Home > Panasonic > Air Conditioner > Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual

Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							6-3
    6. Test run
     U1, K1, T1, F1 Type
    6-2. Caution
    This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit.
    The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The settings
    required for operation were made at the time of shipment.
    Only the correct combination of indoor and outdoor units can be used.
    This test run manual describes primarily the procedure when using the wired remote controller.
    6-3. Test Run Procedure
    Recheck the items (see IV-4) to che ck before the test run.
    Turn ON the indoor and outdoor power.
    Set the remote controller to “test run.”
    Return the remote controller to normal
    control.YESNO Automatic
    address?(See I-98)
    (See 6-4) Check the combination (wiring) of indoor and
    outdoor units.
    Refer to “Table of  Self-Diagnostic
    Functions and Corrections” to 
    check the system. YESNO
    Note:   Check the indoor-side drainage. Has the
    test run been
    completed?Check the warning code.
    Fig. 6-3
    6
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							6-4
    6. Test run
    6-4. Items to Check Before the Test Run
    (1)
    (2)Turn the breaker ON at least 12 hours in advance in order to energize the crank case heater.
    Fully open the closed valves on the liquid tube and gas tube sides.
    6-5. Test Run Using the Remote Controller
    (1) Press and hold the remote controller  button for 4 seconds or longer. Then press the  button.
    • “TEST” appears in the LCD display during the test run.
     Temperature control is not possible when test run mode is engaged.
    (This mode places a large load on the devices. Use it only when performing the test run.)
    (2)
    Note: The outdoor unit will not operate for approximately 3 minutes after the power is turned ON or after it stops
    operating.
    (3)
    Refer to the “Table of Self-Diagnostic Functions and Corrections” on the next page, and correct the problem.
    (4)
     button again. Check that “TEST” disappears from the LCD display.
    (This remote controller includes a function that cancels test run mode after 60 minutes have elapsed, in order to
    prevent continuous test run operation.)
    (5)Use either Heating or Cooling mode to perform the test run.
    If normal operation is not possible, a code appears on the remote controller LCD display.
    After the test run is completed, press the 
    For the test run of an inverter outdoor unit, operate the compressors for a minimum of 10 minutes.
    * When performing a test run using a wired remote controller, 
    operation is possible without attaching the cassette-type 
    ceiling panel. 
    (“P09” will not be displayed.)
    6-6. Precautions
    Request that the customer be present when the test run is performed. At this time, explain the operation manual
    and have the customer perform the actual steps.
    Be sure to pass the manuals and warranty certificate to the customer.
    Check that the AC 230 / 208 V power is not connected to the inter-unit control wiring connector terminal.
    * If AC 230 / 208 V is accidentally applied, the indoor or outdoor unit control PCB fuse (0.5A for both indoor
    and outdoor units) will blow in order to protect the PCB. Correct the wiring connections, then disconnect the
    2P connectors (indoor: blue, OC) (outdoor: blue, OC) that are connected to the PCB, and replace them with
    2P connectors (indoor: brown, EMG) (outdoor: brown, EMG). (Refer to the figure below.) If operation is still not
    possible after changing the brown connectors, try cutting the varistor (VA002) (both indoor and outdoor).
    (Be sure to turn the power OFF before performing this work.)
    Indoorunit control PCB
    Outdoorunit control PCB
    IC8Varistor (black)
    FuseVA002
    CN44 EMG
    CN40 OC VA002 (Varistor)
    OC (blue)
    connector
    0.5A 0.5ATerminal plug (black) 3 – 5 HP
    EMG (brown) connector
    Fig. 6-4
    Fuse
    CZ-RTC2
    6
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							6-5
    6. Test run
    Wired remote 
    controller display
    Cause
    Correction
    Nothing is
    displayedNothing is
    displayed
    E 0 1
     dis
    played
    E 0 2
     displayed
    E 0 9
     displayed
    E 1 4
     displayed
    E 0 4
     displayed
    E 0 6
     di
    splayed
    E 1 5
     displayed
    E 1 6
     displayed
    E 2 0
     di
    splayed
    P 0 5
     displayed
    L 0 2
     displayed
    L 1 3 
    displayed
    P 0 9
     displayed
    L 0 7
     displayed
    Indoor unit 
    receiver lampOperating
     lamp
    is blinking.
    Standby lamp
    is blinking.Both the Operation
    lamp and Stan
    dby 
    lamp are blinking
    together. Operation lamp an
    d
    S
    tandby lamp are 
    blinking alternately.
    Timer lamp and
    S
    tandby lamp are 
    blinking alternately.Remote co
    ntroller is not connected correctly.
    Indoor un
    it power is not ON.
    A
    utomatic address setting has n
    ot been
    completed.
    Inter-unit control wiring is cut or is not
    connected correctly.
    Remote controller is n
    ot conn
    ected correctly 
    (remote controller receiving failure).
    Remote controller is not connected correctly 
    (failure in transmission from remote controller
    to indoor unit).
    Indoor-outdoor inter-unit wiring is not
    connected correctly.
    Indoor unit capacity is too low.
    Indoor un
    it capacity is too hig
    h.
    No s
    erial sign
    al is bei
    ng received at all from 
    the indoor units.
    Inter-unit circu
    it or open phase i
    n the o
    utdoor
    unit power
    Insufficient
    gas
    Indoor-outdoor unit type mismatch
    The indoor unit ceiling panel connector is not
    conn
    ected correctly.Remote controller is not connected with 
    indoor unit correctly
    Indoor unit power is not ON.
    Automatic address setting has not been
    completed.
    Inter-unit control wiring is cut or is not
    connected correctly.
    Remote controller is not connected with 
    indoor unit correctly
    Remote controller is not connected with 
    indoor unit correctly
    Same as at left
    Indoor-outdoor inter-un
    it wiring is cut or 
    is not connected correctly.
    Same as at left
    Reversed phase or open phase in the 
    3
    -phase power at one of the outdoor
    un
    its i
    n the group
    Same as at leftSame as at left Same as at left
    Same as at left
    Same as at left
    Same as at leftSame as at left
    Same as at leftSame as at left
    Same as at left Same as at left Same as at leftSame as at left S
    ame as at left Same as at leftSame as at left
    Same as at left
    Same a
    s at left Remote controller crossover wiring is cut or 
    is not connected correctly.
    Indoor unit ceiling panel connector is not
    connected correctly.
    Remote controller crossover wiring is conn
    ected
    to the indoor unit, however it is set for individual
    operation.
    Connect the remote controller correctly.
    Turn ON the indoor unit power.
    2 remote controllers are 
    set as the main remote 
    controller.
    Check the remote controller and inter-unit
    control wiring.
    Perform automatic address setting.
    Connect the remote controller correctly.
    Refer to 11-8-6 Main-sub remote control, and
    make the correct settings.
    Check the remote controller crossover wiring.
    Perform automatic address setting again.
    Connect the wiring correctly.
    Refer to 11-8 System Control, and make the 
    correct settings.
    Check that the total capacitie
    s of the i
    ndoor
    and outdoor unit
    s are appropriate.Check that the indoor unit power is ON, and that 
    the inter-unit control wiring is connected correctly.Reverse 2 phases of the outdoor unit 3-phase
    power and connect them correctly.
    Check that the indoor and o
    utdoor unit types
    are correct.
    Perform automatic address s
    etting.
    Connect the indoor unit ceiling panel
    conn
    ector correctly.
    Ceiling panel connector at one of the 
    indoorunit
    s in the gro
    up i
    snot
    connected correctly.
    Reversed phase or ope
    n phase in the 
    outdoor unit 3-phase power 1:1 connectio
    nog n i s (  rG ) e p y t eno i t c e n n o c   p u lSimultaneous-operation multi system
    (flexible combination)Control by main-sub
    remote controllers
    6-7.  Table of Self-Diagnostic Functions and Corrections  (X, T, U, K Type)
    6-7. Table of Self-Diagnostic Functions and Corrections (U1, K1, T1, F1 Type)
    6
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							6-6
    6. Test run
    6-8. Examples of Wiring Diagrams
    Basic wiring diagram 1
    Single-type system
    Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.)
    1
    212
    0
    L2
    U1
    RCU2
    L1 U2U1 G
    1
    2
    System address rotary switch
    (Set to “0” at the time of shipment.)
    Outdoor unit
    Indoor
    unit
    Wired remote 
    controller
    WHTBLK
    (Optional)
    Remote controller wiring
    (Field supply) Ground
    Power supply
    Single-phase
    230 / 208 V
    Inter-unit power line
    230 / 208 V, 60 Hz
    Fig. 6-5
    6
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							6-7
    6. Test run
    1
    212 L2
    U1
    RCU2
    L1 U2U1 G
    1
    2
    12 L2
    U1
    RCU2
    L1 U2U1 G
    1
    2
    System address rotary switch
    (Set to “0”at the time of shipment.)
    Outdoor unit
    Indoor
    unit
    Wired remote
    controller
    WHTBLK
    (Optional)
    Remote controller wiring
    (Field supply)System address rotary switch
    (Set to “0” at the time of shipment.)
    Outdoor unit
    Indoor
    unit
    Remote controller crossover wiring
    for group control Ground
    Power supply
    Single-phase
    230 / 208 V
    Inter-unit power line
    230 / 208 V, 60 Hz
    Ground
    Power supply
    Single-phase
    230 / 208 V
    Inter-unit power line
    230 / 208 V, 60 Hz
    12
    Basic wiring diagram 2
    Group control (when a central control device is not used)
    Simultaneous-operation multi system
    A maximum of 8 indoor units can be connected to 1 remote controller.
    Set the system address (refrigerant tubing system address) before turning on the remote power switch.
    (Refer to “Setting the system addresses” on next page.)
    (Set using the system address rotary switch on the outdoor unit control PCB.)
    (Wiring procedure)
    (1) Connect the remote controller to the indoor unit remote
    controller wiring.
    Use the remote controller connection wire coming from
    the indoor unit, and field-supply wire and a wire joint to
    complete the connection as shown in Fig. 6-6b. The
    remote controller connection wire coming from the
    indoor unit includes a connector, therefore cut off the
    connector and use the wire joint to connect the wire
    from the remote controller.
    (2) Connect the indoor units (U1, U2) and the outdoor units
    (1, 2).
    Connect the other outdoor units and indoor units (with
    different refrigerant systems) in the same way.
    Connect the inter-unit control wiring to the indoor units
    (U1, U2) for each refrigerant system.
    (Inter-unit control wiring)
    Fig. 6-6b
    1
    2
    RC RC RC
    Indoor
    unit 1Indoor
    unit 2Indoor
    unit 3
    Wired remote 
    controller
    WHTBLK
    (Optional)
    Fig. 6-6a
    6
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							6-8
    6. Test run
    Setting the outdoor unit system addresses
    For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...)
    ON
    1
    2
    0
    System address rotary switch
    (Set to “0” at time of shipment)
    System address rotary switch
    System address
    DIPswitch
    OFFON 10s 20s
    3 –  5HPOutdoorunit control PCB
    Fig. 6-7
    System address No.System address 10s digit
    (2P DIP switch)System address 1s place
    (Rotary switch)
    0 Automatic address
    (Setting at shipment = “0”) 
    1 (If outdoor unit is No. 1)“0” setting0
    0
    1
    1
    1
    2
    Both OFF
    Both OFF
    Both OFF
    10s digit ON
    20s digit ON
    10s digit and 20s digit ON“1” setting
    “2” setting
    “1” setting
    “1” setting
    “0” setting 2 (If outdoor unit is No. 2)
    11 (If outdoor unit is No. 11)
    21 (If outdoor unit is No. 21)
    30 (If outdoor unit is No. 30)
    ONON
    OFF12
    ONON
    OFF12
    ONON
    OFF12
    ONON
    OFF12
    ONON
    OFF12
    ONON
    OFF12
    Automatic address setting using the remote controller
    When the outdoor unit shown in “Basic wiring diagram 2” is used for group control of multiple outdoor units , use the
    remote controller to perform automatic address setting. (During automatic address setting, “SETTING” blinks on the
    remote controller display.)
    Press the remote controller timer time   button and 
     button simultaneously. (Hold for 4 seconds or longer.)
    Then press the 
     button. (Item code “AA” appears: All systems automatic address setting.)
    (Automatic address setting is performed in sequence for all outdoor units from No. 1 to No. 30. When automatic
    address setting is completed, the units return to normal stopped status.)
    To select each refrigerant system individually and perform automatic address setting, press the remote controller
    timer time   button and 
     button simultaneously. (Hold for 4 seconds or longer.) Then press either the tempera-
    ture setting   or 
     button. (Item code “A1” appears: Individual system automatic address setting)
    Use either the 
     or  button to select the outdoor unit to perform automatic address setting. (For example,
    when selected R.C.1 “R.C.1” is displayed.) Then press the 
     button. (Automatic address setting is performed for
    refrigerant circuit 1.) When automatic address setting for circuit 1 is completed, the system returns to normal
    stopped status. When automatic address setting for circuit 1 is completed, the system returns to normal stopped
    status. In the same way, press the remote controller timer time   button and 
     button simultaneously to per-
    form automatic address setting for a different R.C. (refrigerant circuit) if necessary. Then in the same way as
    above (use the 
     button to display “R.C.2,” for example), select the next circuit and perform automatic ad-
    dress setting.
    System address rotary switch
    System address 10s digit and 20s digit
    DIP switch
    Automatic address
    button (black)
    Terminal plug (black)
    6
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							6-9
    6. Test run
    Indicating (marking) the indoor and outdoor unit combination number
    Indicate (mark) the number after automatic address setting is completed.
    (1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that
    the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB,
    and use a magic marker or similar means which cannot be easily erased to indicate the numbers in an easily
    visible location on the indoor units (near the indoor unit nameplates).
    Example: (Outdoor) 1 - (Indoor) 1-1...(Outdoor) 2 - (Indoor) 2-2...
    (2) These numbers will be needed for maintenance. Be sure to indicate them.
    * Use the remote controller to check the addresses of the indoor units. Press and hold the 
     button and 
    button for 4 seconds or longer (simple settings mode). Then press the button  and select the indoor
    address. (Each time the button is pressed, the address changes as follows: 1-1, 2-1, ....) The indoor unit fan
    operates only at the selected indoor unit. Confirm that correct fan is operating, and indicate address on the
    indoor unit.
    Press the 
     button again to return to the normal remote controller mode.
    For details, refer to the separate handbook.
    Main-sub remote controller control
    Control using 2 remote controller switches
    Main-sub remote controller control refers to the use of 2 remote controllers to control 1 indoor unit.
    (A maximum of 2 remote controllers can be connected.)
    Connecting 2 remote controllers to
    control 1 indoor unit
    1 2
    1 2
    1 2
    U1U2
    1 2
    Remote controller wiring
    OptionalOptional
    Remote controller
    switch (sub) Remote controller
    switch (main)
    Indoor unit
    Outdoor unit Ground
    Groundfor remote 
    controller wiring Terminal plate 
    RCU. Main/SubMain Sub
    CODEDATAITEM
    Clock display
    12 hours (AM/PM)24 hours
    RCU. CKNormal RCU. CK
    Room temperature sensorMain unit RCU
    Remote controller setting mode
    To set the remote controller main/sub setting or change the sensor, follow the steps below.
     Press both 
     and  buttons on the remote controller for more than 
    4 seconds together.
     Select CODE No. with 
     buttons.
     Change DATA with 
    / (TIMER) buttons.
     Press 
     . Finally, press   .
    *
    *Make sure to set [Normal] for RCU. CK. DATA is memorized in the RCU. (DATA setting will not
    be changed even when the power is turned off.)
    6
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							201201
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual