Home > Panasonic > Air Conditioner > Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual

Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							4-7
    4. Service procedures
    Judgment condition
    Clear condition
    F31
    L02
    L04
    L07
    L10
    L13
     E07  E06
    E14
    E15
    E16
    E20
    E31
    H01
    Remote
    controller
    alarm displayAlarm
    contentsJudgment and correction
    Automatic recovery EEPROM trouble Reading/writing failure Recovery at power 
    reset1. Check EEPROM (IC007).
    2. Check outdoor unit control 
    PCB.
    Mismatch of indoor 
    and outdoor unit types 
    (Espacio, Multi )Indoor unit judges that type 
    does not match outdoor unit 
    type.Recovery at power 
    reset1. Check indoor unit EEPROM.
    2. Check indoor unit control 
    PCB.
    Settings failure
    Settings failure
    Settings failureDuplicated outdoor unit 
    address (system address)1. Check outdoor unit 
    system address.
    2. Check inter-unit control 
    wiring.
    Group control wiring is 
    connected to an 
    independent-control indoor Recovery at power 
    reset1. Check inter-unit control 
    wiring.
    2. Check indoor unit 
    EEPROM.
    Outdoor unit capacity not set. Recovery at power 
    resetCheck outdoor unit EEPROM.
    Indoor-outdoor unit 
    typesOutdoor unit judges that type 
    does not match indoor unit 
    type.Recovery at power 
    reset1. Check indoor unit 
    EEPROM.
    2. Check outdoor unit control 
    PCB.
    Outdoor unit detected 
    abnormal signal from 
    indoor unit.Serial signal receiving failure 
    (including failure to verify No. 
    of units)
    Automatic
    recovery Automatic
    recovery1. Check inter-unit control 
    wiring.
    2. Check outdoor unit 
    Outdoor unit sending 
    failure to indoor unitl o r t n o c t i n u - r e t n i k c e h C . 1 e r u l i a f g n i d n e s l a n g i s l a i r e S
    wiring.
    2. Check outdoor unit control 
    PCB.
    Settings failure Duplicated master unit in 
    simultaneous-operation multi 
    control
    (Detected by outdoor unit)Recovery at power 
    reset1. Check inter-unit control 
    wiring.
    2. Check indoor unit 
    combination.
    Automatic address 
    setting failure
    Automatic address 
    setting failure
    Automatic address 
    setting failureIndoor unit capacity too low. Recovery at power 
    reset
    Recovery at power 
    reset
    Recovery at power 
    reset1. Check inter-unit control 
    wiring.
    2. Check outdoor unit control 
    PCB.
    l o r t n o c t i n u - r e t n i k c e h C . 1 . h g i h o o t y t i c a p a c t i n u r o o d n I
    wiring.
    2. Check outdoor unit control 
    PCB.
    Outdoor unit cannot receive 
    any serial signals from indoor 
    units.1. Check inter-unit control 
    wiring.
    2. Check outdoor unit control 
    PCB.
    Communications
    trouble within unitNo communication possible 
    with MDC for 3 minutes or 
    longer.Automatic recover y Check outdoor unit control 
    PCB.
    Overcurrent  Inverter stops after alarm is 
    detected.Recovery at restart 1. Refrigerant cycle trouble, 
    overload operation
    2. Loose screws between HIC 
    control PCB and radiating 
    plate
    3. Cooling failure of radiating 
    plate
    4. Check outdoor unit PCB 
    wiring.
    4
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							4-8
    4. Service procedures
    No
    No
    No
    No
    NoNo
    No No
    No
    Ye s Ye s Ye sYe s
    Ye s
    Ye s Ye s Ye s Ye s
    [Alarm “P29”]
    (MDC trouble) (1)
    Input power detection circuit trouble
    Compressor does not run.
    Breakdown
    Motor current detection circuit trouble
    Is power OK? Correct power line.
    Is
    current
    detection
    circuit wiring
    OK?Check and correct 
    wiring.
    Are
    wiring and 
    connector
    connections
    OK?Check and correct
    wiring.
     Is 
    compressor
     OK?
     Ground 
    fault?Replace
    compressor.
     Coil 
    resistor
    short circuit?
    Coil open 
    circuit?
    Is there 
    abnormal refrigerant 
    accumulation?Replace
    compressor.
    Is
    operation of 
    electronic
    control valve 
    OK?
    Replace outdoor 
    unit control PCB. Are 
    C1 and TS 
    sensors
    OK?  Replace C1 and 
    TS sensors.
    Replace electronic 
    control valve.
    Is there overload? Remove 
    the cause.
    4-3. Details of Alarm Messages
    4
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							4-9
    4. Service procedures
    No
    No
    No
    NoNo
    No
    No Ye s
    Ye s
    Ye s
    Ye s
    Ye s
    Ye s
    Ye s
    Replace outdoor unit 
    control PCB.
    (2)  [Alarm “P26”]
       HIC PCB trouble)IGBT short-circuit protection on inverter control (IPDU) PCB 
    Is power OK?
     Correct power line.
    Are
    circuit wiring, 
    connector
    connections, and 
    reactor
    connections
    OK?
    Correct.
    Has filter PCB 
    RY001 or RY002 
    relay activated?
     Has filter PCB 
    AC fuse blown?  Replace filter PCB.
    Disconnect
    U.V.W. output 
    terminal on HIC PCB and 
    start operation. 
    Does alarm 
    “P26”
    occur?
     Replace HIC PCB.
    Is
    compressor OK? 
    (Check for layer 
    short circuit.) Replace compressor.
    Is
    resistance
    between
    each terminal on 
    HIC PCB OK? 
    (See following 
    page.)
     Check HIC PCB.
     Replace if PCB 
    has failed.
    4
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							4-10
    4. Service procedures
    HIC +Between terminals Resistance
    HIC +
    HIC +
    HIC +
    HIC –
    HIC –
    HIC –HIC –
    U
    V
    W
    U
    V
    W
    Resistance
    200 kΩ or more
    300 kΩ or more
    300 kΩ or more
    300 kΩ or more
    200 kΩ or more
    200 kΩ or more
    200 kΩ or more
    No
    Ye s
    Replace outdoor unit 
    control PCB.
    (3) [Alarm “E31”]
     (communications 
      trouble within unit)IGBT short-circuit protection
    Is “E31”
    displayed even after 
    the power voltage 
    is reset?Normal
    HIC-CH4872R
    (42 Type)HIC-CH2672R
    (26, 36 Type)
    4
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							4-11
    4. Service procedures
     
     
     
    No
    No
    No
    No Ye s
    Ye s
    Ye s
    Ye s
    (4) [Alarm P22]Outdoor unit fan motor drive circuit trouble
    Are connectors CN003 and CN004 connected 
    correctly to the outdoor unit control PCB? Correct the connector 
    connections.
    Disconnect connectors CN003 and CN004 
    from outdoor unit control PCB, and rotate 
    fan by hand. Does it rotate easily?
    Outdoor unit fan motor coil resistance is 
    OK if it is as shown below.
    (1) Red – white:  30 – 40 Ω
    (2) White – black: 30 – 40 Ω
    (3) Black – red: 30 – 40 Ω *  Disconnect connector CN004 and 
      measure on the plug side.
    Motor position detection circuit resis-
    tance is OK if it is as shown below.
    *  Disconnect connector CN003 and measure 
      on the plug side.
    (1) Grey – yellow:  100 kΩ or more, or ∞ (open)
    (2)  Grey – blue:   100 kΩ or more, or ∞ (open)
    (3)  Grey – orange: 100 kΩ or more, or ∞ (open)
    Fan motor is OK; outdoor unit 
    control PCB has failed.
    → Replace.Fan motor trouble
    → Replace.
    Note:
    In the case of a GND circuit failure inside the motor, the results 
    of the above check may be OK.
    If operation is not OK after the outdoor unit control PCB has 
    been replaced, then replace the outdoor unit fan motor.
    4
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							4-12
    4. Service procedures
    No
    No Ye s
    Ye s
    Check the outdoor unit 
    control PCB.
    Replace if PCB has failed.
    Sensor trouble
    (5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”]
    Are connectors 
    CN020, 021, 022, 023, 
    and 024 (TD,  TO, C1, C2, and 
    TS sensors) connected 
    correctly to the outdoor unit 
    control PCB? Correct the connector 
    connections.
    Are the TD,  TO, C1, 
    C2, and TS sensor resistance* 
    characteristics OK? Replace the TD,  TO, C1, 
    C2, or TS sensor.
    * Refer to “4-4. Table of Thermistor Characteristics.”
    4
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							4-13
    4. Service procedures
    Sensor installation Sensor 
    Sensor typeSensor
    Sensor type
    s s e r d d a s s e r d d a n o i t a c o l
    00 Room temp.  05 –
    (temp. used for control)*
    01 Remote controller temp. 06 Discharge temp.
    Indoor unit 02 Indoor intake temp. 07 –
    03 Indoor heat exchanger temp. (E1 ) 08 –
    04 Indoor heat exchanger temp. (E2 ) 09 –
    0A Discharge temp. (TD ) 12 –
    – 3 1 – b 0
      t n e r r u C 4 1 – C 0
    (AC current)
    Outdoor unit 0d Intake temp. (TS ) 15 Outdoor electronic control
    valve position
    0E Outdoor heat exchanger temp. (C1 ) 16 –
    0F Outdoor heat exchanger temp. (C2 ) 17 –
    – 8 1 – 0 1
    11 Outdoor air temp. 19 –
    Sensor Temperature Correlation Table
    * Main unit only when group control is enabled
    Figure:  Sample display when discharge 
      temperature at unit No. 1-1 is 185F
    Sensor Temperature Display Function (Displayed both when operating and stopped)
    The below check procedure can be used to display
    all remote controller, indoor unit, and outdoor unit
    sensor temperatures.
     
    (1) Press and hold the button and button simultaneously
    for 4 seconds or longer.
    (2) Unit No. X-X (main unit No.), item code XX (sensor
    address), and service monitor 00XX (sensor tem-
    perature) appear on the remote controller LCD. (See
    figure.)
    (3) Press the temperature setting and buttons and
    change the item code to the sensor address of the
    sensor that you want to monitor.
    (For the relationship between the sensor address and
    the sensor type, refer to the below Sensor Tempera-
    ture Correlation Table.)
    (4) During group control and simultaneous operation
    multi control, press the button and change to the unit
    that you want to monitor.
    (5) Press the button to return to normal remote controller
    operation.
    NOTE
    The temperature display reads “- - - - ” for units that are
    not connected.
    If monitor mode is selected during normal operation,
    the only parts of the LCD that change are those
    shown in the figure.
    All other displays do not change, and remain as they
    were during normal operation.
    4
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							4-14
    4. Service procedures
    Check Pin
    Short-circuit the cooling check pin (or heating check pin) on the outdoor unit control PCB to perform the control
    described below.
    1. Thermistor checks
    The checks listed below are performed for 1 second each, in order from the top down. The results are displayed
    by LED 1 and 2.
    Discharge temp. (TD)     
    Outdoor air temp. ( TO)    
    Heat exchanger temp. (C1)     
    Heat exchanger temp. (C2)     
    Intake temp. (TS)    ThermistorCheck results
    Normal  Abnormal
    LED 1 and 2 OFF LED 1 lit
    LED 1 lit
    LED 1 lit LED 2 lit
    2. 4-way valve turns ON for 1 second.
    3. Forced cooling (or heating) operation
    4-4. Table of Thermistor Characteristics
    (1) Outdoor Air Temp. (TO), Intake Temp. (TS), Heat
    Exchanger Temp. (C1) Sensor, Heat Exchanger
    Temp. (C2) Sensor(2) Discharge Temp. (TD) Sensors
    Temperature ( F)
    Resistance (kΩ)
    Temperature (°F)
    Resistance (kΩ)
    4
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							5-1. Overview......................................................................................................................... 5-2
    5-2. Functions ....................................................................................................................... 5-2
    5-3. Normal Display Operations and Functions ................................................................. 5-3
    5-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor
    Temperatures ............................................................................................................. 5-6
    5-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit
    Alarm History ............................................................................................................. 5-7
    5-6. Setting Modes: Setting the Outdoor Unit EEPROM ..................................................... 5-7
    5. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL
    5-1
    5
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							5-2
    5. Outdoor unit maintenance remote control
    5-1. Overview
    What is the outdoor unit maintenance remote controller?
    Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is
    used in the outdoor unit PCB. In this way, the setting switches that were located on
    earlier PCBs have been converted to EEPROM data. This remote controller is an
    outdoor unit maintenance tool that is used to make and change the EEPROM set-
    tings.
    This remote controller can be used for checking the outdoor unit EEPROM settings
    and contents, and also can be used to monitor the outdoor unit alarm history and
    indoor/outdoor unit temperatures, and to check the status of the indoor unit connec-
    tions (No. of units, operating status, etc.).
    Note: Because this tool does not function as a remote controller, it is used only
    during test runs and servicing.
    System diagram
    Outdoor unit maintenance 
    remote controller
    Remote controller 
    Outdoor unit
    Outdoor unit 
    control PCB
    Inter-unit control wiring (main bus)
    Indoor
    unitIndoor
    unit
    Remote
    controllerRemote
    controller
    Special service checker wiring 
    (Optional, Servicing No:CV6231785082) 
    * The special service checker wiring is required in order to connect the outdoor unit maintenance remote control-
    ler to the outdoor unit PCB.
    * Even when the outdoor unit maintenance remote controller is connected, a separate remote controller or other
    control device must be connected to the indoor unit.
    5-2. Functions
    Normal display functions
    (1) Functions: Button operations can be used to perform the following functions.
     Start/stop of all indoor units
     Switching between cooling and heating
     Test run of all indoor units
     High-speed operation of indoor units (Do not use with actual units. This may damage the devices.)
    (2) Display: The following can be displayed.
     Alarm details display
     No. of indoor/outdoor units
     Unit Nos. of connected indoor/outdoor units
     Indoor/outdoor unit operating status (blinks when an alarm occurs)
     Indoor unit thermostat ON
     Individual display of outdoor unit alarms
     Outdoor unit compressor total operating time
     Outdoor unit oil sensor oil level
     Outdoor unit total power ON time
     Outdoor unit microcomputer version
     Other
    Temperature monitor
     Displays the indoor/outdoor unit sensor temperatures.
    Outdoor unit alarm history monitor
     Displays the outdoor unit alarm history.
    Setting modes
     Setting mode 1 and setting mode 2 are used to make the outdoor EEPROM setting.CZ-RTC2
    5
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual