Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
1-35 1. Specifications 1-3 Other Component Specifications Outdoor Unit U-26PE1U6, U-26PS1U6 . o N L E D O M Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ14°F:23.7 , 50 °F : 9.7 23°F:18.8 , 68 °F : 6.5 32°F:15.0 , 86 °F : 4.4 41°F : 12.1 , 104 °F : 3.1 113°F : 2.6 Thermistor (Comp. discharge gas sensor) : TH6 Coil resistance kΩ140°F : 13.8 , 194 °F : 5.1 158°F : 9.7 , 212 °F : 3.8 167°F : 8.2 , 230 °F : 2.8 176°F : 7.0 , 248 °F : 2.2 185°F : 5.9 , 266 °F: 1.7 Solenoid coil or 4 way valve STF-02U2G e v l a v y a w 4 ) y l n o l e d o m p m u p t a e H ( 1 A U 3 0 5 Q A 1 0 - F T S l i o c d i o n e l o S DATA SUBJECT TO CHANGE WITHOUT NOTICE Electric expansion valve (MOV) ValveUKV - 18D13 CoilUKV - U013E1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-36 1. Specifications 1-3 Other Component Specifications Outdoor Unit U-36PE1U6, U-36PS1U6 . o N L E D O M Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ14°F:23.7 , 50 °F: 9.7 23°F:18.8 , 68 °F: 6.5 32°F:15.0 , 86 °F: 4.4 41°F : 12.1 , 104 °F: 3.1 113°F: 2.6 Thermistor (Comp. discharge gas sensor) : TH6 Coil resistance kΩ140°F : 13.8 , 194 °F: 5.1 158°F : 9.7 , 212 °F: 3.8 167°F : 8.2 , 230 °F: 2.8 176°F : 7.0 , 248 °F : 2.2 185°F : 5.9 , 266 °F: 1.7 Solenoid coil or 4 way valve G 2 U 2 0 - F T S e v l a v y a w 4 ) y l n o s l e d o m p m u p t a e H ( 1 A U 3 0 5 Q A 1 0 - F T S l i o c d i o n e l o S DATA SUBJECT TO CHANGE WITHOUT NOTICE Electric expansion valve (MOV) ValveUKV - 18D13 CoilUKV - U013E1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-37 1. Specifications U-42PE1U6, U-42PS1U6 . o N L E D O M Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ14°F:23.7 , 50 °F: 9.7 23°F : 18.8 , 68 °F : 6.5 32°F : 15.0 , 86 °F: 4.4 41°F : 12.1 , 104 °F : 3.1 113°F: 2.6 Thermistor (Comp. discharge gas sensor) : TH6 Coil resistance kΩ140°F : 13.8 , 194 °F : 5.1 158°F : 9.7 , 212 °F: 3.8 167°F : 8.2 , 230 °F : 2.8 176°F : 7.0 , 248 °F : 2.2 185°F : 5.9 , 266 °F : 1.7 Solenoid coil or 4 way valve G 1 U 4 0 - F T S e v l a v y a w 4 ) y l n o l e d o m p m u p t a e H ( 1 A U 3 0 5 Q A 1 0 - F T S l i o c d i o n e l o S DATA SUBJECT TO CHANGE WITHOUT NOTICE Electric expansion valve (MOV) ValveUKV - 25D CoilUKV - U013E 1-3 Other Component Specifications Outdoor Unit 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-38 1. Specifications 1-4 Dimensional data Indoor unit : 4-Way Cassette Type 26 Type 33-27/323-15/16 30-9/16 19-11/16 19-11/16 12-1/8 1-3/16 4-7/8 15/32 15/32 1-7/833-27/32 32-9/32 (Ceiling opening) Grille center 29-13/16 (Suspention bolt pitch) 14-1/2 1 Air intake grille Air outlet Refrigerant liquid line (3/8) Flare connection Refrigerant gas line (5/8) Flare connection Drain connection Power supply entry (conduit size : 1/2) For discharge duct Suspention bolt mounting For fresh air intake X-view X 1917_X_S 14-27/32 22-9/32 (Suspention bolt pitch) 32-9/32 (Ceiling opening) 9-1/8 11-1/2 13-11/32 6-3/16 2-5/167-5/32 Dimension : inch 4-7/8 8-11/16 8-27/32 30-9/16 15/32 15/32 Detail of ø5-29/32ø6-3/8 4-ø1/8 hole 2-5/322-3/8 3-15/16 10-9/32 8-11/16 4-7/8 4-7/8 Min. 2-15/32 Min. 19/32 3 9 9ø4-13/324-ø1/8 hole Detail of 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-39 1. Specifications 1-4 Dimensional data Indoor unit : 4-Way Cassette Type 36, 42Type 45-9/32 41-31/32 31-3/32 19-11/1613-5/16 1-3/16 4-7/8 15/32 15/32 1-7/833-27/32 32-9/32 (Ceiling opening) Grille center 29-13/16 (Suspention bolt pitch) 20-3/16 1 Air intake grille Air outlet Refrigerant liquid line (3/8 ) Flare connectionRefrigerant gas line (5/8) Flare connectionDrain connection Power supply entry (conduit size : 1/2) For discharge duct Suspention bolt mounting For fresh air intake X-view X 1918_X_S 20-9/16 33-11/16 (Suspention bolt pitch) 43-11/16 (Ceiling opening) 9-1/8 11-1/2 13-11/32 7-3/32 6-3/16 2-5/167-5/32 Dimension : inch 4-7/8 9-19/32 9-13/16 30-9/16 15/32 15/32 Detail of ø5-29/32ø6-3/ 8 4-ø1/8 hole 2-5/322-3/8 3-15/16 11-15/32 9-19/32 4-7/8 4-7/8 Min. 2-15/32 Min. 19/32 3 9 9ø4-13/324-ø1/8 hole Detail of 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-40 1. Specifications 1-4 Dimensional data Dimension : inchRefrigerant liquid line (3/8) Flare connection Refrigerant gas line (5/8) Flare connection Drain hose OD 45/64 Drain and wiring port (3-5/32) Indoor unit : Wall Mounted Type 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-41 1. Specifications 1-4 Dimensional data Indoor unit : Ceiling Type 26 Type Drain connection Drain connection for left side Refrigerant liquid line (3/8) Flare connection Refrigerant gas line (5/8) Flare connection Hole for rear side refrigerant tubing Hole for through-the-wall refrigerant tubing (ø3-15/16 hole) Hole for fresh air intake (Knockout hole) Hole for right side refrigerant tubing (Knockout hole) Hole for left side drain connection (Knockout hole) Hole for power supply (Conduit size 1/2) Infrared rays receiver for wireless remote controller Cutting position for fresh air intake 1919_THS_I Dimension : inch Air intakeAir outlet 2 ft. or more Hole for wall-through piping (View from front) 9-7/8 7-15/32 8-7/1651-3/16 26-3/8 11-1/32 12-7/32 50-13/32 5-25/32 12-19/326-5/16 3-3/32 3-3/45-25/32 4-23/32 2-17/325-9/325-25/32 1-3/32 6-5/16 3-9/32 4-9/165-3/4 7-7/32 4-1/16 9-7/8 5-9/16 1-3/848-7/16 (Suspension bolt hole pitch) 3-1/2 5-25/32 2-25/32 5-3/16 11-1/323-15/16 1-3/8 3-3/8 6-3/32 3-15/16 Front (Service space) (Service space)Holes in the rear side (View from front) (Suspension bolt hole pitch) 10 or more10 or more 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-42 1. Specifications 1-4 Dimensional data Indoor unit : Ceiling Type 36, 42 Type Drain connection Drain connection for left side Refrigerant liquid line (3/8) Flare connection Refrigerant gas line (5/8) Flare connection Hole for rear side refrigerant tubing Hole for through-the-wall refrigerant tubing ( ø3-15/16 hole) Hole for fresh air intake (Knockout hole) Hole for right side refrigerant tubing (Knockout hole) Hole for left side drain connection (Knockout hole) Hole for power supply (Conduit size 1/2) Infrared rays receiver for wireless remote controller Cutting position for fresh air intake 1920_TS_I Dimension : inch Air intakeAir outlet 2 ft. or more Hole for wall-through piping (View from front) 9-7/8 9-7/16 8-7/1662 26-3/8 11-1/32 12-7/32 61-7/32 7-3/4 12-19/326-5/16 5-15/16 5-1/27-3/4 6-11/16 4-1/27-1/47-3/4 1-3/32 6-5/16 3-5/32 4-3/4 5-3/4 7-7/32 4-1/16 9-7/8 5-9/16 1-3/859-1/4 (Suspension bolt hole pitch) 3-1/2 5-25/32 2-25/32 5-3/16 11-1/323-15/16 1-31/32 3-3/8 6-3/32 7-31/32 Front (Service space) (Service space)Holes in the rear side (View from front) (Suspension bolt hole pitch) 10 or more10 or more 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-43 1. Specifications 1-4 Dimensional data Indoor unit : Low Silhouette Duct Type 26 Type Refrigerant liquid line (3/8) Flare connectionRefrigerant gas line (5/8) Flare connectionUpper drain port (O.D. 1-1/4) Bottom drain port (O.D. 1-1/32) Suspension lug Power supply inlet (conduit size 1/2) Fresh air intake port ( ø5-29/32) Flange for the flexible air outlet duct (ø7-7/8) Tube cover Electrical component box Flange for the air intake duct (option or field supply)91011 1914_U_I (Suspension bolt pitch) 16- ø1/8 (Hole) 37-7/8 (Air outlet duct flange) 35-7/16 39-3/8 42-17/32 (Suspension bolt pitch)(5-29/32)1-9/16 11-13/32 11-12/32 10-23/32 2-15/16 2-9/16 7-3/321-7/32 1-7/32 22-27/32 31/324-17/32 3/4 1115/16 10-1/4(Air outlet duct flange) Dimension : inch 3-17/327-9/32 10 11-7/32 2-3/4 5-1/8 31/32 8-9/3212-7/32 31/32 6-7/8 1-3/8 7-15/32 3-11/32 31/32 2-3/4 1-3/166-5/16 24-13/16 31/32 13/32 Inspection access (17-23/32× 17-23/32) (Field supply) 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-44 1. Specifications 1-4 Dimensional data Indoor unit : Low Silhouette Duct Type 36 Type Refrigerant liquid line (3/8) Flare connection Refrigerant gas line (5/8) Flare connection Upper drain port (O.D. 1-1/4) Bottom drain port (O.D. 1-1/32) Suspension lug Power supply inlet (conduit size 1/2) Fresh air intake port ( ø5-29/32) Flange for the flexible air outlet duct (ø7-7/8) Tube cover Electrical component box Flange for the air intake duct (option or field supply)91011 1915_U_I (Suspension bolt pitch) 18-ø1/8 (Hole) 56-25/32 (Air outlet duct flange) 9-1/16 P × 6 = 54-11/32 58-9/32 61-13/32 (Suspension bolt pitch)(5-29/32)1-9/16 13-3/16 13-3/16 13-3/16 12-7/32 2-15/16 2-9/16 9-1/161-7/32 1-7/32 22-27/32 31/324-17/32 3/4 1115/16 10-1/4(Air outlet duct flange) 10 11-7/32 2-3/4 5-1/8 31/32 8-9/3212-7/32 31/32 6-7/8 1-3/8 7-15/32 3-11/32 31/32 2-3/4 1-3/166-5/16 24-13/16 31/32 13/32 Inspection access (17-23/32× 17-23/32) (Field supply) 3-17/327-9/32 Dimension : inch 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC