Galaxy 3 Series Programming Manual
55
05 = Entry Time
This parameter determines the entry time allowed to users when unsetting the system. The Entry Time is
programmable within the range 0–300 seconds; the default is 45. Assigning a value of  000 seconds sets the
Entry Time to infinity.
This parameter can be assigned a different value for each group.
NOTE:A Final zone assigned a 7 when programming the function will double the programmed Entry
Time for the group it is allocated to.
06 = System Reset
This...

Page 62

Galaxy 3 Series Programming Manual
56
Zones that are open at the end of the bell time must be omittable (Omit attribute enabled); the re-arm will omit
these zones. The complete zone circuit, including the tamper facility, is omitted. Refer to menu option 52 =
PROGRAM ZONES for details on enabling the zone omit attribute.
NOTE:If an open zone is not omittable, then the system will not re-arm, unless parameter 09 = Omit All is
set to 2.
09 = Omit All
This option determines if activated zones can be omitted...

Page 63

Galaxy 3 Series Programming Manual
57
13 = PA Delay
This parameter determines the delay between the activation of a PA Delay or PA Delay Silent zone and the
alarm sounding and signalling a PA via the communicator. The PA Delay is programmable within the range
1–60 seconds; the default is 60.
This parameter can be assigned a different value for each group.
14 = Key/SW Level
This parameter assigns a code type to zones programmed as Keyswitch.  The Keyswitch zone can be used
to reset system, tamper and PA...

Page 64

Galaxy 3 Series Programming Manual
58
17 = Restart
This parameter re-configures the system without the need to remove and reconnect the power. The system
displays a WARNING!!! ent=RESET SYSTEM, press the ent key to reconfigure the system. The keypad
display becomes blank for a few seconds, then displays the message Configuring Please Wait. When
configuration is complete the banner returns to the normal display (day mode). The Restart option configures
any modules that have been added to the system but...

Page 65

Galaxy 3 Series Programming Manual
59
22 = PA Reset
This option allows the engineer or the remote code to determine the code type that can reset the system
following a PA activation.  The default type is 3.6 — manager; the programmable range is:
•2.3 - 2.5 for the user
•3.6 for the manager
•3.7 for the engineer
This parameter can be assigned a different value for each group.
The panel only requests Engineer Level Reset if alarms have been signalled, via the Communication Module
and appropriate type reset...

Page 66

Galaxy 3 Series Programming Manual
60
26 = Forced
The Forced parameter enables or disables Menu option 14 = FORCED SET. If the parameter is set to 1 
(enabled) the user can force the system to set, automatically omitting any omittable zones that are open at the
time of setting. If the parameter is set to 0 (disabled), option 14 = FORCED SET is not available to the user;
the message Option not available is displayed.  The parameter defaults to 0 (disabled).
NOTE:It is recommended that Final, Entry and...

Page 67

Galaxy 3 Series Programming Manual
61
30 = Video
This parameter determines the number of activations that must occur on any of the zones programmed as
Video, in a single set period, before a full alarm occurs; there is no time limit on the period between
activations. The Video parameter is programmable within the range 1–9 activations; the default is 2.
activations.  The Video zones activation counter is reset when the system is unset.
NOTE:The activations of the Video zones are cumulative - the counter...

Page 68

Galaxy 3 Series Programming Manual
62
35 = Fail to Set
This parameter determines the period of time that a zone must remain open, following the start of the setting
procedure, before the Fail Set outputs activate. The programmable range is 0–999 seconds; the default is
360 .
NOTE:The Fail to Set countdown time begins as soon as the setting procedure is started.
NOTE:The Fail to Set time should be at a minimum 5 seconds longer than the Exit Time (option 51.04),
to allow for the setting period to expire....

Page 69

Galaxy 3 Series Programming Manual
63
40 = Datelock
Option not available
41 = Weekend Work
This parameter is used to enable or disable menu option 45.6 = TIMER CONTROL.Weekend Work.  If
the parameter is set to 1, the engineer can assign a Pattern Day and the user can authorize Weekend Work-
ing. If the parameter is set to 0 (disabled — default setting), the message Option not available is displayed
on selecting menu option 45.6, Weekend Work.
42 = PIN Change
This parameter defines the expiry period of...

Page 70

Galaxy 3 Series Programming Manual
64
46 = Zone resistance
RIOs rev 1.2 and Smart PSUs rev 0.7 and above allow the zones to be programmed, with different resistance
preset values for zone status activation. This feature allows selection of End Of Line or Double Balanced zone
resistance types. The on-board zones can also be modified using this feature.
The “EOL/Dbl. Bal.” resistance types are selectable from this option. The system default value is 1k Fault
(Double Balanced). There are eight preset...