Home > Panasonic > Air Conditioner > Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual

Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							5-3
    5. Outdoor unit maintenance remote control
    Remote controller Assy Special service checker wiring
    Relay connector (2P, white)PCB connector 
    (3P, blue)RC (3P, blue)
    Outdoor
    unit PCB
    5-3. Normal Display Operations and Functions
    Normal display functions
     Connect the special service checker wiring to the outdoor unit PCB.
    The connection is shown in the figure below.
    * It is not necessary to disconnect the communications line in the inter-unit control wiring if it has already been
    connected at this time.
    * Setting modes 1 and 2 can be used even when the outdoor unit is independent (when 1 maintenance remote
    controller is connected to 1 outdoor unit and automatic address setting for the indoor units has not been com-
    pleted).
    * Displays the overall system status for that refrigerant system.
    All units start/stop (Fig. 1)
    
    The
     button can be used to start and stop all the indoor units.
     The LED turns ON when 1 or more indoor units is operating.
     The LED blinks when an alarm has occurred at 1 or more indoor units
    during operation.
    Switching between cooling/heating (Fig. 1)
    
    The
     button switches between heating and cooling modes.
     The specifications are equivalent to the heating/cooling input that was
    present on earlier outdoor unit PCBs.
     The display shows the operating mode of the indoor unit with the lowest
    number.
    All units test run (Fig. 2)
    
    The
     button switches test run ON/OFF for all indoor units.
     Press and hold for 4 seconds to turn ON.
    “Test run” is displayed while the test run is in progress.
     Conditions of test runs that are started from the unit remote controller are
    not displayed on the outdoor unit maintenance remote controller.Fig. 1
    Fig.2
    5
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							5-4
    5. Outdoor unit maintenance remote control
    Display (functions)
     Use the temperature setting 
     and  buttons to change the item code.
    s k r a m e R s t n e t n o c y a l p s i D e d o c m e t I
    00 (1)s u t a t s l a i t i n i t A l a m r o n n e h w F F O : ) e d o c ( s t n e t n o c m r a l a t i n u r o o d t u O
    Blinking 8-alarm code display at pre-trip, LED (2)
    01 No. of indoor units connected in that refrigerant system
    02 Unit. Nos. of connected indoor units in that refrigerant system *2
    03 Operating status of indoor units in that refrigerant system (blinks when alarms occur) *2
    04 Unit Nos. of indoor units in that refrigerant system where the thermostats are ON *2
    05 No. of outdoor units connected in that refrigerant system
    No. of connected 
    units: 1
    06 Unit Nos. of connected outdoor units in that refrigerant system *2
    07 Operating status of outdoor units in that refrigerant system (blinks when alarms occur) *2
    08
    09
    0A
    0b
    0C
    0d
    0E
    0F
    10 Total compressor operating time (in 1-hr. units) *3
    11
    12
    13
    14
    15
    16 Total power ON time of outdoor unit (in 1-hr. units)
    17 Compressor start count
    18
    19
    FE Outdoor unit microcomputer firmware version
    FF Outdoor unit microcomputer software version
    * See following page for *2 and *3.
    (3) XX-YY R.C.
    Displays the outdoor unit address of the selected outdoor sub-bus.
    XX = Main bus line outdoor system address (1 – 30)
    YY = Outdoor unit address in outdoor sub-bus (1 – 4). This is “1” when
    there is only 1 outdoor unit.
    02: 
    
    01: 
    4 units connected
    Locations where (1), (2), and (3) are displayed
    are shown below.
    LED
    (3)(1)
    (2)
    5
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							5-5
    5. Outdoor unit maintenance remote control
    *2:7-segment, 4-digit display for remote controller timer display
    The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit (
    ) display and the
    colon.
    —
    ———————
    1
    7 1 2 1 7 28 1 3 1 38
    9 1 4 1 49
    510 15206 1 1 1 6
    21
    22 27 32 378 3 3 3 3 228
    9 3 4 3 4 229
    25 30 35 40  6 3 1 3 6 2
    Display for unit Nos. 1 – 20
    Display for unit Nos. 21 – 40Not lit
    LitNot lit
    LitNot lit
    LitNot lit
    Lit
     Display of unit No. 1
     Display of unit Nos. 1 and 2
     Display of unit Nos. 1, 2, and 3
     Display of unit Nos. 1, 2, 3, and 4 Not lit
    LitNot lit
    LitNot lit
    LitNot lit
    LitMeaning of display colon
    Meaning of display colonis not displayed.
    The meaning of the colon display changes in the same way, allowing unit Nos. up to 80 to be displayed.
    Sample displays of the unit Nos. of connected indoor units
    NOTE
    The colon display changes automatically every 10 seconds.
    (The display does not change if higher unit numbers do not
    exist.)
    Pressing the 
     button switches the display immediately to
    the next higher level, even if 10 seconds have not passed.
     (A) and (B) are displayed alternately.
    B A
    10: 
    *3:The total compressor operating time is displayed
    (in 1-hour units) using 8 digits.
     When the first 4 digits are displayed, the top
    point of the colon is lit.
     When the last 4 digits are displayed, the
    colon points are not lit.
     The display of the first 4 and last 4 digits
    changes automatically every 10 seconds. It
    can also be changed by pressing the 
    button.
    NOTE
    With the outdoor unit maintenance remote controller (when connected to the outdoor unit), the unit remote controller
    check functions will not operate.
    5
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							5-6
    5. Outdoor unit maintenance remote control
    5-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures
    
    (1) Press and hold the 
     button and  button simultaneously for 4 seconds or
    longer to switch to temperature monitor mode.
    During temperature monitoring, “Service Monitor” is lit.
    (The display and operations are the same as when monitor mode is started from
    the unit remote controller.)
    (2) Press 
     the button and select the indoor unit to monitor.
    (3) Use the temperature setting 
     and  buttons to select the item code of the
    temperature to monitor.
    The selected indoor unit No. and the temperature data are displayed.
    (4) To end monitoring, press the 
     button. The display returns to the normal display.
    * The display does not blink.
    (3)
    (1) (4)
    (2)
    e d o C f o g n i n a e M e d o c m e t I
    Indoor unit data 02 Indoor unit intake temp.
    03 Indoor unit heat exchanger temp. (E1)
    04 Indoor unit heat exchanger temp. (E2)
    05 –
    06 Indoor unit discharge temp.
    07 –
    08 –
    09
    Outdoor unit data 0A Discharge temp. (TD)
    0b –
    0C –
    0d Intake temp. (TS)
    0E Outdoor unit heat exchanger temp. (C1)
    0F Outdoor unit heat exchanger temp. (C2)
    10 –
    11 Outdoor air temp. (TO)
    12 –
    13 –
    14 Current value
    15 Outdoor MV value
    19 Frequency
    * Depending on the model, some items may not be displayed.
    5
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							5-7
    5. Outdoor unit maintenance remote control
    5-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History
    * Displays outdoor unit alarms only. Does not display indoor unit alarms.
    * Check the indoor unit alarm histories separately using the indoor unit remote
    controllers or other control device.
    
    (1) Press and hold the 
     button and  button simultaneously for 4 seconds or longer
    to change to outdoor unit alarm history mode.
    During the alarm history display, “Service Check” is lit.
    The display and operations are the same as the monitoring of the alarm device
    history that is performed using the unit remote controller. However, the outdoor unit
    address appears instead of the unit No.
    (2) Press the  button and select the outdoor unit for alarm history monitoring.
    (3) Use the temperature setting  and  buttons to select the item code for the alarm history.
    The display shows the address of the selected outdoor unit, the item code, and the alarm history (alarm data).
    The outdoor unit address is displayed as system XX-YY.
    System XX = Outdoor unit system address
    YY = Outdoor unit sub-bus address
    The item code is displayed as 01– 08. 01 indicates the most recent alarm.
    The alarm history is indicated by the alarm code. (If there have been no alarm codes, “
    ” is displayed.)
    (4) To clear the alarm history, press the 
     button. (The outdoor unit alarm history will be cleared.)
    (5) To end, press the  button. The display returns to the normal remote controller display.
    5-6. Setting Modes: Setting the Outdoor Unit EEPROM
     Setting mode 1
    
    (1) Press and hold the 
     button and  button simultaneously for 4 sec-
    onds or longer.
    (2) Use the temperature setting 
     and  buttons to change the item code.
    The item codes and setting data are shown in the table on the next
    page.
    (3) Use the timer time 
     and  buttons to change the setting data.
    To confirm the changed setting data, press the 
     button.
    (At this time, “Setting” stops blinking and remains lit.)
    (4) During this mode, “Setting” is displayed, blinking. The outdoor unit
    address display section displays “ALL,” the item code and number (DN
    value in the table), and the setting data (6 digits).
    (The setting data is displayed in 6 digits. The display changes between
    the first 3 digits (Fig. 
    A) and the last 3 digits (Fig. B).
    When the first 3 digits are displayed, the top point of the colon is lit.)
    (5) To end the setting mode, press the 
     button.
    (3)
    (1)
    (4)
    (2)
    (5)
    are displayed alternately.  Display of first 3 digits 
    A
    B
    Display of last 3 digits
    and
    (Example shows display of 000 001.)
    A
    B
    (3) (1)(2)
    (5)
    5
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							5-8
    5. Outdoor unit maintenance remote control
    List of Item Codes
    r e t e m a r a P e d o c m e t I
    01 Control system schedule
    02 Control system schedule
    03 Control system schedule
    04 Snowfall sensor operatio n 0 = No sensor, control performed 
    1 = No sensor, control not performed Do not set
    Do not set
    Do not set
    Do not set
    Do not set
    Do not set
    Do not set
    Do not set
    Do not set
    Do not set
    Do not set Do not set Do not set Do not set Do not set
    Do not set
    2 = Sensor present, control performed
    3 = Sensor present, control not performed
    05 Outdoor fan quiet mode Do not set
    06 Defrost fan speed selection Do not set
    07 Ignore capacity 0 = Disabled 1 = Ignores capacity ratio
    08 Control system schedule
    09 Control system schedule
    0A Control system schedule
    0b Control system schedule
    0C Forced operation of  0 = Disabled
    indoor unit drain pump 1 = During cooling only, 2 hours stopped + 20 minutes operating 
    (regardless of whether the unit is running or stopped)
    2 = During cooling only, 4 hours stopped + 20 minutes operating 
    (regardless of whether the unit is running or stopped)
    3 = At all times, 4 hours stopped + 20 minutes operating
    4 = At all times, 2 hours stopped + 20 minutes operating
    0d Odor countermeasure when  Do not set
    indoor cooling thermostat is OFF
    y l n o l o o C = 1 p m u p t a e H = 0 y l n o l o o C E 0
    0F Control system schedule
    10 Control system schedule
    11 Multi-floor installation
    12
    External Electronic Expansion Valve Kit
    13 Control system schedule
    4E Test mode 1
    4F Test mode 2      
    % 0 6 1 . . . % 0 0 1 . . . % 5 4 , % 0 4 1 d n a m e D 0 5
    % 0 6 1 . . . % 0 0 1 . . . % 5 4 , % 0 4 2 d n a m e D 1 5
    52 Current control leve l 40%, 45% ... 100% ... 160%,  –1 (normal: at shipment from factory)
    53
    Control system schedule 55Do not set Control system schedule 54
    7 5
    8 5
    9 5
    A 5
    B 56 5
    * Figures in parentheses indicate the data at the time of shipment from the factory.0 = No 1 = Yes
    Control system schedule
    Control system schedule
    Do not set
    Control system schedule
    Do not set Control system scheduleDo not set Control system schedule
    Do not set Control system scheduleDo not set Control system schedule
    5
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							5-9
    5. Outdoor unit maintenance remote control
     Setting mode 2
    
    (1) Press and hold the 
     button,  button, and  button simultaneously for 4
    seconds or longer.
    (2) Use the temperature setting 
     and  buttons to change the item code. The
    item codes and setting data are shown in the table below.
    (3) Use the timer time 
     and  buttons to change the setting data.
    To confirm the changed setting data, press the 
     button.
    (At this time, “Setting” stops blinking and remains lit.)
    (4) During this mode, “Setting” is displayed, blinking. The display shows the set
    outdoor unit address “System XX-YY” (System XX = System address, YY =
    Address at outdoor unit sub-bus), item code number (DN value in the table
    below), and the setting data (6 digits).
    (The setting data is displayed in 6 digits. The display changes between the first 3 digits (Fig. 
    A) and the last 3
    digits (Fig. 
    B). When the first 3 digits are displayed, the top point of the colon is lit.)
    (5) To end the setting mode, press the 
     button. The display returns to the normal display mode.
    (3) (1)(2)
    (5)
    80:   A  and  B  are displayed alternately. (Example shows 000 410 (R410A).)
    s t i g i d 3 t s a l f o y a l p s i D s t i g i d 3 t s r i f f o y a l p s i DA
    B
    (3) (1)(2)
    (5)
    5
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							5-10
    5. Outdoor unit maintenance remote control
    r e t e m a r a P e d o c m e t I
    80 Refrigerant type 407 = R407C   22 = R22   410 = R410A
    81 Outdoor unit capacity* 0 = Disabled             80 : 26 type
    112 : 36 typ 140 : 42 type
    Do not set
    Do not set
    Do not set 82 Control system schedule
    83 Control system schedule
    84 3-phase or single-phase 0 = 3-phase   1 = single-phase
    85 Power frequenc y Do not set
    86 Control system schedule
    List of Item Codes
    (*) Figures represent the capacity data for each model. Do not set 8E Control system scheduleDo not set
    8b Control system scheduleDo not set 8A Control system schedule0 = No  1 = Yes 89 Crank case heater controlDo not set
    88 Control system scheduleDo not set 87 Control system schedule
    5
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							6-1. Preparing for Test Run...............................................................................................
    6-2. Caution........................................................................................................................
    6-3. Test Run Procedure ....................................................................................................
    6-4. Items to Check Before the Test Run..........................................................................
    6-5. Test Run Using the Remote Controller ......................................................................
    6-6. Precautions................................................................................................................
    6-7. Table of Self-Diagnostic Functions and Corrections (U1, K1, T1, F1 Type)...............
    6-8. Examples of Wiring Diagrams....................................................................................6-2
    6-3
    6-3
    6-4
    6-4
    6-4
    6-5
    6-6
    6. TEST RUN
    6-1
    6
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    							6-2
    6. Test run
    6. TEST  RUN
    6-1. Preparing for Test Run
    Before attempting to start the air conditioner,
    check the following:
    (1) All loose matter is removed from the cabinet espe-
    cially steel filings, bits of wire, and clips.
    (2) The control wiring is correctly connected and all
    electrical connections are tight.
    (3) The protective spacers for the compressor used for
    transportation have been removed. If not, remove
    them now.
    (4) The transportation pads for the indoor fan have been
    removed. If not, remove them now.
    (5) The power has been supplied to the unit for at least
    5 hours before starting the compressor. The bottom
    of the compressor should be warm to the touch and
    the crankcase heater around the feet of the com-
    pressor should be hot to the touch. (Fig. 6-1)
    (6) Both the gas and liquid tube service valves are open.
    If not, open them now. (Fig. 6-2)
    (7) Request that the customer be present for the trial
    run.
    Explain the contents of the instruction manual, then
    have the customer actually operate the system.
    (8) Be sure to give the instruction manual and warranty
    certificate to the customer.
    (9) When replacing the control PCB, be sure to make all
    the same settings on the new PCB as were in use
    before replacement.
    The existing EEPROM is not changed, and is
    connected to the new control PCB.
    Fig. 6-1
    Fig. 6-2
    Power mains switch(Power must be turned ON
    at least 5 hours before
    attempting test run)ON
    Liquid tubeGas tube
    6
    4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual