Home > Mitel > Communications System > Mitel SX-200 DIGITAL Pabx Engineering Information Manual

Mitel SX-200 DIGITAL Pabx Engineering Information Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Mitel SX-200 DIGITAL Pabx Engineering Information Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 55 Mitel manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Troubleshooting 
    CHART 2-2 
    EMERGENCY TROUBLESHOOTING PROCEDURES 
    ttep 
    Action Description I Follow-up Remarks 
    1 Check if the green ACTIVE LED on the Main Control Yes: l Go to step 9. 
    Card front panel is flashing. No : l Go to step 2. 
    2 Press the SYSTEM RESET pushbutton on the front l If the Main Control card 7-segment 
    panel of the Main Control card. displays are blank, go to step 3; 
    otherwise go to step 11. 
    3 Check if the POWER ON LED on the Bay 2 power Yes: l Go to step 4. 
    supply is on (ensure the switch is in the ON No : 0 Go to step 8. 
    position). 
    4 Turn the Bay 2 power supply off, reseat the Main Yes: 0 Go to step 1 I. 
    Control card, and turn the power on again. No : l Go to step 5. 
    Anything on 7-segment displays? 
    5 Turn the Bay 2 power supply off, unplug the Main l Reseat the Main Control Card; turn the see Fig 
    Control Card, and verify that the flea clips are power back on. 2-l 
    properly connected (particularly clips W4 and W8). l If the problem persists, go to step 6. 
    6 Check power rails and continuity on the Bay 2 * Verify that the required voltage signals see Fig 
    backplane. actually are present at the Wlain Controi 2-2 
    card edge connectors. 
    l Once verified go to step 7. 
    7 Power down Bay 2, remove Main Control card, and Yes: 0 Possible EPROM problem (check revision see Fig 
    check if EPROM IC is securely installed. label) - replace Main Control card. 2-3 
    No : * If loose, plug in securely; go back to step 
    the AC distribution frame, to the AC 
    source. 
    l If no cabling problems are found, refer to 
    the Bay Power Supply troubleshooting 
    procedures in Paragraph 4.19. 
    Yes: l Stop. Continue to monitor system. 
    No : a Press the SYSTEM RESET pushbutton on 
    Page 2-4  
    						
    							Troubleshooting 
    CHART 2-2 (Cont’d) 
    EMERGENCY TROUBLESHOOTiNG PROCEDURES 
    12 
    13 
    18 Action 
    :heck for the following error codes on the Main 
    :ontrol card 7-segment displays: 
    0 
    E 
    0 
    E 
    1 
    E 
    6 E E 
    3 4 or 
    E 
    2 
    E 
    7 
    E 
    b. 
    Sequence: E 
    2 8 9 b b 
    - ANY OTHER ERROR CODE - Description / Follow-up l Power down Bay 2, remove Main Control 
    card, check flea clip W3 - re-install or 
    replace as required; go back to step 2. 
    l If problem persists, replace Main Control 
    card. 
    8 Power down Bay 2, remove Main Control 
    card, inspect installation of DRAM and DX 
    modules. 
    @ If improperly installed, install correctly, 
    and go back to step 2. 
    * If properly installed, problem likely with 
    1. either DRAM or DX modules - replace 
    Main Control card. 
    0 Power down Bay 2, replace Main Control 
    card. 
    * Power down Bay 2, remove Main Control 
    card, inspect installation of EPROM IC. 
    * If improperly installed, install- correctly, 
    and go back to step 2. 
    e If properly installed, problem likely with 
    EPROM IC - replace Main Control card. 
    * Power down Bay 2. remove Main Control 
    card, inspect installation of DRAM 
    module. 
    0 If improperly installed, install correctly, 
    and go back to step 2. 
    * If properly installed, problem likely with 
    DRAM module - replace Main Control 
    card. 
    * 
    GO to step 20. 
    * Power down the Main Control card, and 
    check the installation of the Decryption 
    module. 
    0 If it is installed incorrectly, install it 
    correctly. 
    l If installed correctly, likely problem with 
    Decryption module; replace Main Control 
    card. 
    * Go back to step 2. 
    * If this persists, go to step 26. emarks 
    ;ee Fig 
    2-1 
    see Fig 
    2-3 
    see Fig 
    2-3 
    see Fig 
    2-3 
    lee Note 
    1 
    see Not 
    2 
    Page 2-5  
    						
    							Troubleshooting 
    CHART 2-2 (Cont’d) 
    EMERGENCY TROUBLESHOOTING PROCEDURES 
    Action Description / Follow-u 
    ns as required, then go 
    that the lock latch is closed. 0 If problem persists, go to step 22. 
    . Replace diskette if damaged. 
    l If not damaged, attempt to reset system 
    o If problem persists, go to step 23. 
    o If problem persists, go to step 24. 
    Yes: * Go to step 25. 
    position (up, with respect to the board). No : * Put switch into ON position, go to step 2. 
    * If problem persists, go to step 26. 
    Notes: 1. In this case, the normal test progression will take place, software will be loaded from 
    disk, but will not be started; rather, the system resets This cycle will continue until the 
    problem is corrected. 
    2. A normal running system may show other error codes on the 7-segment displays 
    during normal operation; however, during a system reset, only those error codes 
    shown in steps 12 through 18 are possible. Other error codes may be: 
    a) Disk error codes - see paragraph 4.16. 
    b) Faulty card error codes - where the top 7-segment display indicates the Bay 
    number and the bottom -/-segment display indicates the slot number. 
    Page 2-6  
    						
    							g$T 
    I.. . . . . . . . . . . 
    no & 
    On 
    S3 0 
    on 
    4 no I 
    no I 
    Inn [I SVSTEi 
    RESET 
    El 
    RESET 
    ALARM 
    0 
    PLANE 
    -IANSFf 
    El 
    A3 
    II 
    B3 0 
    0 
    0 
    0 
    0 
    I IUMPER POSITIONS ARE 
    NDICATED THIS WAY: 
    0 TOP VIEW 
    UOTE: ALL S3 SWITCHES 
    MUST BE OFF 
    (UP POSITION). 
    PCTIVE 
    WNOR ALARM 
    MAJOR ALARM 
    CRITICAL ALARM  
    						
    							BAY 2 SLOT 3+4 BAY 1 SLOT 7t8 BAY 1 SLOT 5t6 
    E4 (DG) 0 
    r-l 
    .0-e 523-0 0 ABC 
    NOT USED 
    Jl 
    TEMP SENSE pf 
     NOT USED 
    J17A 
    10  
    PCM TO 
    15 
    I  BAV 3 
    20 
    Jl7B 
    25 PCM TO 
    SAV 4 
    30 
    ;: 
    -I s 
    E. 
    CONSOLE 
    MAINTENANCE 
    DISK DRIVE PANEL 
    . . . . 
    POWER 
    .,27 
    lb 
    DISK DRIVE 
    DATA/ADDRESS 
    0 ABC 
    6 
    Ill25 NOT USED 
    0 SD 
    11130 J3 *a* 
    T+R TEST LINE 0 . . J41 OCUP 
    El (EDGI 
    8 
    E2 (DGi 
    0 
    WY 2 SLOT lt2 BAY 1 SLOT 3t4 BAY 1 SLOT lt2 
    NOTE: J19 = LOCAL RS-232 CONNECTOR 
    ON MAINTENANCE PANEL 
    521 I REMOTE RS-232 CONNECTOR 
    ON MAINTENANCE PANEL 
    7276RZE1 
    Figure 2-2 8X-200@ DlGlTAL PABX Backplane  Troubleshooting 
    Page 2-8  
    						
    							Troubleshooting 
    DX 
    MODULE 
    DRAM 
    MODULE 
    EPfiOM 
    IC 
    Figure 2-3 Main Control Card Module Locations 
    Page 2-9 --’  
    						
    							Troubleshooting 
    PROCEDURE 2 - CRITICAL ALARM 
    General 
    --- 2.06 The raising of a critical alarm indicates a fault of actual or 
    potentially catastrophic magnitude has occurred. Such an alarm 
    is usually accompanied by activation of the automatic power fail 
    transfer operation in a bay, bays, or throughout the entire system. 
    Chart 2-3 shows the steps to be taken in analyzing a fault resulting in 
    the raising of a critical system alarm. Refer to Section 
    MITL9108-093-353-NA, General Maintenance Information for details on 
    alarms. 
    Page 2-10  
    						
    							Troubleshooting 
    CHART 2-3 
    CRITICAL ALARM TROUBLESHOOTING PROCEDURES - SYSTEM 
    #tep Action Description / Follow-up Remarks 
    1 Check if system has gone into power fail transfer Yes: l Go to step 2. see Note 
    mode - examine maintenance log. No : l Force the system into power fail transfer 1 
    mode via the maintenance panel 
    switches, and leave it in this condition 
    until the system is repaired. . 
    2 Check if the Main Control card appears to be Yes: l Go to step 3. see Note 
    functioning correctly - check visual displays on No : l Refer to Emergency Troubleshooting 3 
    Main Control card front panel. Procedures (Chart 2-2). 
    3 If there are analog cards in the system, check if Yes: 0 Go to step 4. see Note 
    they seem to be functioning correctly - check No : e Refer to Peripheral Control Card 3 
    visual displays on control card front panels. troubleshooting procedures. 
    4 Check maintenance log history for indications of Yes: a Refer to the appropriate troubleshooting see Note 
    trouble before the critical alarm; any such No : e Go to step 5. 2 
    indications? 
    5 Identify the fault(s) which caused the critical alarm l Use the SHOW ALARMS command. see Note 
    condition. * If maintenance cannot be accessed, refer 2 
    to the Emergency Troubieshooting 
    Procedures (Chart 2-2). 
    0, Go to step 6. 
    6 Refer to the appropriate troubleshooting * If this leads nowhere, go to-step 7. 
    procedures as indicated by the alarm report. 
    7 Check maintenance log for possible cause(s). * If this uncovers a clue, refer to the see Note 
    appropriate troubleshooting procedures; 2 
    otherwise go to step 6. 
    6 Check if the bays have power. Yes: 0 Go to step 9. 
    No : 0 Refer to the power supply 
    troubleshooting procedures. 
    9 Exercise call processing to test stability. e Make station-to-station calls, see Note 
    station-to-trunk calls, etc. 4 
    * If critical alarm persists to this point, go 
    to step 10. 
    10 Refer to the Power Fail Transfer card 8 If the PFT cards appear functional, go to 
    troubleshooting procedures. step 11. 
    11 Refer to the Main Control card troubleshooting 
    procedures. 
    Notes: 1. Refer to Section MITL9108-093-353-NA, General Maintenance lnformation for details 
    on the power fail transfer switches. 
    2. Refer to Section MITL9108-093-351-NA, RS-232 Maintenance Terminal for information 
    on procedures. 
    3. Refer to Section MITL9108-093-353-NA, General Maintenance Information for detaits 
    on control card status indicators. 
    4. Avoid using stations or trunks under Power Fail Transfer (PFT) control. 
    Page 2-l 1  
    						
    							Troubleshooting 
    PROCEDURE 3 - MAJOR ALARM 
    General 
    2.07 A major alarm is raised when a serious degradation of service 
    occurs. The major alarm is activated when a preprogrammed 
    percentage of ports fail, or when any common control card fails. Refer 
    to Section MITL9108-093-353-NA, General Maintenance Information 
    for further details on alarms. Chart 2-4 outlines the troubleshooting 
    procedures for both system-related major alarms and bay-related ma- 
    jor alarms. 
    Pa’ge 2-12  
    						
    							Troubleshooting 
    CHART 2-4 
    MAJOR ALARM TROUBLESHOOTING PROCEDURES 
    Action Description I Follow-up 
    dentify the fault(s) which caused the major alarm 
    ondition. 
    1 l Use the SHOW ALARMS command. 
    l If maintenance cannot be accessed, refer 
    to the Main Control card troubleshooting 
    procedures. 
    l Go to step 2. 
    2 lefer to the appropriate troubleshooting * If this leads nowhere, go to step 3. 
    rrocedures as indicated by the alarm report. 
    3 Check maintenance log for possible cause(s). l If this uncovers a clue, refer to the 
    appropriate troubleshooting procedures. 
    0 If this is a system major alarm, or a 
    digital bay major alarm, go to step 4. 
    * Otherwise go to step 6. 
    4 Check if the affected bay(s) have power. (es: l Go to step 5. 
    Uo : 0 Refer to the bay power supply 
    troubleshooting procedures. 
    5 Check if the Main Control card appears to be fes: * Go to step 8. 
    unctioning correctly. Uo : e Refer to the Main Control card 
    troubleshooting procedures. 
    6 Check if the affected bay(s) have power. les: l Go to step 7. 
    Uo : * Refer to the rear-door power supply 
    troubleshooting procedures. 
    7 f there are analog cards in the system, check if fes: l Go to step 8. 
    hey appear to be functioning correctly. Vo : * Refer to Peripheral Control Card 
    troubleshooting procedures. 
    a Check connections at the backplane (see Fig. 2-2). 0 Secure connections / replace cable as 
    required. 
    * Go to step 9. 
    9 Check maintenance log history for indications of Yes: l Refer to the appropriate troubleshooting 
    trouble before the major alarm; any such procedures. 
    indications? No : * Go to step 10. 
    10 Check if any other observable cause exists for the Yes: * Refer to the appropriate troubleshooting 
    alarm. procedures. 
    No : * Alarm may have been caused by a 
    transient condition; record details and 
    monitor the system’s progress. 
    - 
    ?e Note 
    1 
    ze Note 
    2 
    ee Note 2 
    ee Note 3 
    Notes: 1. Refer to Section MITL9108-093-351-NA, RS-232 Maintenance Terminal for details of 
    procedures. 
    emarks 
    2. Refer to Section MITL9108-093-353-NA, General Maintenance Information for details 
    of control card status indicators. 
    3. Refer to Section MITL9108-093-200-NA, Shipping, Receiving and Installation for loca- 
    tion and connections of the interconnect card. 
    Page 2-13  
    						
    All Mitel manuals Comments (0)

    Related Manuals for Mitel SX-200 DIGITAL Pabx Engineering Information Manual