Page 221
DK424 T1 Applications Strata DK I&M 5/996-11 DK424 T1 Applications Each RDTU T1 PCB requires the following connecting equipment and cables to provide service (see the following sections and Figure 6-4). RDTU to Network If the RDTU must interface to a public telephone network or common carrier T1 circuit, the RDTU must be connected to a CSU. Use the NDTU cable (30 ft. cable supplied with RDTU) to connect the RDTU to the CSU. The function of the CSU is to provide the required interface between the...
Page 222
DK424 T1 Applications 6-12Strata DK I&M 5/99 RDTU to PBX T1 (Separated Less Than 655 ft.) If the RDTU is within 655 ft. of the far-end PBX T1 circuit, a CSU is not required. However, connecting a RDTU T1 span to another PBX or Key/Hybrid T1, in a Tie line configuration at a distance less than 655 ft. (without a CSU) will require a customer provided special cable. The transmit and receive pair of this span cable must be separated by at least five cable pairs and the wires must be 24 AWG, twisted...
Page 223
DK424 T1 Hardware and Cabling Strata DK I&M 5/996-13 DK424 T1 Hardware and Cabling RDTU Cable Length Switch The distance between the DK424, RDTU and CSU or RDTU to other Customer Premise Equipment (CPE) T1 may vary (0~655 ft.) as shown. (See Figures 6-4, 6-5, and 6-6.) The RDTU interface transmitter must be equalized and its impedance must be matched to the cable length connecting the RDTU to the CSU or other CPE, T1. RDTU transmit equalization/ impedance matching is accomplished by setting RDTU...
Page 224
DK424 T1 Hardware and Cabling 6-14Strata DK I&M 5/99 Synchronization LEDs ©Primary Synchronization (PSYNC) LED (see Figure 6-1 on Page 6-6) – If one RDTU PCB is assigned as the Primary Timing T1 PCB in Program *42, the PSYNC LED of this RDTU PCB flashes when it is synchronized with the far end T1 span line clock provider. If the Primary RDTU is not synchronized with the clock provider, the PSYNC LED will be ON steady. The SSYNC LED of the Primary sync RDTU PCB should always be OFF. The Primary...
Page 225
DK424 T1 Hardware and Cabling Strata DK I&M 5/996-15 DK424 T1 1670 RDTU PCB (26) (1) (27) (2) T R T1 R1 Black Red White Green Customer-supplied Cable (See Notes) RDTU To Customer Premise Equipment (CPE) T1 RDTU Amphenol CPE T1 (PBX or Key System) or Channel Bank 655 Feet MaximumTransmit Receive (4) T (5) R (1) T1 (2) R1 Network Interface Unit USOC-RJ48C or RJ48X 8-Pin Modular (RJ45 Type Jack)NDTU DB-15 Connector (Male) DB-15 Connector (Female) Customer Supplied Cable (See Notes)RDTU To Network...
Page 226
DK424 T1 Loop Back Testing 6-16Strata DK I&M 5/99 Loop Back Testing The RDTU provides three loop back test configurations. These loop back tests should be performed as required in conjunction with CSU loop back tests (see CSU loop back test documentation). RDTU Self Test This test should be performed upon initial installation of a RDTU PCB. Program the RDTU per “System Programming for T1” on Page 6-3; then perform the RDTU loop back test, per the instructions in Figure 6-8, before connecting the...
Page 227
DK424 T1 Loop Back Testing Strata DK I&M 5/996-17 DK424 T1 Network/CSU/RDTU Span Test This test checks all equipment that is checked with the test in the above paragraph, but this test also checks that the RDTU Mitel LSI chip is functioning. Guidelines for this test are described in Figures 6-8~6-10. NoteLoop back tests with CSU and Network equipment can also be performed when connecting the RDTU PCB directly to a customer premise (PBX, Key Hybrid, Channel bank) T1 circuit. The RDTU Self Test is...
Page 228
DK424 T1 Performance Monitoring 6-18Strata DK I&M 5/99 Performance Monitoring The performance of the RDTU can be monitored using the Data Dump Mode. This requires an RSIU, RSIS, PIOU or PIOUS PCB, an ASCII terminal (or PC) and, if monitoring RDTU performance from a remote location, an IMDU or RMDS modem or Hayes compatible modem is required. The RDTU monitoring feature provides a printout (or CRT display) of RDTU detected T1 errors as shown in Figure 6-10. There are no time parameters given with...
Page 229
DK424 T1 Performance Monitoring Strata DK I&M 5/996-19 DK424 T1 Figure 6-10 RDTU Performance Monitor Printout The error categories are as follows: ©Synchro Bit Error: This counter increments each time the RDTU detects 1024 synchronization bit errors. ©Bipolar Violation Error: This counter increments each time the RDTU detects 6.55 x 104 bipolar violations. ©Slip error: This counter increments each time the RDTU detect 256 slips. ©CRC Errors: Cyclical Redundancy Check counter increments each time the...
Page 230
DK424 T1 T1 Fault Isolation 6-20Strata DK I&M 5/99 ä To receive the “T1 ERROR DISPLAY” from a terminal (local or remote) 1. Establish communication with the terminal or PC using a communication software (e.g., Procomm®). 2. Enter the security code, and press Enter (or Return ). 3. At the >MODE prompt, type DUMP (must be all caps), press Enter (or Return) . The >D prompt displays on your screen. 4. At the >D prompt, type T1ERR and press Enter (or Return ). The display (see Figure 6-10) shows...