.) (4) During group control and simultaneous operation multi control, press the button and change to the unit that you want to monitor. (5) Press the button to return to normal remote controller operation. NOTE The temperature display reads “- - - - ” for units that are not connected. If monitor mode is selected during normal operation, the only parts of the LCD that change are those shown in the figure. All other displays do not change, and remain as they were during normal operation. 4 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
4-14 4. Service procedures Check Pin Short-circuit the cooling check pin (or heating check pin) on the outdoor unit control PCB to perform the control described below. 1. Thermistor checks The checks listed below are performed for 1 second each, in order from the top down. The results are displayed by LED 1 and 2. Discharge temp. (TD) Outdoor air temp. ( TO) Heat exchanger temp. (C1) Heat exchanger temp. (C2) Intake temp. (TS) ThermistorCheck results Normal Abnormal LED 1 and 2 OFF LED 1 lit LED 1 lit LED 1 lit LED 2 lit 2. 4-way valve turns ON for 1 second. 3. Forced cooling (or heating) operation 4-4. Table of Thermistor Characteristics (1) Outdoor Air Temp. (TO), Intake Temp. (TS), Heat Exchanger Temp. (C1) Sensor, Heat Exchanger Temp. (C2) Sensor(2) Discharge Temp. (TD) Sensors Temperature ( F) Resistance (kΩ) Temperature (°F) Resistance (kΩ) 4 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
5-1. Overview......................................................................................................................... 5-2 5-2. Functions ....................................................................................................................... 5-2 5-3. Normal Display Operations and Functions ................................................................. 5-3 5-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures ............................................................................................................. 5-6 5-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History ............................................................................................................. 5-7 5-6. Setting Modes: Setting the Outdoor Unit EEPROM ..................................................... 5-7 5. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL 5-1 5 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
5-2 5. Outdoor unit maintenance remote control 5-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this way, the setting switches that were located on earlier PCBs have been converted to EEPROM data. This remote controller is an outdoor unit maintenance tool that is used to make and change the EEPROM set- tings. This remote controller can be used for checking the outdoor unit EEPROM settings and contents, and also can be used to monitor the outdoor unit alarm history and indoor/outdoor unit temperatures, and to check the status of the indoor unit connec- tions (No. of units, operating status, etc.). Note: Because this tool does not function as a remote controller, it is used only during test runs and servicing. System diagram Outdoor unit maintenance remote controller Remote controller Outdoor unit Outdoor unit control PCB Inter-unit control wiring (main bus) Indoor unitIndoor unit Remote controllerRemote controller Special service checker wiring (Optional, Servicing No:CV6231785082) * The special service checker wiring is required in order to connect the outdoor unit maintenance remote control- ler to the outdoor unit PCB. * Even when the outdoor unit maintenance remote controller is connected, a separate remote controller or other control device must be connected to the indoor unit. 5-2. Functions Normal display functions (1) Functions: Button operations can be used to perform the following functions. Start/stop of all indoor units Switching between cooling and heating Test run of all indoor units High-speed operation of indoor units (Do not use with actual units. This may damage the devices.) (2) Display: The following can be displayed. Alarm details display No. of indoor/outdoor units Unit Nos. of connected indoor/outdoor units Indoor/outdoor unit operating status (blinks when an alarm occurs) Indoor unit thermostat ON Individual display of outdoor unit alarms Outdoor unit compressor total operating time Outdoor unit oil sensor oil level Outdoor unit total power ON time Outdoor unit microcomputer version Other Temperature monitor Displays the indoor/outdoor unit sensor temperatures. Outdoor unit alarm history monitor Displays the outdoor unit alarm history. Setting modes Setting mode 1 and setting mode 2 are used to make the outdoor EEPROM setting.CZ-RTC2 5 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC