Mitel SX-200 DIGITAL Pabx Engineering Information Manual
Have a look at the manual Mitel SX-200 DIGITAL Pabx Engineering Information Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 55 Mitel manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
![](/img/blank.gif)
Troubleshooting CHART 2-2 EMERGENCY TROUBLESHOOTING PROCEDURES ttep Action Description I Follow-up Remarks 1 Check if the green ACTIVE LED on the Main Control Yes: l Go to step 9. Card front panel is flashing. No : l Go to step 2. 2 Press the SYSTEM RESET pushbutton on the front l If the Main Control card 7-segment panel of the Main Control card. displays are blank, go to step 3; otherwise go to step 11. 3 Check if the POWER ON LED on the Bay 2 power Yes: l Go to step 4. supply is on (ensure the switch is in the ON No : 0 Go to step 8. position). 4 Turn the Bay 2 power supply off, reseat the Main Yes: 0 Go to step 1 I. Control card, and turn the power on again. No : l Go to step 5. Anything on 7-segment displays? 5 Turn the Bay 2 power supply off, unplug the Main l Reseat the Main Control Card; turn the see Fig Control Card, and verify that the flea clips are power back on. 2-l properly connected (particularly clips W4 and W8). l If the problem persists, go to step 6. 6 Check power rails and continuity on the Bay 2 * Verify that the required voltage signals see Fig backplane. actually are present at the Wlain Controi 2-2 card edge connectors. l Once verified go to step 7. 7 Power down Bay 2, remove Main Control card, and Yes: 0 Possible EPROM problem (check revision see Fig check if EPROM IC is securely installed. label) - replace Main Control card. 2-3 No : * If loose, plug in securely; go back to step the AC distribution frame, to the AC source. l If no cabling problems are found, refer to the Bay Power Supply troubleshooting procedures in Paragraph 4.19. Yes: l Stop. Continue to monitor system. No : a Press the SYSTEM RESET pushbutton on Page 2-4
![](/img/blank.gif)
Troubleshooting CHART 2-2 (Cont’d) EMERGENCY TROUBLESHOOTiNG PROCEDURES 12 13 18 Action :heck for the following error codes on the Main :ontrol card 7-segment displays: 0 E 0 E 1 E 6 E E 3 4 or E 2 E 7 E b. Sequence: E 2 8 9 b b - ANY OTHER ERROR CODE - Description / Follow-up l Power down Bay 2, remove Main Control card, check flea clip W3 - re-install or replace as required; go back to step 2. l If problem persists, replace Main Control card. 8 Power down Bay 2, remove Main Control card, inspect installation of DRAM and DX modules. @ If improperly installed, install correctly, and go back to step 2. * If properly installed, problem likely with 1. either DRAM or DX modules - replace Main Control card. 0 Power down Bay 2, replace Main Control card. * Power down Bay 2, remove Main Control card, inspect installation of EPROM IC. * If improperly installed, install- correctly, and go back to step 2. e If properly installed, problem likely with EPROM IC - replace Main Control card. * Power down Bay 2. remove Main Control card, inspect installation of DRAM module. 0 If improperly installed, install correctly, and go back to step 2. * If properly installed, problem likely with DRAM module - replace Main Control card. * GO to step 20. * Power down the Main Control card, and check the installation of the Decryption module. 0 If it is installed incorrectly, install it correctly. l If installed correctly, likely problem with Decryption module; replace Main Control card. * Go back to step 2. * If this persists, go to step 26. emarks ;ee Fig 2-1 see Fig 2-3 see Fig 2-3 see Fig 2-3 lee Note 1 see Not 2 Page 2-5
![](/img/blank.gif)
Troubleshooting CHART 2-2 (Cont’d) EMERGENCY TROUBLESHOOTING PROCEDURES Action Description / Follow-u ns as required, then go that the lock latch is closed. 0 If problem persists, go to step 22. . Replace diskette if damaged. l If not damaged, attempt to reset system o If problem persists, go to step 23. o If problem persists, go to step 24. Yes: * Go to step 25. position (up, with respect to the board). No : * Put switch into ON position, go to step 2. * If problem persists, go to step 26. Notes: 1. In this case, the normal test progression will take place, software will be loaded from disk, but will not be started; rather, the system resets This cycle will continue until the problem is corrected. 2. A normal running system may show other error codes on the 7-segment displays during normal operation; however, during a system reset, only those error codes shown in steps 12 through 18 are possible. Other error codes may be: a) Disk error codes - see paragraph 4.16. b) Faulty card error codes - where the top 7-segment display indicates the Bay number and the bottom -/-segment display indicates the slot number. Page 2-6
![](/img/blank.gif)
g$T I.. . . . . . . . . . . no & On S3 0 on 4 no I no I Inn [I SVSTEi RESET El RESET ALARM 0 PLANE -IANSFf El A3 II B3 0 0 0 0 0 I IUMPER POSITIONS ARE NDICATED THIS WAY: 0 TOP VIEW UOTE: ALL S3 SWITCHES MUST BE OFF (UP POSITION). PCTIVE WNOR ALARM MAJOR ALARM CRITICAL ALARM
![](/img/blank.gif)
BAY 2 SLOT 3+4 BAY 1 SLOT 7t8 BAY 1 SLOT 5t6 E4 (DG) 0 r-l .0-e 523-0 0 ABC NOT USED Jl TEMP SENSE pf NOT USED J17A 10 PCM TO 15 I BAV 3 20 Jl7B 25 PCM TO SAV 4 30 ;: -I s E. CONSOLE MAINTENANCE DISK DRIVE PANEL . . . . POWER .,27 lb DISK DRIVE DATA/ADDRESS 0 ABC 6 Ill25 NOT USED 0 SD 11130 J3 *a* T+R TEST LINE 0 . . J41 OCUP El (EDGI 8 E2 (DGi 0 WY 2 SLOT lt2 BAY 1 SLOT 3t4 BAY 1 SLOT lt2 NOTE: J19 = LOCAL RS-232 CONNECTOR ON MAINTENANCE PANEL 521 I REMOTE RS-232 CONNECTOR ON MAINTENANCE PANEL 7276RZE1 Figure 2-2 8X-200@ DlGlTAL PABX Backplane Troubleshooting Page 2-8
![](/img/blank.gif)
Troubleshooting DX MODULE DRAM MODULE EPfiOM IC Figure 2-3 Main Control Card Module Locations Page 2-9 --’
![](/img/blank.gif)
Troubleshooting PROCEDURE 2 - CRITICAL ALARM General --- 2.06 The raising of a critical alarm indicates a fault of actual or potentially catastrophic magnitude has occurred. Such an alarm is usually accompanied by activation of the automatic power fail transfer operation in a bay, bays, or throughout the entire system. Chart 2-3 shows the steps to be taken in analyzing a fault resulting in the raising of a critical system alarm. Refer to Section MITL9108-093-353-NA, General Maintenance Information for details on alarms. Page 2-10
![](/img/blank.gif)
Troubleshooting CHART 2-3 CRITICAL ALARM TROUBLESHOOTING PROCEDURES - SYSTEM #tep Action Description / Follow-up Remarks 1 Check if system has gone into power fail transfer Yes: l Go to step 2. see Note mode - examine maintenance log. No : l Force the system into power fail transfer 1 mode via the maintenance panel switches, and leave it in this condition until the system is repaired. . 2 Check if the Main Control card appears to be Yes: l Go to step 3. see Note functioning correctly - check visual displays on No : l Refer to Emergency Troubleshooting 3 Main Control card front panel. Procedures (Chart 2-2). 3 If there are analog cards in the system, check if Yes: 0 Go to step 4. see Note they seem to be functioning correctly - check No : e Refer to Peripheral Control Card 3 visual displays on control card front panels. troubleshooting procedures. 4 Check maintenance log history for indications of Yes: a Refer to the appropriate troubleshooting see Note trouble before the critical alarm; any such No : e Go to step 5. 2 indications? 5 Identify the fault(s) which caused the critical alarm l Use the SHOW ALARMS command. see Note condition. * If maintenance cannot be accessed, refer 2 to the Emergency Troubieshooting Procedures (Chart 2-2). 0, Go to step 6. 6 Refer to the appropriate troubleshooting * If this leads nowhere, go to-step 7. procedures as indicated by the alarm report. 7 Check maintenance log for possible cause(s). * If this uncovers a clue, refer to the see Note appropriate troubleshooting procedures; 2 otherwise go to step 6. 6 Check if the bays have power. Yes: 0 Go to step 9. No : 0 Refer to the power supply troubleshooting procedures. 9 Exercise call processing to test stability. e Make station-to-station calls, see Note station-to-trunk calls, etc. 4 * If critical alarm persists to this point, go to step 10. 10 Refer to the Power Fail Transfer card 8 If the PFT cards appear functional, go to troubleshooting procedures. step 11. 11 Refer to the Main Control card troubleshooting procedures. Notes: 1. Refer to Section MITL9108-093-353-NA, General Maintenance lnformation for details on the power fail transfer switches. 2. Refer to Section MITL9108-093-351-NA, RS-232 Maintenance Terminal for information on procedures. 3. Refer to Section MITL9108-093-353-NA, General Maintenance Information for detaits on control card status indicators. 4. Avoid using stations or trunks under Power Fail Transfer (PFT) control. Page 2-l 1
![](/img/blank.gif)
Troubleshooting PROCEDURE 3 - MAJOR ALARM General 2.07 A major alarm is raised when a serious degradation of service occurs. The major alarm is activated when a preprogrammed percentage of ports fail, or when any common control card fails. Refer to Section MITL9108-093-353-NA, General Maintenance Information for further details on alarms. Chart 2-4 outlines the troubleshooting procedures for both system-related major alarms and bay-related ma- jor alarms. Pa’ge 2-12
![](/img/blank.gif)
Troubleshooting CHART 2-4 MAJOR ALARM TROUBLESHOOTING PROCEDURES Action Description I Follow-up dentify the fault(s) which caused the major alarm ondition. 1 l Use the SHOW ALARMS command. l If maintenance cannot be accessed, refer to the Main Control card troubleshooting procedures. l Go to step 2. 2 lefer to the appropriate troubleshooting * If this leads nowhere, go to step 3. rrocedures as indicated by the alarm report. 3 Check maintenance log for possible cause(s). l If this uncovers a clue, refer to the appropriate troubleshooting procedures. 0 If this is a system major alarm, or a digital bay major alarm, go to step 4. * Otherwise go to step 6. 4 Check if the affected bay(s) have power. (es: l Go to step 5. Uo : 0 Refer to the bay power supply troubleshooting procedures. 5 Check if the Main Control card appears to be fes: * Go to step 8. unctioning correctly. Uo : e Refer to the Main Control card troubleshooting procedures. 6 Check if the affected bay(s) have power. les: l Go to step 7. Uo : * Refer to the rear-door power supply troubleshooting procedures. 7 f there are analog cards in the system, check if fes: l Go to step 8. hey appear to be functioning correctly. Vo : * Refer to Peripheral Control Card troubleshooting procedures. a Check connections at the backplane (see Fig. 2-2). 0 Secure connections / replace cable as required. * Go to step 9. 9 Check maintenance log history for indications of Yes: l Refer to the appropriate troubleshooting trouble before the major alarm; any such procedures. indications? No : * Go to step 10. 10 Check if any other observable cause exists for the Yes: * Refer to the appropriate troubleshooting alarm. procedures. No : * Alarm may have been caused by a transient condition; record details and monitor the system’s progress. - ?e Note 1 ze Note 2 ee Note 2 ee Note 3 Notes: 1. Refer to Section MITL9108-093-351-NA, RS-232 Maintenance Terminal for details of procedures. emarks 2. Refer to Section MITL9108-093-353-NA, General Maintenance Information for details of control card status indicators. 3. Refer to Section MITL9108-093-200-NA, Shipping, Receiving and Installation for loca- tion and connections of the interconnect card. Page 2-13