Home
>
Panasonic
>
Air Conditioner
>
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
6-3 6. Test run U1, K1, T1, F1 Type 6-2. Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit. The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The settings required for operation were made at the time of shipment. Only the correct combination of indoor and outdoor units can be used. This test run manual describes primarily the procedure when using the wired remote controller. 6-3. Test Run Procedure Recheck the items (see IV-4) to che ck before the test run. Turn ON the indoor and outdoor power. Set the remote controller to “test run.” Return the remote controller to normal control.YESNO Automatic address?(See I-98) (See 6-4) Check the combination (wiring) of indoor and outdoor units. Refer to “Table of Self-Diagnostic Functions and Corrections” to check the system. YESNO Note: Check the indoor-side drainage. Has the test run been completed?Check the warning code. Fig. 6-3 6 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
6-4 6. Test run 6-4. Items to Check Before the Test Run (1) (2)Turn the breaker ON at least 12 hours in advance in order to energize the crank case heater. Fully open the closed valves on the liquid tube and gas tube sides. 6-5. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer. Then press the button. • “TEST” appears in the LCD display during the test run. Temperature control is not possible when test run mode is engaged. (This mode places a large load on the devices. Use it only when performing the test run.) (2) Note: The outdoor unit will not operate for approximately 3 minutes after the power is turned ON or after it stops operating. (3) Refer to the “Table of Self-Diagnostic Functions and Corrections” on the next page, and correct the problem. (4) button again. Check that “TEST” disappears from the LCD display. (This remote controller includes a function that cancels test run mode after 60 minutes have elapsed, in order to prevent continuous test run operation.) (5)Use either Heating or Cooling mode to perform the test run. If normal operation is not possible, a code appears on the remote controller LCD display. After the test run is completed, press the For the test run of an inverter outdoor unit, operate the compressors for a minimum of 10 minutes. * When performing a test run using a wired remote controller, operation is possible without attaching the cassette-type ceiling panel. (“P09” will not be displayed.) 6-6. Precautions Request that the customer be present when the test run is performed. At this time, explain the operation manual and have the customer perform the actual steps. Be sure to pass the manuals and warranty certificate to the customer. Check that the AC 230 / 208 V power is not connected to the inter-unit control wiring connector terminal. * If AC 230 / 208 V is accidentally applied, the indoor or outdoor unit control PCB fuse (0.5A for both indoor and outdoor units) will blow in order to protect the PCB. Correct the wiring connections, then disconnect the 2P connectors (indoor: blue, OC) (outdoor: blue, OC) that are connected to the PCB, and replace them with 2P connectors (indoor: brown, EMG) (outdoor: brown, EMG). (Refer to the figure below.) If operation is still not possible after changing the brown connectors, try cutting the varistor (VA002) (both indoor and outdoor). (Be sure to turn the power OFF before performing this work.) Indoorunit control PCB Outdoorunit control PCB IC8Varistor (black) FuseVA002 CN44 EMG CN40 OC VA002 (Varistor) OC (blue) connector 0.5A 0.5ATerminal plug (black) 3 – 5 HP EMG (brown) connector Fig. 6-4 Fuse CZ-RTC2 6 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
6-5 6. Test run Wired remote controller display Cause Correction Nothing is displayedNothing is displayed E 0 1 dis played E 0 2 displayed E 0 9 displayed E 1 4 displayed E 0 4 displayed E 0 6 di splayed E 1 5 displayed E 1 6 displayed E 2 0 di splayed P 0 5 displayed L 0 2 displayed L 1 3 displayed P 0 9 displayed L 0 7 displayed Indoor unit receiver lampOperating lamp is blinking. Standby lamp is blinking.Both the Operation lamp and Stan dby lamp are blinking together. Operation lamp an d S tandby lamp are blinking alternately. Timer lamp and S tandby lamp are blinking alternately.Remote co ntroller is not connected correctly. Indoor un it power is not ON. A utomatic address setting has n ot been completed. Inter-unit control wiring is cut or is not connected correctly. Remote controller is n ot conn ected correctly (remote controller receiving failure). Remote controller is not connected correctly (failure in transmission from remote controller to indoor unit). Indoor-outdoor inter-unit wiring is not connected correctly. Indoor unit capacity is too low. Indoor un it capacity is too hig h. No s erial sign al is bei ng received at all from the indoor units. Inter-unit circu it or open phase i n the o utdoor unit power Insufficient gas Indoor-outdoor unit type mismatch The indoor unit ceiling panel connector is not conn ected correctly.Remote controller is not connected with indoor unit correctly Indoor unit power is not ON. Automatic address setting has not been completed. Inter-unit control wiring is cut or is not connected correctly. Remote controller is not connected with indoor unit correctly Remote controller is not connected with indoor unit correctly Same as at left Indoor-outdoor inter-un it wiring is cut or is not connected correctly. Same as at left Reversed phase or open phase in the 3 -phase power at one of the outdoor un its i n the group Same as at leftSame as at left Same as at left Same as at left Same as at left Same as at leftSame as at left Same as at leftSame as at left Same as at left Same as at left Same as at leftSame as at left S ame as at left Same as at leftSame as at left Same as at left Same a s at left Remote controller crossover wiring is cut or is not connected correctly. Indoor unit ceiling panel connector is not connected correctly. Remote controller crossover wiring is conn ected to the indoor unit, however it is set for individual operation. Connect the remote controller correctly. Turn ON the indoor unit power. 2 remote controllers are set as the main remote controller. Check the remote controller and inter-unit control wiring. Perform automatic address setting. Connect the remote controller correctly. Refer to 11-8-6 Main-sub remote control, and make the correct settings. Check the remote controller crossover wiring. Perform automatic address setting again. Connect the wiring correctly. Refer to 11-8 System Control, and make the correct settings. Check that the total capacitie s of the i ndoor and outdoor unit s are appropriate.Check that the indoor unit power is ON, and that the inter-unit control wiring is connected correctly.Reverse 2 phases of the outdoor unit 3-phase power and connect them correctly. Check that the indoor and o utdoor unit types are correct. Perform automatic address s etting. Connect the indoor unit ceiling panel conn ector correctly. Ceiling panel connector at one of the indoorunit s in the gro up i snot connected correctly. Reversed phase or ope n phase in the outdoor unit 3-phase power 1:1 connectio nog n i s ( rG ) e p y t eno i t c e n n o c p u lSimultaneous-operation multi system (flexible combination)Control by main-sub remote controllers 6-7. Table of Self-Diagnostic Functions and Corrections (X, T, U, K Type) 6-7. Table of Self-Diagnostic Functions and Corrections (U1, K1, T1, F1 Type) 6 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
6-6 6. Test run 6-8. Examples of Wiring Diagrams Basic wiring diagram 1 Single-type system Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.) 1 212 0 L2 U1 RCU2 L1 U2U1 G 1 2 System address rotary switch (Set to “0” at the time of shipment.) Outdoor unit Indoor unit Wired remote controller WHTBLK (Optional) Remote controller wiring (Field supply) Ground Power supply Single-phase 230 / 208 V Inter-unit power line 230 / 208 V, 60 Hz Fig. 6-5 6 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
6-7 6. Test run 1 212 L2 U1 RCU2 L1 U2U1 G 1 2 12 L2 U1 RCU2 L1 U2U1 G 1 2 System address rotary switch (Set to “0”at the time of shipment.) Outdoor unit Indoor unit Wired remote controller WHTBLK (Optional) Remote controller wiring (Field supply)System address rotary switch (Set to “0” at the time of shipment.) Outdoor unit Indoor unit Remote controller crossover wiring for group control Ground Power supply Single-phase 230 / 208 V Inter-unit power line 230 / 208 V, 60 Hz Ground Power supply Single-phase 230 / 208 V Inter-unit power line 230 / 208 V, 60 Hz 12 Basic wiring diagram 2 Group control (when a central control device is not used) Simultaneous-operation multi system A maximum of 8 indoor units can be connected to 1 remote controller. Set the system address (refrigerant tubing system address) before turning on the remote power switch. (Refer to “Setting the system addresses” on next page.) (Set using the system address rotary switch on the outdoor unit control PCB.) (Wiring procedure) (1) Connect the remote controller to the indoor unit remote controller wiring. Use the remote controller connection wire coming from the indoor unit, and field-supply wire and a wire joint to complete the connection as shown in Fig. 6-6b. The remote controller connection wire coming from the indoor unit includes a connector, therefore cut off the connector and use the wire joint to connect the wire from the remote controller. (2) Connect the indoor units (U1, U2) and the outdoor units (1, 2). Connect the other outdoor units and indoor units (with different refrigerant systems) in the same way. Connect the inter-unit control wiring to the indoor units (U1, U2) for each refrigerant system. (Inter-unit control wiring) Fig. 6-6b 1 2 RC RC RC Indoor unit 1Indoor unit 2Indoor unit 3 Wired remote controller WHTBLK (Optional) Fig. 6-6a 6 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
6-8 6. Test run Setting the outdoor unit system addresses For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...) ON 1 2 0 System address rotary switch (Set to “0” at time of shipment) System address rotary switch System address DIPswitch OFFON 10s 20s 3 – 5HPOutdoorunit control PCB Fig. 6-7 System address No.System address 10s digit (2P DIP switch)System address 1s place (Rotary switch) 0 Automatic address (Setting at shipment = “0”) 1 (If outdoor unit is No. 1)“0” setting0 0 1 1 1 2 Both OFF Both OFF Both OFF 10s digit ON 20s digit ON 10s digit and 20s digit ON“1” setting “2” setting “1” setting “1” setting “0” setting 2 (If outdoor unit is No. 2) 11 (If outdoor unit is No. 11) 21 (If outdoor unit is No. 21) 30 (If outdoor unit is No. 30) ONON OFF12 ONON OFF12 ONON OFF12 ONON OFF12 ONON OFF12 ONON OFF12 Automatic address setting using the remote controller When the outdoor unit shown in “Basic wiring diagram 2” is used for group control of multiple outdoor units , use the remote controller to perform automatic address setting. (During automatic address setting, “SETTING” blinks on the remote controller display.) Press the remote controller timer time button and button simultaneously. (Hold for 4 seconds or longer.) Then press the button. (Item code “AA” appears: All systems automatic address setting.) (Automatic address setting is performed in sequence for all outdoor units from No. 1 to No. 30. When automatic address setting is completed, the units return to normal stopped status.) To select each refrigerant system individually and perform automatic address setting, press the remote controller timer time button and button simultaneously. (Hold for 4 seconds or longer.) Then press either the tempera- ture setting or button. (Item code “A1” appears: Individual system automatic address setting) Use either the or button to select the outdoor unit to perform automatic address setting. (For example, when selected R.C.1 “R.C.1” is displayed.) Then press the button. (Automatic address setting is performed for refrigerant circuit 1.) When automatic address setting for circuit 1 is completed, the system returns to normal stopped status. When automatic address setting for circuit 1 is completed, the system returns to normal stopped status. In the same way, press the remote controller timer time button and button simultaneously to per- form automatic address setting for a different R.C. (refrigerant circuit) if necessary. Then in the same way as above (use the button to display “R.C.2,” for example), select the next circuit and perform automatic ad- dress setting. System address rotary switch System address 10s digit and 20s digit DIP switch Automatic address button (black) Terminal plug (black) 6 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
6-9 6. Test run Indicating (marking) the indoor and outdoor unit combination number Indicate (mark) the number after automatic address setting is completed. (1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB, and use a magic marker or similar means which cannot be easily erased to indicate the numbers in an easily visible location on the indoor units (near the indoor unit nameplates). Example: (Outdoor) 1 - (Indoor) 1-1...(Outdoor) 2 - (Indoor) 2-2... (2) These numbers will be needed for maintenance. Be sure to indicate them. * Use the remote controller to check the addresses of the indoor units. Press and hold the button and button for 4 seconds or longer (simple settings mode). Then press the button and select the indoor address. (Each time the button is pressed, the address changes as follows: 1-1, 2-1, ....) The indoor unit fan operates only at the selected indoor unit. Confirm that correct fan is operating, and indicate address on the indoor unit. Press the button again to return to the normal remote controller mode. For details, refer to the separate handbook. Main-sub remote controller control Control using 2 remote controller switches Main-sub remote controller control refers to the use of 2 remote controllers to control 1 indoor unit. (A maximum of 2 remote controllers can be connected.) Connecting 2 remote controllers to control 1 indoor unit 1 2 1 2 1 2 U1U2 1 2 Remote controller wiring OptionalOptional Remote controller switch (sub) Remote controller switch (main) Indoor unit Outdoor unit Ground Groundfor remote controller wiring Terminal plate RCU. Main/SubMain Sub CODEDATAITEM Clock display 12 hours (AM/PM)24 hours RCU. CKNormal RCU. CK Room temperature sensorMain unit RCU Remote controller setting mode To set the remote controller main/sub setting or change the sensor, follow the steps below. Press both and buttons on the remote controller for more than 4 seconds together. Select CODE No. with buttons. Change DATA with / (TIMER) buttons. Press . Finally, press . * *Make sure to set [Normal] for RCU. CK. DATA is memorized in the RCU. (DATA setting will not be changed even when the power is turned off.) 6 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC