    Have a look at the manual Lucent Technologies DEFINITY Enterprise Communications Server Release 8.2 Installation And Maintenance For Survivable Remote EPN Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Maintenance 
    2-35 Fault isolation procedures 
    2
    8. Connec t the transmit and  rec eive c ab les tog ether using  the fib er op tic  
    c oup ler (Comc od e 407643014, p rovided  in Maintenanc e Kit #30) to c reate 
    a loop  as shown in Fig ure 2-19
    .
    Figure 2-19. Manual loopback with fiber optic coupling
    9. Go to the front of the c ab inet and  inspec t the yellow LED.
    a. If the yellow LED flashes on at a rate of onc e p er sec ond , the 
    Exp ansion Interfac e or Switc h Nod e Interfac e c irc uit p ac k or 
    transc eiver should  b e rep lac ed .
    b . If the yellow LED flashes on at a rate of 5 times p er sec ond , the  
    Exp ansion Interfac e or Switc h Nod e Interfac e c irc uit p ac k or the 
    lig htwave transc eiver may need  rep lac ement. This c ond ition may 
    also b e d ue to a faulty system c loc k on the network c ontaining  the 
    Exp ansion Interfac e c irc uit pac k or in the switc h nod e c arrier 
    containing the SNI.
    c . If the yellow LED was b linking  b efore starting  this proc ed ure and  
    the yellow LED is not b linking now, this c irc uit p ac k (Exp ansion 
    Interfac e or Switc h Nod e Interfac e) and  the lig htwave transc eiver 
    are func tioning  p rop erly. Figure Notes
    1. Fib er op tic  coup ling  (Comcod e 407643014)
    RX
    RX TX
    TX
    cydfloop LJK 032398
    Back of cabinet
    1 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Maintenance 
    2-36 Fault isolation procedures 
    2
    10. Rep lac e faulty c omp onent(s) and rec onnec t the orig inal fib er. Be sure to 
    rec onnec t the fib ers p rop erly as noted  in Step  7 in this  ‘‘
    Manual loop bac k 
    p roc ed ure’’ section.
    11. Release the Exp ansion Interfac e c irc uit p ac k or Switc h Nod e Interfac e 
    c irc uit p ac k (release board UUCSS
    ).
    12. If p rob lems still exist after the Manual Loop b ac k Proc edure ind ic ates that 
    b oth Exp ansion Interfac e c irc uit p ac ks and  b oth lig htwave transc eivers 
    are healthy, verify that eac h op tic al fib er is c onnec ted  to a transmitter at 
    one end  and  a rec eiver at the other.
    DS1 interface cable pinout
    Table 2-11 shows the p in assig nments for the c ab le c onnec ting  the TN1654 DS1 
    CONV c irc uit p ac k to DS1 fac ilities. 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Maintenance 
    2-37 Fault isolation procedures 
    2
    Table 2-11. DS1 Interface Cable Connectors 
    Lead Desig.50-Pin 
    Connector 
    Pin #15-Pin 
    Connector 
    Color Pin Color
    Plug 04
    Fac ility D Line In LID 38 W-BL 11 W-BL
    Fac ility D Line In LID* 13 BL-W 03 BL-W
    Fac ility D Line Out LOD 39 W-O 09 W-O
    Fac ility D Line Out LOD* 14 O-W 01 O-W
    Plug 03
    Fac ility C Line In LIC 41 W-G 11 W-G
    Fac ility C Line In LIC* 16 G-W 03 G-W
    Fac ility C Line Out LOC 42 W-BR 09 W-BR
    Fac ility C Line Out LOC* 17 BR-W 01 BR-W
    Plug 02
    Fac ility B Line In LIB 44 W-S 11 W-S
    Fac ility B Line In LIB* 19 S-W 03 S-W
    Fac ility B Line Out LOB 45 R-BL 09 R-BL
    Fac ility B Line Out LOB* 20 BL-R 01 BL-R
    Plug 01
    Fac ility A Line In LIA 47 R-O 11 R-O
    Fac ility A Line In LIA* 22 O-R 03 O-R
    Fac ility A Line Out LOA 48 R-G 09 R-G
    Fac ility A Line Out LOA* 23 G-R 01 G-R
    Continued on next page 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Maintenance 
    2-38 110 block cross-connect pins 
    2
    110 block cross-connect pins
    Table 2-12. 110 block cross-connect pins
    SRP AuxEPN Aux
    Amphenol
    Pin 
    Number ColorCross-
    Connect 
    Pin 
    NumberLead 
    Designation
    1
    1. When the loop b etween Cust A (alarm) and  Cust Rtn (return) c loses, the SRSwitc h c onfigures the SRP into 
    Restore mod e, overriding  the fac ep late switc h setting . Closure of the c ustomer alarm relay is c ontrolled  b y 
    an SRP SAT c ommand whic h c loses the c ustomer alarm relay on the SRP p roc essor.
    Pwr Fail (-48V) is g round ed  when the TN2301 d etec ts that its -48V red und ant p ower is b ad .
    Cust A (alarm) - see ab ove.
    SRPresent is always g round ed , indic ating  to the TN775C (Maint.) that it is c onnec ted  in a SREPN.
    SRAc tive is g enerated  b y TN775C (Maint.) to d isc onnec t links from Release 7r to SRP in Survive mod e.
    -48V In/Rtn is inp ut and  return used by DC/DC c onverter for sup p lying red und ant p ower to the op tic al 
    transc eivers.
    SR Cntrl/Rtn, when ac tive, c onnec ts to the SR Cntrl Rtn signal on the TN775C (Maint.). Loop c losed  - 
    TN2301 goes into Survive mod e; loop  op en - TN2301 c annot c ome out of Survive mode without manual or 
    remote reset.
    Cross-
    Connect 
    Pin 
    Number ColorAmphenol
    Pin 
    Number
    23 G-V 46 Cust Rtn 3 W-O 27
    SRP AuxSRP Switch
    Amphenol
    Pin 
    Number ColorCross-
    Connect 
    Pin 
    NumberLead 
    DesignationCross-
    Connect 
    Pin 
    Number ColorAmphenol
    Pin 
    Number
    27 W-O 3 Pwr Fail (-48V) 46 G-V 23
    48 V-G 45 Cust A 23 BK-O 37
    EPN AuxSRP Switch
    Amphenol
    Pin 
    Number ColorCross-
    Connect 
    Pin 
    NumberLead 
    DesignationCross-
    Connect 
    Pin 
    Number ColorAmphenol
    Pin 
    Number
    02 O-W 4 Cust Rtn 24 O-BK 12
    28 W-G 5 SRPresent 47 V-BR 49
    29 W- B R 7 SRA c t i ve 4 8 BR- V 24
    46 V-BL 41 -48V Rtn 41 V-BL 46
    21 BL-V 42 -48V In 42 BL-V 21
    48 V-G 45
    2
    2. Momentarily short these two lead s on the EPN Aux to verify the d etec tion c irc uit on the TN2301 and  the 
    Maintenanc e (TN775C) c irc uit pac k wiring .
    SR Cntrl 43 V-O 47
    23 G-V 46
    2SR Cntrl Rtn 44 O-V 22 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Maintenance 
    2-39 Replacing the TN2301 circuit pack 
    2
    Fi g u re  2 - 2 0 shows the p inout and  c ross-c onnec tions for the SREPN.
    Figure 2-20. SREPN pinout and connections
    Replacing the TN2301 circuit pack
    !CAUTION:
    EPN service is interrupted until a replacement TN2301 is installed, powered 
    up , and  the EI links restored .
    Unseat the circuit pack
    1. Power d own the c ab inet b y turning  the p ower switc h off.
    2. Attac h an ESD strap  to your wrist. Figure Notes
    1. Switc hes to g round  after link failure 
    (ap p roximately 3 minutes)2. Momentary c losure after 3 minutes
    A-PNC
    B-PNC
    ABEI
    EI
    EISRP
    TN 2301
    SR Switch
    Latch
    Latch
    Reset
    TN 790
    processor
    R6R PPN47SRPresent (V-BR) (W-G) Aux_Alm_3
    48
    41
    42
    43
    44
    24
    46
    23SRActive (BR-V)
    -48v. Rt (BL-V)
    SRCnt1 (V-O)
    SRCntRt (O-V)
    CustRtn (O-BK)
    PwrFail (G-V) -48v. (V-BL)5
    7
    41
    42
    45
    46
    4
    3 (W-BR) Aux_Alm_4
    (V-BL) Grd
    (BL-V) -48v.
    -48v. (V-G) Ext_Alm
    (G-V) Ext_Alm_Rt
    (O-W) Grd
    (W-O) Aux_Alm_2
    Maintenance/Test
    TN775C EPN
    Aux
    EPNAux_Alm_2 (W-O)
    Y cable3
    46
    Ext_Alm_Rt (G-V)
    Ext_Alm (V-G) 45CustA (BK-O)
    SR Switch
    SRP Aux
    1
    2
    iodf001 EWS 111198 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Maintenance 
    2-40 Replacing the TN2301 circuit pack 
    2
    3. Push the latc h p in up ward  to unloc k the loc king  lever.
    4. Pull d own on the loc king  lever until the c irc uit p ac k d isc onnec ts from its 
    soc ket.
    5. Pull the c irc uit pac k just enoug h to b reak c ontac t with the bac kp lane 
    c onnec tor, b ut d o not remove it from the c ab inet.
    !CAUTION:
    Ensure that there is enoug h slac k d rawn from the extra fib er op tic  c ab ling  
    from the bottom p an of the c ab inet to c lear the c irc uit p ac k from the c ab inet 
    (ap p roximately 18 inc hes or 45.7 c m).
    Replace the circuit pack
    NOTE:
    If the same op tic al transc eivers c an b e reused , then the op tic al 
    c onnec tions to the transc eivers d o not have to b e removed. Just remove 
    the transc eivers from the old  c irc uit p ac k and  rec onnec t them to the 
    c orresp ond ing  c onnec tor p ositions on the rep lac ement c irc uit p ac k.
    1. Remove the fib er c onnec tions from eac h transc eiver, 
    taking  c are to note to 
    whic h transc eiver the c ab les g o and whic h is the transmit (TX) and  rec eive 
    (RX) c onnec tions for eac h transc eiver. 
    See Fig ure 2-2 1. 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Maintenance 
    2-41 Replacing the TN2301 circuit pack 
    2
    Figure 2-21. Transceivers attached to the TN2301 circuit pack
    2. Remove the b rac ket and then the transc eivers from the old  c irc uit p ac k 
    and  rep lac e them 
    in the id entic al positions on the new TN2301 c irc uit 
    pack.
    3. Rep lac e the b rac ket over the transc eivers to sec ure them to the b oard . 
    4. Feed  the fib er c ab les throug h the slot in the b ac k of the c irc uit p ac k and  
    rep lac e the fib er c onnec tions on eac h of the transc eivers. Figure Notes
    1. Connec tions from PPN A (lig htwave 
    transc eiver typ e must match other end )
    2. Connec tions to EPN A
    3. Connec tions from PPN B
    4. Connec tions to EPN B5. Lig htwave transc eiver (9823A is 
    always in this p osition)
    6. Fib er op tic  cab le p airs from the 
    rear p anel of the SRP c ab inet
    ckdf03fo KLC 010899
    R
    XT
    X
    R
    XT
    X
    1
    2
    3
    4
    5
    6
    PPN A
    EPN A
    PPN B
    EPN B 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Maintenance 
    2-42 Restore from remote location 
    2
    5. Insert the new c irc uit p ac k, feed ing  the fiber p atc h c ord s to the b ottom 
    p an of the c ab inet.
    Reseat the circuit pack
    1. Reseat the c irc uit pac k into the b ac kp lane c onnec tor.
    !WARNING:
    Ensure that the fib er c ab les are not b ent or p inc hed  b etween the 
    b ac k of the c irc uit p ac k and  the b ac kp lane of the c ab inet.
    2. Lift the loc king lever until the p in engag es.
    3. Power up  the c ab inet.
    Restore from remote location
    Th e  restore survivable-remote-link
     c ommand  rec onfig ures the EI link 
    c onnec tions to the Release 7r PPN just as if the fac ep late switc h was manually 
    set to the RSTR (Restore) p osition. 
    NOTE:
    The TN2301 fac ep late switc h p osition overrid es the restore 
    survivable-remote-link
     c ommand , should  the two c onflic t.
    Onc e the c onnec tion to the Release 7r is repaired :
    1. Dial in and  log  onto the SRP p roc essor.
    2. Typ e the restore survivable-remote-link
     c ommand , whic h c loses the 
    relay on the Proc essor c irc uit p ac k.
    3. Wait at least 3 minutes while the EPN g oes throug h its c old  restart and  
    then c hec k the status of the link c onnec tions with the status health
     
    command for 
    both
     the Release 7r and the SRP systems to d etermine 
    whether the link b etween the Release 7r and  the EPN is up  (Fi g u re  2 - 9
    ).
    When the c onnec tions are up  on b oth sid es (EPN and  Release 7r), the 
    system is suc c essfully rec onnec ted . 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Maintenance 
    2-43 Restore from remote location 
    2
    Th e  Tab le 2-13 d esc rib es the c ond itions in whic h the restore from a remote 
    loc ation is p ossib le.
    Table 2-13.TN2301 switch configuration based on input 
    Inputs to Control Logic Modes
    Remote 
    restoreSurvive 
    mode 
    requested
    1
    1. The EPN Maintenance (TN775C) c irc uit p ac k req uests switc hing  to Survive mod e.
    Switch 
    positionSRP 
    power State of SREPN
    Not activeNot activeAUTOGoodNormal mod e: EPN c onnected with Release 7r 
    PPN
    Not activeActiveAUTOGoodSurvive mode: EPN c onnec ted  to SRP 
    Not activeDoes not 
    matterTESTGoodSurvive mode: EPN c onnec ted  to SRP
    ActiveDoes not 
    matterTESTGoodSurvive mode: EPN c onnec ted  to SRP
    Not activeDoes not 
    matterRSTRGoodNormal mod e: EPN connec ted  to Release 7r 
    PPN
    Not activeDoes not 
    matterRSTRBadNormal mod e: EPN c onnected with Release 7r 
    PPN
    ActiveDoes not 
    matterAUTO or
    RSTRGoodNormal mod e: EPN connec ted  to Release 7r 
    PPN
    Continued on next page 
    						
    							DEFINITY® Enterprise Communications Server Release 7 Installation and 
    Maintenance for Survivable Remote EPN  555-233-102  Issue 2
    June 1999
    SREPN Maintenance 
    2-44 System links 
    2
    System links
    The state of a system link is d ep end ent on the state of the various hard ware 
    c omp onents that it travels over. The switc h maintains a list of hard ware 
    c omp onents over whic h the link travels, c alled  the hard ware p ath. 
    For eac h system link there is a c urrent and  a faulted  hard ware p ath as shown in 
    Tab le 2-14
    .
    1. Foc us attention on the 
    c urrent hardware path for p rob lems that d o not 
    involve a link that is d own.
    2. If the link is down, foc us on the 
    faulted  hard ware p ath. 
    3. If any alarms are p resent, follow the maintenanc e p roc ed ures for the 
    alarmed  c omp onents to c lear those alarms first.
    Table 2-14. Hardware path data for link repair
    Hardware 
    pathLink 
    statusHardware path 
    data present?Errors cleared at 
    recovery?
    CurrentUp Yes Yes
    Down No Yes
    Faulted
    1
    1. Path that the link traversed  when it last went d own.Up Yes
    Down Yes
    2
    2. The time at whic h the faulted p ath was last rec ord ed is p reserved and  is 
    ac c essib le throug h the status sys-link loc ation, whic h shows the state of 
    b oth the hardware paths (current and  faulted ) and the state of eac h of the 
    comp onents in that path, and the list sys-link command s.
    No 
    						