    Have a look at the manual Lucent Technologies DEFINITY Enterprise Communications Server Release 8.2 Installation And Maintenance For Survivable Remote EPN Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Installation 
    1-9 Install the SRP cabinet 
    1
    3. Alig n the mounting  holes in the g round  p late with the four holes at the top 
    of the c ab inet b elow the top  c abinet. Slid e the mounting  plate d own to 
    seat on the sc rews.
    4. Do not tig hten the sc rews yet.
    Install front ground plates (Systems with
    radiation shielding and earthquake protection)
    Use the front g round  p late instead  of the c ab inet c lip  to attac h the c ab inets to 
    eac h other. Use one front g round  p late b etween two 
    stac ked c ab inets.
    1. At the front of the c ab inets, alig n the holes in the top  of the front g round  
    p late with the holes at the b ottom of the up per c ab inet, and insert the four 
    sc rews. Do not tighten the sc rews yet. See Fi g u re  1 - 3
    .
    2. At the front of the c ab inets, alig n the holes in the b ottom of the front 
    g round  p late with the holes at the top of the lower c ab inet. Insert the four 
    sup p lied  #12-24 x 1/2-inc h (1.27 c m) thread -forming sc rews. 
    3. Tighten all screws securely. 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Installation 
    1-10 Install the SRP cabinet 
    1
    Figure 1-3. Rear ground plate and front plate or cabinet clip — side view Figure Notes
    1. Front ground  p late or c ab inet c lip 2. Rear g round  plate
    21
    scdfgrpl KLC 011799 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Installation 
    1-11 Install the SRP cabinet 
    1
    Install cabinet clips (Systems without
    earthquake protection)
    A c ab inet c lip  is required  b etween eac h p air of stac ked  c ab inets.
    At the front of the c ab inets, install a c ab inet c lip  b etween eac h p air of c ab inets 
    b y hooking  the c lip  into the slot of the up p er c ab inet and  snap p ing the straig ht 
    leg of the c lip  into the slot on the lower c ab inet. See Fig ure  1-4
    .
    Figure 1-4. Location of Cabinet Clips Figure Notes
    1. Control Cab inet 
    2. Port Cab inet or Dup lic ated  Control Cab inet
    3. Port Cab inet4. SRP Cab inet
    5. Cab inet Clip s 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Installation 
    1-12 Connect cables to the SRP 
    1
    Connect cables to the SRP
    The TN2301 survivab le remote switc h c irc uit p ac k is loc ated  in slot 7 of the SRP 
    c ab inet. Fib er op tic  transc eivers are attac hed  to the TN2301 c irc uit pac k. Fib er 
    c ab les are c onnec ted  from these transc eivers to the TX and  RX c onnec tors on 
    the rear of the c ab inet. 
    NOTE:
    Always c onnec t a fib er c ab le from a TX c onnec tor to an RX c onnec tor and  
    vic e versa. 
    Do not c onnec t the c ab les to the EPN until you reac h the ‘‘
    Re p la c e  EPN  
    c irc uit pac ks and  make c able c onnec tions’’ sec tion.
    Dep end ing  on the c ustomer’s c onfig uration, refer to one of the following  sec tions 
    for c onnec ting  fib er c ab les to the SRP:
    nConnec t SRP fib er c ab les for stand ard /hig h reliab ility
    nConnec t SRP fib er c ab les for c ritic al reliab ility
    Connect SRP fiber cables for standard/high 
    reliability
    1. Connec t the eq uip ment as shown in Fi g u re  1 - 5.
    2. Go to the ‘‘
    Connec t the SRP and  manag ement terminal’’ sec tion.
    Connect SRP fiber cables for critical reliability
    1. Connec t the eq uip ment as shown in .
    2. Go to the ‘‘
    Connec t the SRP and  manag ement terminal’’ sec tion. 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Installation 
    1-13 Connect cables to the SRP 
    1
    Figure 1-5. SRP fiber cables for standard/high reliability Figure Notes
    1. To EPN A
    2. To Port Network Connec tivity (PNC) A
    3. Fib er op tic  cab le4. SRP c ab inet
    5. B25A 25-p air c ab le
    6. Main Distribution Frame (MDF)
    cydfsdsa RPY 030998
    TX
    EPN B EPN APPN B PPN A
    TX TX TX
    RX RX RX RX
    3
    3 2
    1
    5 4
    6 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Installation 
    1-14 Connect cables to the SRP 
    1
    Figure 1-6. SRP fiber cables for critical reliability Figure Notes
    1. To EPN B
    2. To EPN A
    3. To Port Network Connec tivity (PNC) B
    4. To Port Network Connec tivity (PNC) A5. Fib er op tic  cab le
    6. SRP c ab inet
    7. B25A 25-p air c ab le
    8. Main Distribution Frame (MDF)
    TX
    EPN B EPN APPN B PPN A
    TX TX TX
    RX RX RX RX
    cydfaepn RPY 030998
    12
    34
    5
    5
    5
    5
    6
    7
    8 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Installation 
    1-15 Connect the SRP and management terminal 
    1
    Connect the SRP and management 
    terminal
    1. See Fig ure 1-7 for SRP and  manag ement terminal c onnec tions. 
    Figure 1-7. SRP and management terminal connections Figure Notes
    1. 14-inc h (35.5 c m) Y c able
    2. B25A 25-p air cab le
    3. To Main Distrib ution Frame (MDF)
    4. RS-232 c ab le5. RS-232 null modem c able (to 
    COM2 c onnec tor on management 
    terminal)
    6. 715 BCS-2 manag ement terminal
    7. SRP c ab inet
    scdfsre2 RPY 030398
    PI EITXEPN B EPN APPN B PPN ATX TX TX
    RX RX R X RXAU X
    DCE TERM
    S.R.
    SW IT CH
    13
    2
    45
    6
    7 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Installation 
    1-16 MDF connections 
    1
    MDF connections
    1. Punc h d own the following  wires at the MDF. See Tab le 1-8.
    Table 1-8. 110 block cross-connect pins
    SRP AuxEPN Aux
    Color
    1
    1. The following  wire c olors ap p ly to this tab le:
    W =  White, BL =  Blue, O =  Orang e, G =  Green, 
    BR =  Brown, BK =  Blac k, V =  Violet
    Cross-
    Connect 
    Pin 
    NumberCross-
    Connect 
    Pin 
    Number Color
    G-V 46 3 W-O
    SRP AuxSRP Switch
    ColorCross-
    Connect 
    Pin 
    NumberCross-
    Connect 
    Pin 
    Number Color
    W- O 3 4 6 G -V
    V- G 4 5 2 3 BK - O
    EPN AuxSRP Switch
    ColorCross-
    Connect 
    Pin 
    NumberCross-
    Connect 
    Pin 
    Number Color
    O-W 4 24 O-BK
    W- G 5 4 7 V-B R
    W-B R 7 4 8 BR-V
    V-BL 41 41 V-BL
    BL-V 42 42 BL-V
    V- G 4 5 4 3 V-O
    G-V 46 44 O-V 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Installation 
    1-17 Power up the SRP 
    1
    Power up the SRP
    1. Set the TN2301 switc h to the Restore (RSTR) p osition d uring  the 
    ad ministration to prevent the c ab inet from g oing  into the survive mod e.
    2. At the rear of the SRP, set the c irc uit b reaker to ON
    . This starts the system 
    initialization and  test.
    Administer the Release 7r and SRP
    !CAUTION:
    Do not save announc ements to the SRP translation c ard .
    NOTE:
    Ad ministering  the SRP may take several hours.
    NOTE:
    This d oc umentation assumes that the Release 7r manag ement 
    terminal and the SRP manag ement terminal are loc ated in the same 
    room. If this is not the c ase, make the ap p rop riate p rovisions.
    NOTE:
    An “ init”  log in is req uired  to p erform the following . Contac t the 
    reg ional CSA (Customer Software Assoc iate) to assig n the Offer 
    Categ ory option. Maintenanc e c ap abilities to initialize the system 
    and  ac c ess to either an internal or external mod em are the only 
    c ommand  op tions availab le until the Offer Categ ory op tion is set.
    NOTE:
    Not all ad ministration should  b e c op ied  direc tly (Examp le: c overag e 
    paths, abbreviated dial lists, and bridged appearances). These 
    ad ministration items may not b e valid  if the SRP g oes into survival 
    mode.
    NOTE:
    The following  are examples of the typ es of ad ministration that need  
    to b e ad d ed  to the SRP. Sinc e c onfig urations and  ad ministration 
    varies for every switc h, it is not p ossib le to list all of the 
    ad ministration that is needed  for your SRP. 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Installation 
    1-18 Administer the Release 7r and SRP 
    1
    Administration of the Release 7r
    1. Type display system-parameters maintenance 
    and  p ress En te r. Rec ord  
    the p rod uc t ID for later use.
    2. Choose an op tion and  enter the c ommand  on the Release 7r manag ement 
    terminal:
    nIf c hang ing  an existing  EPN to an SREPN, typ e change cabinet
     
      (number is the c abinet number of the SREPN) and 
    p ress 
    En t e r.
    nIf ad ding  a new EPN as an SREPN, type add cabinet
      (next 
    g ives you the next availab le numb er).
    3. In the Survivable Remote EPN?
     field , typ e y
    .
    4. In the Survivable Remote Processor ID
     field , ad d  the p rod uc t ID of 
    the SRP. The p rod uc t ID is loc ated  on the d isp lay system-p arameters 
    maintenanc e sc reen on the SRP manag ement terminal.
    5. Press 
    En t e r.
    Administration of the SRP
    The first step  is to administer the hard ware. The next step  is to ad minister the 
    software. Finally, ad minister any ind ivid ual features.
    Administering the hardware
    1. On the Release 7r manag ement terminal, typ e list cabinet
     and  press En t e r. 
    Id entify the p ort network of the SREPN. See Fig ure 1-8
    .
    Figure 1-8. List cabinet screen
    list cabinet                                                      SPE B
                                   CABINET REPORT
    No. Type Layout Room      Floor      Building    A     B     C     D     E
    1    PPN 5-car  CS_1      1          ABC_DE    PN 01 PN 01 PN 01 SN 01 SN 01
    2    EPN 5-car  CS_1      1          ABC_DE    PN 04 PN 04 PN 04 PN 16 PN 16
    3   sEPN 5-car  CS_1      1          ABC_DE    PN 05 PN 05 PN 05 SN 44 SN 44
    4    EPN 5-car  B-32      B          VWX_YZ    PN 06 PN 06 PN 06 SN 07 SN 07
    5    EPN 5-car  2-12      2          MNO_PQ    PN 08 PN 08 PN 08 SN 09 SN 09
    6    EPN 5-car  E-51      1          VWX_YZ    PN 10 PN 10 PN 10 SN 11 SN 11 
    						