Home > Panasonic > Air Conditioner > Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual

Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							1-105
    1. Specifications
    7-11. Misoperation Alarm Indicators
    Alarm indicator lamps on the indoor unit indicate the error 
    cause if the air conditioner fails to operate upon being 
    switched on. The possible alarm indications are given in 
    Table 1-9. Fig. 1-95 shows the location of the alarm lamps 
    on the indoor unit.
    (See Table 1-9 and Fig. 1-95.)
    Table 1-9
    Alarm
    (OPERATION(TIMER(STANDBYCause of Trouble
    lamp) lamp) lamp)
    S.C. errors* between the indoor unit’s controller (PCB) and the remote
    controller.
    Compressor protector is working.
    S.C. errors between indoor and outdoor units.
    Indoor or outdoor thermistor is malfunctioning.
    Outdoor unit protector is working.
    Indoor unit protector is working.
    TEST RUN switch on the operation controller is in ON state.
    * S.C.: Serial communications
    OPERATION
    lampTIMER
    lampSTANDBY
    lampRemote control
    receiver
    Fig. 1-95
    NOTE
    Stick the alarm message label accompanying the
    wireless remote controller on the electrical component
    box to indicate the cause of trouble for future reference.
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-106
    1. Specifications
    
    CAUTION If the signal receiving unit is installed near a rapid-start or inverter type fluorescent 
    lamp (neither one uses glow lamps), it may be impossible to receive signals from the 
    wireless remote controller. To avoid signal interference from fluorescent lamps, install 
    the receiving unit at least 6.6 ft. away from the lamps and install at a location where 
    wireless remote controller signals can be received when the fluorescent lamps are on.
    7-12. Separate Type Signal Receiving Unit Installation
    CAUTION Do not twist the operating
    controller wires together
    with the power supply
    wires. Doing so can result
    in malfunction.
     If electrical noise is induced
    in the unit power supply,
    take appropriate measures,
    for example installing a
    noise  lter.
      If local electrical codes allow, this signal receving
    unit can be mounted using a conventional wall box
    for  ush mounting.
    (1) If Wall mounted Fixed Position
    Install the remote controller at a convenient
    location on a nearby wall. However, before
    attaching the remote controller mounting cradle,
    check that the remote controller can operate from
    the desired wall position. (Fig. 1-97)
    How to Install Batteries
    See Fig. 1-98.
    (1) Press and slide the lid on the back of the remote
    controller in the direction of the arrow.
    (2) Install two AAA alkaline batteries. Make sure the
    batteries point in the direction marked in the
    battery compartment.
    (3) Press the reset hole, then replace the lid. If you
    press it, the current time, ON time, and OFF time
    are all reset to 0:00.
    Fig. 1-97
    12
    Fasten the remote control 
    mount with screws.Fitting the remote 
    control in the mount.
    Remote control mount
    Press
    Put in
    Fig. 1-98
    Reset hole
    Cover
    Fig. 1-96
    Cover plate Notch
    Spacer
    Switch box (no cover) Signal receiving unit
    M4× L1
    Screws (2)
    123
    4R D
    A6 5
    
    L
    L
    AB
    U S :
    U C R
    N I
    A
    M :
    U C
    R
    L A
    M R O
    N. K
    H C
    B C PN
    U
    R T S E T
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-107
    1. Specifications
    When using the signal receiving unit on a wall with
    the front exposed, choose a wall surface that the
    signal receiving unit can be mounted on.
    (1) Insert a  athead screwdriver into the slot on the lower 
    side of the signal receiving unit and pry off the back 
    case.
    (2) The wire routing at the signal receiving unit comes out 
    of the upper case (thin portion at upper center) so use 
    nippers or a similar tool to cut out a notch beforehand 
    large enough for the remote control cable (option) to 
    pass through as shown in Fig. 1-99.
    (3) Remove the wire, which is connected prior to shipping,
    from the connector.
    (4) Connect the remote control cable (option) to the signal 
    receiving unit connector as shown in Fig. 1-100 after the 
    clamp (supplied) with the unit is installed.
    (5) After arranging the wiring on the printed circuit board 
    as shown in Fig. 1-101 so that it is contained within the 
    signal receiving unit, attach the back case. At this time, 
    arrange so that the head of the clamp faces the side.
    (6) Remove the cover plate and install the signal receiving 
    unit using the 2 wood screws.
    (7) Fasten to the wall using the cord clip (supplied).
    (8) Reinstall the cover plate.
      To use the signal receiving unit while mounted on the 
    ceiling, install by using the carrier for ceiling installation 
    supplied with the unit.
    (1) Remove the cover plate by inserting a  athead 
    screwdriver into the notch in the lower section and 
    prying it off.
    (2) Cut out a section (3-3/4×2-1/32) on the ceiling using 
    the paper pattern (supplied) as a guide.
    (3) Run the wire through the mounting carrier and insert 
    into the installation hole as shown in Fig. 1-103.
    (4) Fit securely into the ceiling material at sections (A) 
    and (B) as shown in Fig. 1-104.
    (5) Connect the wire (2-wire core) from the signal 
    receiving unit with the wire from the indoor unit. (See 
    section on how to wire the receiving unit.) as shown in 
    Fig. 1-104.
    (6) Use the supplied spacers to adjust for a thickness 
    several inches more than the ceiling material and 
    lightly fasten the receiving unit in place with the small 
    screws (M4×1-9/16, 2 pcs.) supplied with the unit.
    (7) Tighten the machine screws after  tting sections (A) 
    and (B) into the openings, in the gap between the 
    signal receiving unit and ceiling surface as in Fig. 1-105. 
    Do not apply strong force when tightening the screws. 
    Excessive force might warp or damage the cover. 
    When  nished, the signal receiving unit should still be 
    able to move slightly when pressed as shown in Fig. 
    1-105.
    (8) Reinstall the cover plate.
    Run the remote con
    cable through a notch
    in the upper case.Clamp (Supplied)
    About 3/32-1/8
    ConnectorRemote control cord 
    (Option)
    Remote control cord (Option)
    ClampSignal receiving unit
    Wood screws (2)
    123
    4R
    D A6 5
     L L
    AB U
    S :
    U C
    R
    N
    I A M
    :
    U C R
    L
    A M
    R O N. K H
    C B
    C PN U R
    T S
    E T
    B A
    Fig. 1-99
    Fig. 1-100
    Fig. 1-101
    Fig. 1-102
    Fig. 1-103
    Fig. 1-104
    Fig. 1-105
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-108
    1. Specifications
    7-13. Electrical Wiring
    CAUTIONBe sure to do the wiring
    correctly (incorrect
    wiring will damage the
    equipment).
      Recommended wire diameter and allowable length
    for signal receiving unit wiring and its branch wiring:
    AWG #18, MAX 1,300 ft.
    7-14. Test  Run  Switch
    (1) Remove the cover plate of the signal receiving unit.
    Set the “TEST RUN” switch of the dip switches to
    the ON position.
    (2) Press the ON/OFF operation button on the
    wireless remote controller.
    Wire joint (2 pcs.
    white, supplied)
    1 WHT
    BLK
    21
    2Terminal board 
    for indoor unit
    remote control
    wiring
    Signal receiving unit wiring (field supply)ConnectionWire from signal receiving unitSignal receiving
    unit
    Wire joint CE-1 
    (supplied)
    Signal receiving
    unit wiring Signal receiving
    unit wiring
    CAUTIONTo avoid placing an
    excessive load on the
    equipment, use this
    function only when
    conducting the test run.
    (3) Make a test run using the air conditioner in
    COOL or HEAT mode.
    (4) During the test run, the “OPER.,” “TIMER,”
    and “STDBY” LED all blink.
      To protect the air conditioner from overloading, the outdoor unit will not start running for approximately 3 minutes
    after power is applied or the air conditioner is turned off and then back on.
      When the DIP switch is set to “TEST – ON,” temperature control from the wireless remote controller is disabled.
    Do not use this setting at any time other than for the test run. Doing so will place an excessive load on the system.
    (5) After the test run, press the ON/OFF operation button on the wireless remote controller. Then, set the
    TEST RUN switch back to the OFF position to cancel the test run mode.
    (This receiver includes a 60-minute automatic OFF timer function in order to prevent continuous test run.)Fig. 1-106
    123
    4ADR56
    ALLRCU : SUB
    RCU : MAIN
    NORMALPCB CHK.TEST RUN
    ALL
    RCU : SUB
    PCB CHK.
    TEST RUN
    (1) Strip the insulation to approximately 9/16 from the ends
          of the wires that will be connected.
    (2) Twist together the 2 wires and create a crimp connection
          at the wire joint.
    (3) If a special crimping tool is not used, or if the connection
          is soldered, insulate the wires using insulation tape.
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-109
    1. Specifications
    7-15. Misoperation Alarm Indicators
    A blinking lamp for other than the signal receiving unit
     lter shows that a problem has occurred in the unit, so
    make an inspection. (Refer to servicing information in
    the service manual, etc.) Also, if wired remote controller
    and dedicated service check lines (CV6380230938: 
    service use) are available, then detailed error
    information can be obtained by connecting to the
    service connector as shown in the drawing. For
    information on how to connect to the signal receiving
    unit, refer to the instruction manual that came with the
    dedicated service check lines.
    Table 1-10
    Fig. 1-107
    Fig. 1-108
    Lamp
    OPERATIONTIMER STANDBYu g i r BaC tel b u o r T   f o   e s h
    lamp lamp lamp
    No power supply or mis-wiring of signal receiving unit.
    S.C.* errors between the indoor unit’s controller (PCB) and
    signal receiving unit.
    S.C. errors between indoor and outdoor units.
    Alternately Indoor unit protector is activated.
    Alternately Outdoor unit protector is activated.
    Compressor protector is activated.
    Concurrent Mis-setting of indoor unit.
    Concurrent Mis-setting of outdoor unit.
    * S.C.: Serial communications
    ALLRCU : SUB
    RCU : MAIN
    NORMALPCB CHK.TEST RUN
    Service
    connector
    1. Operation Display
    2. Start/Stop button
    3. Fan speed button
    4. Swing/Wind Direction button
    5. Timer setting button
    6. Reset button
    7. Cover8. Transmitter
    9. Remote control sensor
    10. Temperature setting buttons
    12. Mode Select button 11. Filter button
    13. Ventilation button
    14. Address button
    15. Sensor button
    16. Clock button
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-110
    1. Specifications
    7-16. Basic Wiring Diagram
    CAUTIONBe sure to do the wiring
    correctly (incorrect wiring
    will damage the equipment).
     Wiring procedure
    Carry out the wiring according to the above wiring
    diagram.
      Address setting is automatically executed
    after turning on the system.
    An indoor unit address is assigned to each
    indoor unit.
    Operation takes place successively at
    intervals of 1 second, by using combinations
    of the address setting of each unit.  In case of using shielded wires for inter-unit control 
    wiring, ground the shield on one side. (Fig. 1-109)
    Otherwise misoperation because of electrical noise
    may occur.
    Shielded wire
    Ground
    Fig. 1-109
    U1
    U2
    U1
    U2
    1
    2
    : Ground (earth)
    Outdoor unit
    Indoor unit
    No. 1
    1
    2 Remote
    Controller
    Inter-unit
    control
    wiringWire joint
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-111
    1. Specifications
    7-17. Wiring System Diagram for Group Control
    This diagram shows when several units (maximum of
    8) are controlled by a signal receiving unit (main
    unit). In this case, a signal receiving unit can be
    connected at any indoor unit.
     Group control using 2 signal receiving units
    It does not matter which of the 2 signal receiving units
    you set as the main controller.Wiring procedure
    Wire according to the diagram at left:
      Address setting is executed automatically when the 
    outdoor unit is turned on.
      Each successive unit will respond at one-second
    intervals following the order of the group address
    when the remote controller is operated.
    When using multiple signal receiving units (up to 2
    can be used), one is the main signal receiving
    unit and the other is the sub-signal receiving unit.
      To set up a sub-signal receiving unit, change its
    remote control address connector (RCU. ADR)
    located on its PCB from main to sub position
    (main: when shipped from factory).
    (sub)
    12
    Wire jointRemote
    Controller
    (main)
    : Ground (earth)
    Connection wiring
    for group control 12
    U1
    U2
    U1
    U2U1
    U2
    U1
    U2U1
    U2
    U1
    U2U1
    U2
    U1
    U2
    1
    2
    Outdoor unit
    Indoor unit
    No. 1
    1
    2
    Outdoor unit
    Indoor unit
    No. 2
    1
    2
    Outdoor unit
    Indoor unit
    No. 3
    1
    2
    Outdoor unit
    Indoor unit
    No. 8
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-112
    1. Specifications
    7-18. Wiring System Diagram for Multiple Remote Controllers
      To operate 1 indoor unit with 2 signal receiving units
    set at different locations.
    CAUTIONCarry out the wiring correctly
    (incorrect wiring will damage
    the equipment).
     When installing multiple remote controllers
    This multiple system is used for operating the unit(s) at
    different positions. (A maximum of 2 signal receiving
    units can be installed.)
     Setting method
    To execute this control, make the setting according
    to the following procedure.
    (1) Of the two installed signal receiving units, make
    one the main signal receiving unit (factory-shipped
    state).
    (2) On the other signal receiving unit, change the
    address connector on the PCB from main to sub
    position.
    In this state, it functions as a sub-signal receiving
    unit.
     Basic wiring diagram
    Connection wiring Signal receiving unit
    1
    2
    Indoor unit
    Earth(sub) (main)
    1
    2
    (Option)
    1
    2
    Remote control
    cable terminal
    board
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-113
    1. Specifications
    
    7-19. Test  Run  Procedure
       Wall mounted Type
        (K1 Type)
    7-20. Check Items Before the Test Run
    (1) Turn ON the remote power switch at least 12 hours before the test run in order to charge the crankcase heater.
    (2) Fully open the service valves on the gas-tube and liquid-tube sides.
    (3) Set the sliding switches on the inside of the wireless remote controller cover to the correct settings for that model.
    After changing the settings, press the RESET hole.
    Check the “Check Items Before the Test Run.”
    Set the indoor unit controller to “TEST.”
    Return the indoor unit controller to 
    “NORM.” (Item 7-21-3)NO
    Is operation
    possible? Verify the combination (wiring) of indoor and 
    outdoor units. 
    Check using the Diagnosis 
    function table. (Refer to 7-24)
    YESNote:   Check the indoor-side drainage.(Item 7-20)
    (Item 7-21-3)
    Wireless remote controller transmitter
    Verify that sliding switch 1 is in the “S” position.
    SKN
    Set sliding switch 2 to the correct setting for these models.
    A: Heat pump model
    (H: Heat pump, no auto heating/cooling)
    C: Cooling-only modelAHC AHCRESET hole
    Sliding switchSENSOR button
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							1-114
    1. Specifications
    7-21. Preparing for the Test Run
    7-21-1. Changing the room temperature sensor
      Room temperature sensors are installed inside the indoor unit and the wireless remote controller.
    Either room temperature sensor can be used.
      When “Unit Sensor” is indicated on the wireless remote controller’s LCD, the indoor unit sensor is operating as the 
    room temperature sensor.
    To change to the remote control sensor, open the remote control cover and press the SENSOR button once. The 
    “Unit Sensor” display disappears, and the remote control sensor becomes the room temperature sensor.
    CAUTION
    If the temperature data from the remote controller is not communicated to the indoor
    unit for a period of 10 minutes when the remote control sensor is selected, the unit
    automatically switches back to the indoor unit sensor.
    Install the remote controller in a location where the signal can reliably be received by
    the indoor unit.
    7-21-2. Using the remote controller
      Face the remote controller toward the receiver (indoor unit).
      The maximum distance where the remote controller signal can be received is approximately 26 ft., however this
    distance is only a guide. The actual distance may vary somewhat depending on battery capacity and other
    conditions.
      Make sure there are no obstructions which can block the signal between the remote controller and the receiver.
      When the remote controller signal is received correctly, the indoor unit beeps.
    (It beeps twice only when operation is started.)
      Do not drop, throw, or wash the remote controller.
      Do not place the remote controller in a location exposed to direct sunlight, or near a stove or similar appliance.
    7-21-3. Test  run
     Using the controller
    (1) Slide the main unit controller switch from “ON” to “TEST”.
    (The outdoor unit will not operate for approximately 3 minutes after
    the power is turned ON, or after operation is stopped.)
    (2) All indicator lamps on the display blink while test run is in progress.
    (3) Temperature control is not possible during the test run.
    (4) If normal operation is not possible, the lamps on the display will indicate
    the problem. Refer to “7-24. Diagnosis Table”.
    (5) After the test run is completed, move the controller switch from “TEST” to “ON”  and verify that the indicator lamps 
    stop blinking.
    (A 60-minute automatic OFF timer function is included in order to prevent continuous test run.)
    Receiver
    Wireless Remote Controller
    CAUTION
    Controller
    Indicator
    For S-26PK1U6 
    OFF ON
    TEST
     Do not use this setting at any time other than for the test run. Doing so will place an excessive load on
    the system.
       Test run is not possible if the power was turned ON when the controller switch was in the “TEST” position.
    Leave the power ON and move the switch to “OFF,” then move the switch back to “TEST.”
    1
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual