Honeywell Galaxy 3 User Manual
Here you can view all the pages of manual Honeywell Galaxy 3 User Manual. The Honeywell manuals for Control panel are available online for free. You can easily download all the documents as PDF.
Page 61
Galaxy 3 Series Programming Manual 55 05 = Entry Time This parameter determines the entry time allowed to users when unsetting the system. The Entry Time is programmable within the range 0–300 seconds; the default is 45. Assigning a value of 000 seconds sets the Entry Time to infinity. This parameter can be assigned a different value for each group. NOTE:A Final zone assigned a 7 when programming the function will double the programmed Entry Time for the group it is allocated to. 06 = System Reset This...
Page 62
Galaxy 3 Series Programming Manual 56 Zones that are open at the end of the bell time must be omittable (Omit attribute enabled); the re-arm will omit these zones. The complete zone circuit, including the tamper facility, is omitted. Refer to menu option 52 = PROGRAM ZONES for details on enabling the zone omit attribute. NOTE:If an open zone is not omittable, then the system will not re-arm, unless parameter 09 = Omit All is set to 2. 09 = Omit All This option determines if activated zones can be omitted...
Page 63
Galaxy 3 Series Programming Manual 57 13 = PA Delay This parameter determines the delay between the activation of a PA Delay or PA Delay Silent zone and the alarm sounding and signalling a PA via the communicator. The PA Delay is programmable within the range 1–60 seconds; the default is 60. This parameter can be assigned a different value for each group. 14 = Key/SW Level This parameter assigns a code type to zones programmed as Keyswitch. The Keyswitch zone can be used to reset system, tamper and PA...
Page 64
Galaxy 3 Series Programming Manual 58 17 = Restart This parameter re-configures the system without the need to remove and reconnect the power. The system displays a WARNING!!! ent=RESET SYSTEM, press the ent key to reconfigure the system. The keypad display becomes blank for a few seconds, then displays the message Configuring Please Wait. When configuration is complete the banner returns to the normal display (day mode). The Restart option configures any modules that have been added to the system but...
Page 65
Galaxy 3 Series Programming Manual 59 22 = PA Reset This option allows the engineer or the remote code to determine the code type that can reset the system following a PA activation. The default type is 3.6 — manager; the programmable range is: •2.3 - 2.5 for the user •3.6 for the manager •3.7 for the engineer This parameter can be assigned a different value for each group. The panel only requests Engineer Level Reset if alarms have been signalled, via the Communication Module and appropriate type reset...
Page 66
Galaxy 3 Series Programming Manual 60 26 = Forced The Forced parameter enables or disables Menu option 14 = FORCED SET. If the parameter is set to 1 (enabled) the user can force the system to set, automatically omitting any omittable zones that are open at the time of setting. If the parameter is set to 0 (disabled), option 14 = FORCED SET is not available to the user; the message Option not available is displayed. The parameter defaults to 0 (disabled). NOTE:It is recommended that Final, Entry and...
Page 67
Galaxy 3 Series Programming Manual 61 30 = Video This parameter determines the number of activations that must occur on any of the zones programmed as Video, in a single set period, before a full alarm occurs; there is no time limit on the period between activations. The Video parameter is programmable within the range 1–9 activations; the default is 2. activations. The Video zones activation counter is reset when the system is unset. NOTE:The activations of the Video zones are cumulative - the counter...
Page 68
Galaxy 3 Series Programming Manual 62 35 = Fail to Set This parameter determines the period of time that a zone must remain open, following the start of the setting procedure, before the Fail Set outputs activate. The programmable range is 0–999 seconds; the default is 360 . NOTE:The Fail to Set countdown time begins as soon as the setting procedure is started. NOTE:The Fail to Set time should be at a minimum 5 seconds longer than the Exit Time (option 51.04), to allow for the setting period to expire....
Page 69
Galaxy 3 Series Programming Manual 63 40 = Datelock Option not available 41 = Weekend Work This parameter is used to enable or disable menu option 45.6 = TIMER CONTROL.Weekend Work. If the parameter is set to 1, the engineer can assign a Pattern Day and the user can authorize Weekend Work- ing. If the parameter is set to 0 (disabled — default setting), the message Option not available is displayed on selecting menu option 45.6, Weekend Work. 42 = PIN Change This parameter defines the expiry period of...
Page 70
Galaxy 3 Series Programming Manual 64 46 = Zone resistance RIOs rev 1.2 and Smart PSUs rev 0.7 and above allow the zones to be programmed, with different resistance preset values for zone status activation. This feature allows selection of End Of Line or Double Balanced zone resistance types. The on-board zones can also be modified using this feature. The “EOL/Dbl. Bal.” resistance types are selectable from this option. The system default value is 1k Fault (Double Balanced). There are eight preset...