Home
>
Panasonic
>
Air Conditioner
>
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
1-55 1. Specifications 1-8 Noise Criterion Curves Outdoor Units REMARKS:1. Value obtained in the actual place where the unit is installed may be slightly higher than the values shown in this graph because of the conditions of operation, the structure of the building, the background noise and other factors. 2. The test results were obtained from an nechoic room. NOTE To evaluate “Noise level” the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used. Read the number on each BAND CENTER FREQUENCIES (horizontal axis) ranging from 63 Hz to 8000 Hz and select the maximum value (vertical axis) among them. U-26PE1U6, U-26PS1U6 U-42PE1U6, U-42PS1U6 U-36PE1U6, U-36PS1U6 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-56 1. Specifications 1-9 Increasing the Fan Speed Jumper cable Jumper cable Electrical component box (At shipment) (Jumper cable installed) 2159_M_I Fan motor socket Fan motor 900 Air Flow (CFM) External Static Pressure 0 50 0 0.1 0.2 0.3 0.4 0.5 150 700 500 300 Limit line L 100 1982_U_I HHH (Pa) (inAq) Limit lineHT Air Flow (CFM) External Static Pressure 0 50 0 0.1 0.2 0.3 0.4 0.5 0.6 0.8 150 200 500 1000 Limit line LHHHHT 100 1983_U_I (inAq)(Pa) Limit line NOTE HT : Using the booster cable H : At shipment How to read the diagram The vertical axis is the external static pressure (Pa) while the horizontal axis represents the AIR FLOW (CFM). The characteristic curves for “HT”, “H”, “M” and “L” fan speed control are shown. The nameplate values are shown based on the “H” air flow. For the 26 type, the air flow is 636 CFM, while the external static pressure is 49 Pa at “H” position. If external static pressure is too great (due to long extension of duct, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed as explained above. If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure: (1) Remove 4 screws on the electrical component box and remove the cover plate. (2) Disconnect the fan motor sockets in the box. (3) Take out the jumper cable (sockets at both ends) clamped in the box. (4) Securely connect the jumper cable sockets between the disconnected fan motor sockets in step 2. (5) Place the cable neatly in the box and reinstall the cover plate. Indoor Fan Performance e p y T 6 3 e p y T 6 2 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-57 1. Specifications 1-10 Air throw distance chart 4-Way Cassette Type 03 7 10131720 0 3 7 10 13HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) AXIS AIR VELOCITY 2111_X_I Model: 26 Type Model: 36, 42 Type : LOUVER ANGLE 20 in Cooling mode : LOUVER ANGLE 60 in Heating mode Condition Fan Speed : Hi Room air temp. : 80F DB in cooling mode 68F DB in heating mode 03 7 10131720 0 3 7 10 13HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) AXIS AIR VELOCITY 2112_X_I 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-58 1. Specifications 1-10 Air throw distance chart Wall Mounted Type COOLING - - - - - HEATING FAN SPEED HIGH HIGH ROOM AIR TEMP. 80°F70°F FLAP ANGLE 0°, 22.5°, 45°45°, 67.5° Axis air velocity (ft./sec.) Vertical distance (ft.) Horizontal distance (ft.) 10 135 0 Model: 26 Type 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-59 1. Specifications 1-10 Air throw distance chart Ceiling Type Model: 26 Type 0371013172023262933 0 3 7 10 13 17HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.)2115_T_I AXIS AIR VELOCITY Model: 36 Type 2116_T_I AXIS AIR VELOCITY 0371013172023262933 0 3 7 10 13 17HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) Model: 42 Type 2117_T_I AXIS AIR VELOCITY FAN SPEEDHEATING COOLING ROOM AIR TEMP. LOUVER ANGLEHIGH HIGH 68 ° F 80°F 54 °– 7° : COOLING : HEATING 0 3 7 1013 172023262933 0 3 7 10 13 17HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-60 1. Specifications 1-11. ELECTRICAL WIRING General Precautions on Wiring (1) as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2)Before wiring, confirm the rated voltage of the unit Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line. (3) unit must be grounded. (4) with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged. (5) compressor, or any moving parts of the fan. (6)To prevent possible hazards from insulation failure, the Each wiring connection must be done in accordance Do not allow wiring to touch the refrigerant tubing, Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes. (7) locality. For field wiring rules, must follow your LOCAL ELECTRICAL CODES before beginning. You must ensure that installation complies with all relevant rules and regulations. (8)Regulations on wire diameters differ from locality to To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows: The remote control wiring and the inter-unit control wiring should be wired apart from the inter- unit power wiring. Use shielded wires for inter-unit control wiring between units and ground the shield on one side only. (9) it must be replaced by a repair shop appointed by the manufacturer, because special-purpose tools are required. (10)If the power supply cord of this appliance is damaged, All wiring used must be Class 1. Recommended Wire Length and Wire Diameter for Power Supply System You must follow LOCAL ELECTRICAL CODES for wiring. Outdoor Unit TypeTime delay fuse or circuit capacity U-26PE1U6 30 A U-36PE1U6 35 A U-42PE1U6 40 ATypeTime delay fuse or circuit capacity U-26PS1U6 25 A U-36PS1U6 30 A U-42PS1U6 35 A Indoor Unit TypeTime delay fuse or circuit capacity U1, K1, T1, F1 15 A Control Wiring (A) Inter-Unit Control Wiring (B) Remote Control Wiring (C) Control Wiring For Group Control AWG #18 Use high voltage wire (300 V) *1AWG #18*2 (0.75 mm2) AWG #18*2 - (0.75 mm2) Max. 650 - ft. (Total) Max. 1,650 ft. Max. 3,300 ft. AWG=American Wire Gauge *1 With ring-type wire terminal *2 Wire joint connection 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-61 1. Specifications Inter-unit power wiringPower wiring Inter-unit control wiring 8P terminal board Outdoor Unit Indoor Unit U1 U2 1 2 G L1 L2 Wiring System Diagrams Basic wiring diagram for standard control NOTE Disconnect switch may be needed by the National/Local code. ALWAYS COMPLY WITH NATIONAL AND LOCAL CODE REQUIREMENTS. NOTE (1) (2) (B), (C) have no polarity. But for other wiring, respect polarity. Be sure to connect as shown in the Wiring System Diagram. (3)Refer to Recommended Wire Length and Wire Diameter for Power Supply System for the explanation of “A”, “B” and “C” in the above diagrams. Inter-Unit Control Wiring (A) and remote control wiring In case of separate supply connection to indoor unit, over current protection must be provided between power source and indoor unit. MAXIMUM OVER CURRENT PROTECTION 15 A (FUSE OR HACR TYPE CIRCUIT BREAKER) U2 L2 U1L1L1 L2 U1U2 L2L1 21WHT Remote ControllerB C Indoor unitL1 L2 Grounding line BLK21 Inter-unit power line 208 / 230 V, 60 Hz, 1-PHPower supply 208 / 230 V, 60Hz, 1-PH Grounding line A Outdoor unit INV unit 12 G * U2 U1L1 L2 U1U2 Indoor unitL1 L2 Grounding line Inter-unit power line 208 / 230 V, 60 Hz, 1-PHPower supply 208 / 230 V, 60Hz, 1-PH Grounding line A Outdoor unit INV unit 12 G ** Disconnect switch Field supply Wire joint connection Wire joint connection Unit control Line Power supplyRemote control Line 5P terminal board L1 L2 U1 U2 K1 Type L1 L2 Unit control Line U1 Power supply U2 5P terminal board U1, T1, F1 Types Remote control Line 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-62 1. Specifications WARNINGLoose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected. How to Connect Wiring to the Terminal For stranded wiring (1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to expose the stranded wiring about 3/8 in. (Fig. 1-1) (2) Using a Phillips head screwdriver, remove the terminal screw(s) on the terminal plate. (3) Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring pressure terminal. (Fig. 1-1) (4) Place the ring pressure terminal, and replace and tighten the removed terminal screw using a screwdriver. (Fig. 1-2) When connecting each power wire to the corresponding terminal, follow the instructions on “How to connect wiring to the terminal” and fasten the wire securely with the fixing screw of the terminal plate. Fig. 1-2 Fig. 1-1 Stranded wire Ring pressure terminal Strip 3/8 in. Screw and Special washer Ring pressure terminal Wire Terminal plateRing pressure terminalScrew Special washer Wire 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-63 1. Specifications 1-12. Installation Instructions 1. Tubing SizeOutdoor Unit Single type Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible. Refer to Table 1-2. Table 1-1 Indoor unit type 26, 36 types 42 type 165 ft. 165 ft. Maximum length Charge-less tubing length (actual length) 10 – 100 ft. 15 – 100 ft. 0.43 oz. Additional charge per 1 ft. Maximum indoor-outdoor height differenceIf outdoor unit is higher H1 H1 100 If outdoor unit is lower 50 Single Main tubing L H1 Table 1-2 Tubing Data for Models U-26PE1U6 U-26PS1U6U-36PE1U6 U-36PS1U6U-42PE1U6 U-42PS1U6 Tubing size outer diameterLiquid tube in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) Gas tube in. (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 165 165 165 (ft.) (ft.) (ft.) (ft.) Limit of tubing length Limit of elevation difference between the 2 unitsOutdoor unit is placed 100 100 100 higher. Outdoor unit is placed 50 50 50 lower. Max. allowable tubing length at shipment 10 – 100 10 – 100 10 – 100 Required additional refrigerant * 1(oz./ft.) a) 0.43 b) 0.43 b) 0.43 Refrigerant charged at shipment (lbs.) 4.2 6.2 7.9 No additional charge of compressor oil is necessary. *1 If total tubing length becomes 100 to 165 ft., charge additional refrigerant by 0.43 oz./ft. Table 1-3 List of Connection Tube Sizes Main tubing (L) Type capacity of indoor units 26 – 42 Gas tube ø5/8 Liquid tube ø3/8 Amount of additional charge per 1 ft.0.43 oz. Tubing DataModels 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-64 1. Specifications CAUTION 1. This unit requires no additional refrigerant charge up to 100 ft. tubing length. In case of more than 100 ft., additional refrigerant charge is required. Refer to Table 1-3. 2. In case of multi type installation, indoor units should be installed within the same room. If multi type indoor units are installed in different rooms, temperature control may develop problems because thermostat operation must follow the thermostat condition of 1 indoor unit only (the main unit). WARNINGAlways check the gas density for the room in which the unit is installed. 2. Check of density limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit. The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent. With the recent increase in the number of high density buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). ASHRAE and the International Mechanical Code of the ICC as well as CSA provide guidance and define safeguards related to the use of refrigerants, all of which define a Refrigerant Concentration Level (RCL) of 25 pounds per 1,000 cubic feet for R410A refrigerant. For additional guidance and precautions related to refrigerant safety, please refer to the following documents: International Mechanical Code 2009 (IMC-2009) (or more recently revised) ASHRAE 15 ASHRAE 34 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC