Home
>
Panasonic
>
Air Conditioner
>
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual
Have a look at the manual Panasonic Inverter Air Conditioner R410A Technical Data And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
1-115 1. Specifications 7-22. Precautions Request that the customer be present at the time the test run is performed. Explain the Operating Instructions to the customer, and then have the customer actually operate the system. Be sure to pass the manual and warranty certi cate to the customer. Verify that the AC 208 / 230 V wiring is not connected to the terminal plate which is used to connect the inter-unit control wiring. * If AC 208 / 230 V is accidentally applied to this terminal plate, the fuse (0.5A for both indoor and outdoor units) on the inter-unit control PCB will be tripped in order to protect the PCB. Correct the wiring connections, then disconnect the 2P connectors (indoor unit: blue, OC, CN40; outdoor unit: blue, OC) which are connected to the PCB and connect the other 2P connectors (indoor unit: brown, EMG, CN44; outdoor unit: brown, EMG). (See the gure below.) If operation is still not possible with the brown connectors connected, cut the varistor (black) (for both the indoor and outdoor units). (Be sure to turn OFF the power before performing this work.) B C P l o r t n o c t i n u r o o d t u O B C P l o r t n o c t i n u r o o d n I Varistor (black)Fuse 0.5A Serial 1 connector (blue) Serial 2 connector (brown) Varistor (black) VA0022P connector (brown) 2P connector (blue) Fuse 0.5A CHK (2P plug) SW103TEST OFF ON 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-116 1. Specifications 7-23. When Setting Indoor Unit Control PCB Switch for Wall Mounted Indoor Unit When using both the wired and wireless remote controller, refer to the procedure below. If this setting is not made correctly an alarm will occur. (The operation lamp on the display blinks.) This setting is not necessary for the case of using wireless remote controller only. The slide switch setting at the time of factory shipment for model K1 type is “B.” When using wired remote controller as “sub”, to set its data to “sub” in remote controller setting mode. When using wireless remote controller as “sub”, set the switch on the indoor unit control PCS to A. S-26PK1U6 A Nos. 1, 2 OFF, No. 3 ON. B Nos. 1, 2, 3 all OFF When using wireless remote controller as “main” When using wireless remote controller as “sub” 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-117 1. Specifications 7-24. Diagnosis TableWired remote Cause E 0 1 E 0 2 E 0 9 E 1 4 E 0 4 E 0 6 E 1 5 E 1 6 E 2 0 P 0 5 L 0 2 P 0 9 dis played L 0 7 displayed Indoor unit 1:1 connection (single type) Nothing is displayedNothing is displayed displayed displayedOperating lamp is blinking. displayed displayed displayed displayed displayed displayed displayed displayed displayed displayed L 1 3 Standby lamp is blinking.Operation lamp and Standby lamp are blinking alternately. Both the Operation lamp and Standby lamp are blinking together. Timer lamp and Standby lamp are blinking alternately.Remote controller is not connected correctly. Indoor unit power is not ON. Automatic address setting has not been completed. Inter-unit control wiring is cut or is not connected correctly. Remote controller is not connected correctly (remote controller receiving failure). Remote controller is not connected correctly (failure in transmission from remote controller to indoor unit). Indoor-outdoor inter-unit wiring is not connected correctly. Indoor unit capacity is too low. Indoor unit capacity is too high. No serial signal is being received at all from the indoor units. Inter-unit circuit or open phase in the outdoor unit power Insufficient gas Indoor-outdoor unit type mismatch The indoor unit ceiling panel connector is not connected correctly.Group connection Remote controller is not connected with indoor unit correctly Indoor unit power is not ON. Automatic address setting has not been completed. Inter-unit control wiring is cut or is not connected correctly. Remote controller is not connected with indoor unit correctly Remote controller is not connected with indoor unit correctly Same as at left Indoor-outdoor inter-unit wiring is cut or is not connected correctly. Same as at left Reversed phase or open phase in the 3-phase power at one of the outdoor units in the group Same as at left Ceiling panel connector at one of the indoor units in the group is not connected correctly. Simultaneous-operation multi system (flexible combination) Same as at left Same as at left Same as at left Control wiring for group control is cut or is not connected correctly. Same as at left Same as at left Same as at left Reversed phase or open phase in the outdoor unit 3-phase power Same as at left Control wiring for group control is connected to the indoor unit, however it is set for individual operation. Indoor unit ceiling panel connector is not connected correctly.Control by main-sub remote controllers Same as at left Same as at left Same as at left 2 remote controllers are set as the main remote controller.Same as at left Same as at left Same as at left Same as at left Same as at left Same as at left Same as at left receiver lamp spcontroller dilay 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-118 1. Specifications 1-13. HOW TO PROCESS TUBING 8. HOW TO INSTALL THE TIMER WIRED REMOTE CONTROLLER The liquid tubing side is connected by a flare nut, and Refer to the Instraction Manual attaehed to the Timer Remote Controller. the gas tubing side is connected by brazing. 1. Connecting the Refrigerant Tubing Use of the Flaring Method Many conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts. Flaring Procedure with a Flare Tool (1) cutter. It is recommended to cut approx. 12 – 20 in. longer than the tubing length you estimate. (2)Cut the copper tube to the required length with a tube Remove burrs at each end of the copper tubing with a tube reamer or file. This process is important and should be done carefully to make a good flare. Be sure to keep any contaminants (moisture, dirt, metal filings, etc.) from entering the tubing. (Figs. 1-110 and 1-111) (3) mount it on the copper tube. (4)Remove the flare nut from the unit and be sure to Make a flare at the end of the copper tube with a flare tool. (Fig. 1-112) NOTE NOTE When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 1-111) NOTE A good flare should have the following characteristics: inside surface is glossy and smooth edge is smooth tapered sides are of uniform lengthFig. 1-110 Fig. 1-111 Fig. 1-112 Deburring BeforeAfter Reamer Copper tubing Flare toolFlare nut Copper tubing 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-119 1. Specifications Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. (2) Be sure to apply refrigerant lubricant to the matching surfaces of the are and union before connecting them together. This is effective for reducing gas leaks. (Fig. 1-113) (3) For proper connection, align the union tube and are tube straight with each other, then screw on the are nut lightly at rst to obtain a smooth match. (Fig. 1-114) Adjust the shape of the liquid tube using a tube bender at the installation site and connect it to the liquid tubing side valve using a are. Cautions During Brazing Replace air inside the tube with nitrogen gas to prevent copper oxide lm from forming during the brazing process. (Oxygen, carbon dioxide and Freon are not acceptable.) Do not allow the tubing to get too hot during brazing. The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become damaged. Therefore allow the tubing to cool when brazing. Use a reducing valve for the nitrogen cylinder. Do not use agents intended to prevent the formation of oxide lm. These agents adversely affect the refrigerant and refrigerant oil, and may cause damage or malfunctions. 2. Connecting Tubing between Indoor and Outdoor Units (1) Tightly connect the indoor-side refrigerant tubing extended from the wall with the outdoor-side tubing. (2) To fasten the are nuts, apply speci ed torque as shown at right. When removing the are nuts from the tubing connections, or when tightening them after connecting the tubing, be sure to use 2 adjustable wrenches or spanners. (Fig. 1-115) If the are nuts are over-tightened, the are may be damaged, which could result in refrigerant leakage and cause injury or asphyxiation to room occupants. When removing or tightening the gas tube are nut, use 2 adjustable wrenches together: one at the gas tube are nut, and one at part A. (Fig. 1-116) For the are nuts at tubing connections, be sure to use the are nuts that were supplied with the unit, or else are nuts for R410A (type 2). The refrigerant tubing that is used must be of the correct wall thickness as shown in the table at right. Because the pressure is approximately 1.6 times higher than conventional refrigerant pressure, the use of ordinary are nuts (type 1) or thin-walled tubes may result in tube rupture, injury, or asphyxiation caused by refrigerant leakage. In order to prevent damage to the are caused by over-tightening of the are nuts, use the table above as a guide when tightening. When tightening the are nut on the liquid tube, use an adjustable wrench with a nominal handle length of 7-7/8 in. Fig. 1-113 Apply refrigerant lubricant Fig. 1-114 Flare nut Union Fig. 1-115 Indoor unit Outdoor unitSpanner Torque wrench Fig. 1-116 A Tube diameter ø1/4 (6.35 mm) ø3/8 (9.52 mm) ø1/2 (12.7 mm) ø5/8 (15.88 mm) Tightening torque (approximate) 120 – 160 in.lbs (140 – 180 kgf · cm) 300 – 360 in.lbs (340 – 420 kgf · cm) 430 – 480 in.lbs (490 – 550 kgf · cm) 590 – 710 in.lbs (680 – 820 kgf · cm)t0.032 t0.032 t0.032 t0.04 Tube thickness (in.) 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-120 1. Specifications Do not use a spanner to tighten the valve stem caps. Doing so may damage the valves. Depending on the installation conditions, applying excessive torque may cause the nuts to crack. Precautions for Packed Valve Operation If the packed valve is left for a long time with the valve stem cap removed, refrigerant will leak from the valve. Therefore, do not leave the valve stem cap removed. Use a torque wrench to securely tighten the valve stem cap. Valve stem cap tightening torque: Charging port 70 – 85 in.lbs (80 – 100 kgf cm) ø3/8 (Liquid side)160 – 180 in.lbs (190 – 210 kgf cm) ø5/8 (Gas side)240 – 270 in.lbs (280 – 320 kgf cm) 3. Insulating the Refrigerant Tubing Tubing Insulation Thermal insulation must be applied to all unit tubing, including the distribution joint (purchased separately). * For gas tubing, the insulation material must be heat resistant to 248°F or above. For other tubing, it must be heat resistant to 176°F or above. Insulation material thickness must be 13/32 in. or greater. CAUTION If the exterior of the outdoor unit valves has been nished with a square duct covering, make sure you allow suf cient space to access the valves and to allow the panels to be attached and removed. Taping the are nuts Wind the white insulation tape around the are nuts at the gas tube connections. Then cover up the tubing connections with the are insulator, and ll the gap at the union with the supplied black insulation tape. Finally, fasten the insulator at both ends with the supplied vinyl clamps. (Fig. 1-119) Insulation material The material used for insulation must have good insulation characteristics, be easy to use, be age resistant, and must not easily absorb moisture. CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.Fig. 1-117 Fig. 1-118 Fig. 1-119 Never grasp the drain or refrigerant connecting outlets when moving the unit. Charging port Valve stem capValve stem Main valvePacked valve 2 tubes arranged together Inter-unit control wiringGas tube Liquid tube Armoring tape Insulation Unit side insulatorInsulation tape (white) (supplied) Sealer (supplied) Flare insulator (supplied) Tube insulator (not supplied) Heat resistant 248°F or above Vinyl clamps (supplied) Flare nut 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-121 1. Specifications 4. Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent condensation from over owing the drain pan, keep the drain hose separate from the refrigerant tubing. (2) Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (3) Clamp the tubing bundle to the wall, using 1 clamp approx. each meter (3 feet). (Fig. 1-120) NOTE Do not wind the armoring tape too tightly since this will decrease the heat insulation effect. Also ensure that the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing. 5. Finishing the Installation After nishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 1-121)Fig. 1-120 Fig. 1-121 Inter-unit control wiringGas tube Liquid tube Armoring tape Insulation Tubing Apply putty here 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-122 1. Specifications 1-14. LEAK TEST, EVACUATION AND ADDITIONAL REFRIGERANT CHARGE Perform an air-tightness test for this package A/C. Check that there is no leakage from any of the connections. Air and moisture in the refrigerant system may have undesirable effects as indicated below. pressure in the system rises operating current rises cooling (or heating) ef ciency drops moisture in the refrigerant circuit may freeze and block capillary tubing water may lead to corrosion of parts in the refrigerant system Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system. Air Purging with a Vacuum Pump (for Test Run) Preparation Check that each tube (both liquid and gas tubes) between the indoor and outdoor units has been properly connected and all wiring for the test run has been completed. Remove the valve caps from both the gas and liquid service valves on the outdoor unit. Note that both liquid and gas tube service valves on the outdoor unit are kept closed at this stage. The refrigerant charge at the time of shipment is only guaranteed suf cient for a tubing length of up to 100 ft. The tubing may exceed this length, up to the maximum permitted length; however, an additional charge is necessary for the amount that the tubing exceeds 100 ft. (No additional refrigerating machine oil is needed.) 1. Leak Test (1) With the service valves on the outdoor unit closed, remove the 1/4 in. are nut and its bonnet on the gas tube service valve. (Save for reuse.) (2) Attach a manifold valve (with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses. CAUTION Use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The “Hi” knob of the manifold valve must always be kept closed.Fig. 1-123 Fig. 1-122 Fig. 1-124 Manifold valve Pressure gaugeLo Hi Charge hose Outdoor unit Liquid tube Gas tubeNitrogen gas cylinder (In vertical standing position) Close Close Open Cylinder valve Outlet Inlet Vacuum pump Manifold gauge 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-123 1. Specifications (3) Pressurize the system up to 4.15 MPa (42 kgf/cm2G) with dry nitrogen gas and close the cylinder valve when the gauge reading reaches 4.15 MPa (42 kgf/cm 2G). Then, test for leaks with liquid soap. CAUTION To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than the bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position. Fig. 1-125 CAUTIONUse a cylinder speci cally designed for use with R410A. (4) Do a leak test of all joints of the tubing (both indoor and outdoor) and both gas and liquid service valves. Bubbles indicate a leak. Wipe off the soap with a clean cloth after the leak test. (5) After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder. 2. Evacuation Be sure to use a vacuum pump that includes a function for prevention of back- ow, in order to prevent back- ow of pump oil into the unit tubing when the pump is stopped. Perform vacuuming of the indoor unit and tubing. Connect the vacuum pump to the gas tube valve and apply vacuum at a pressure of –101kPa ( –755 mmHg, 5 Torr) or below. Continue vacuum application for a minimum of 1 hour after the pressure reaches –101kPa ( –755 mmHg, 5 Torr). (1) Attach the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Con rm that the “Lo” knob of the manifold valve is open. Then, run the vacuum pump. (2) When the desired vacuum is reached, close the “Lo” knob of the manifold valve and turn off the vacuum pump. Con rm that the gauge pressure is under –101kPa ( –755 mmHg, 5 Torr) after 4 to 5 minutes of vacuum pump operation. Manifold valve Pressure gaugeLo Hi Vacuum pump Outdoor unit Liquid tube Gas tube Close Close Open 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC
1-124 1. Specifications CAUTION To avoid gas from leaking when removing the charge hose, make sure the stem of the gas tube is turned all the way out (“BACK SEAT”) position. 3. Charging Additional Refrigerant Charging additional refrigerant (calculated from the liquid tube length as shown in Section 1-12. Installation Instructions, 1. Tubing Size, Table 1-2 Tubing Data for Models, Amount of additional refrigerant charge) using the liquid tube service valve. (Fig. 1-126) Use a balance to measure the refrigerant accurately. If the additional refrigerant charge amount cannot be charged at once, charge the remaining refrigerant in liquid form by using the gas tube service valve with the system in Cooling mode at the time of test run. (Fig. 1-127) * If an additional refrigerant charge has been performed, list the refrigerant tubing length and amount of additional refrigerant charge on the product label (inside the panel). 4. Finishing the Job (1) With a hex wrench, turn the liquid tube service valve stem counter-clockwise to fully open the valve. (2) Turn the gas tube service valve stem counter-clockwise to fully open the valve. (3) Loosen the charge hose connected to the gas tube service port (5/16.) slightly to release the pressure, then remove the hose. (4) Replace the 5/16. are nut and its bonnet on the gas tube service port and fasten the are nut securely with an adjustable wrench or box wrench. This process is very important to prevent gas from leaking from the system. (5) Replace the valve caps at both gas and liquid service valves and fasten them securely.Fig. 1-126 Fi g. 1-127 Valve Liquid Manifold valve Pressure gaugeLo Hi Outdoor unit Liquid tube Gas tube Close Close Close R410A Outdoor unit Liquid tube Gas tube Open Open Open 1 4.@1$J@64MFUUFSJOEC4.@1$J@64MFUUFSJOEC