Page 181
DK424 Installation AC Power Cabling Installation Strata DK I&M 5/995-31 DK424 Installation AC Power for Three or More Cabinets (Wall Mount) Local electrical codes specify that a maximum of one or two AC power cords from the system can be plugged into wall outlets. Systems with three or more cabinets must be equipped with power strips (RPSB1 or RPSB2) to adhere to this requirement. Each power strip has three outlets and an AC power cord. Three- or four-cabinet systems require one power strip, while...
Page 182
DK424 Installation Reserve Power Installation 5-32Strata DK I&M 5/99 Reserve Power Installation Two or four customer-supplied, 12VDC batteries (80 amp hours maximum) can be connected to the system as a power failure backup. In the event of a power failure, the system automatically switches over to battery power without any interruption to existing calls or other normal system functions. The length of time reserve power operates depends on the system, size and number of batteries provided, and the...
Page 183
DK424 Installation Reserve Power Installation Strata DK I&M 5/995-33 DK424 Installation Reserve Power for One or Two Cabinets (Wall Mount) 1. Connect the black jumper wire (supplied with the PBTC-3M cable) from the positive terminal of one 12VDC battery to the negative terminal of the second 12VDC battery (Figure 5-20). 2. Ensure that a serviceable 10-amp fuse is installed in the in-line fuse holder of the PBTC-3M cable. 3. Connect the PBTC-3M battery cable white lead to the open positive terminal of...
Page 184
DK424 Installation Reserve Power Installation 5-34Strata DK I&M 5/99 Reserve Power/AC Wiring for Three or More Cabinets (Floor Mount) Floor-mounted systems with three or more cabinets require a Conduit Connection Box (RCCB) to connect reserve power cabling and AC power cabling to the system. Only a qualified electrician can install cabling between the reserve power source and AC power cabling to the conduit connection box. All other steps required to install reserve power, including installation of...
Page 185
DK424 Installation Reserve Power Installation Strata DK I&M 5/995-35 DK424 Installation + + – – 12 VOLT 12 VOLT 1 2 3-24VPOWER +5V -5V AC INFGDC OUT +- ON OFF BATTPBTC-3M Cable RPSB280 Power Supply - Front View Right Side View Battery Box or Rack Two Jumper to Connect Batteries in Series (Supplied With PBTC Cable) Black Wires White Wires To Dedicated AC Outlet (See Important Note) Two PBTC-3M Cables Cabinet No. 1 Cabinet No. 2PBTC-3M Cable to BATT Connector of Power Supply in Cabinet 1 PBTC-3M Cable to...
Page 186
DK424 Installation Reserve Power Installation 5-36Strata DK I&M 5/99 CAB 2 CAB 3 CAB 4 CAB 5 CAB 6 CAB 1 RPSB1A RPSB1A RPSU280A RPSU280A AC IN AC IN RPSU280A AC IN RPSU280A AC IN RPSU280A AC IN RPSU280A MBJU (see Note below) Jumper Unit AC IN FG FG FG FG FG FG 2043 Frame Ground Screw (FG) Data Cables 115VAC ± 10VAC (50/60 Hz) (11.5 Amp max) Insulated Ground Wire “B” Earth Ground:Cold Water Pipe Or Ground RodAWG #6 Wire Maximum Length: 60 Feet Per General Rules of Article 250 Of The National Electric...
Page 187
DK424 Installation Reserve Power Installation Strata DK I&M 5/995-37 DK424 Installation CAB 1 CAB 2 CAB 3 CAB 4 CAB 5 CAB 6 CAB 7 RPSB1A RPSB1A RPSB2A RPSU280A RPSU280A AC IN AC IN RPSU280A AC IN RPSU280A AC IN RPSU280A AC IN RPSU280A MBJU (see Note below) Jumper Unit AC IN RPSU280A AC IN FG FG FG FG FG FG FG 2044 AC Cable Intercabinet Power Supply Ground Wire Frame Ground Screw (FG) Data Cables 115VAC ± 10VAC (50/60 Hz) (7.5 Amp max)Insulated Ground Wire “B” Earth Ground: Cold Water Pipe or Ground...
Page 188
DK424 Installation Reserve Power Installation 5-38Strata DK I&M 5/99 RBDB1A or RBDB2AF1 (250V, 12 amps each)F6 F7 F5 F4 F3 F2 RBDB1 (6 cabinets) or RBDB2 (7 cabinets) (Shown with cover off) BATT PSU RBDB1 or RBDB2 (shown with cover on) Top Mounting Hole Top Mounting Hole Bottom Mounting Hole Right Side View Remove three side screws to remove cover RBDB1 or RBDB2 (shown with cover on) Bottom Cabinet (wall mount installation) Second Cabinet Up (floor mount installation) Remove three side screws to...
Page 189
DK424 Installation Reserve Power Installation Strata DK I&M 5/995-39 DK424 Installation + – + – BATT PSU + + – – 12 Volt 12 Volt Right Side View Battery Cabinet or Rack RBTC1A-1.5M cables from RBDB/PSU connectors to individual power supply RBSU280 “BATT” connectors Battery Distribution Box RBDB1A (Three or more cabinets, up to six. RBDB2A is required for seven cabinets) White Wires 16 AWG WireTwo “C” cables to connect batteries in series Black Wires 12 Amp Fuse RBTCIA-2M cables to connect batteries...
Page 190
DK424 Installation Reserve Power Installation 5-40Strata DK I&M 5/99 + – + – BATT PSU + + – – 12 Volt 12 Volt Right Side View Battery Cabinet or Rack RBTC1A-1.5M cables from RBDB2/PSU connectors to individual power supply RBSU280 “BATT” connectors (supplied with RDBD2). White Wires 16 AWG WireThree “C” cables to connect batteries in series Black Wires 12 AMP Fuse RBTCIA-2M cables to connect batteries to RBDB2 distribution box (6.5 ft cables)RBDB2 To “BATT” Connector RPSU 280 Bottom Cabinet To...