Page 81

Galaxy 3 Series Programming Manual
75
Table 17.  Available Zone Functions
52 - Program Zones (cont’d)
Zone Function
 01 Final
 02 Exit
 03 Intruder
 04 24 Hours
 05 Security
 06 Dual
 07 Entry
 08 Push Set
 09 Keyswitch
10 Secure Final
11 P a rt F i na l
12 Part Entry
13 PA
14 PA Silent
15 PA Delay
16 PA Delay Silent
17 Link
18 Spare
19 Fire
20 Tamper
21 Bell Tamper
22 Beam Pair
23 Battery Low
24 Line Fail
25 AC Fail
26 LogZone Function
27 Remote Access
28 Video
29 Video Exit
30 Intruder Delay
31 Log...

Page 82

Galaxy 3 Series Programming Manual
76
01 Final
Zones programmed as Final initiate the unsetting procedure and terminate setting procedure; opening the
Final zone when the system or group is set starts the entry timer; opening and then closing the Final zone
during the exit procedure sets the system or assigned groups, providing all the zones are closed. The opening
(+) and closing (–) of Final zones during the setting and unsetting procedures are recorded in the event log.
Pressing the 7 key when...

Page 83

Galaxy 3 Series Programming Manual
77
06 Dual (Double Knock)
The operation of the Dual (Double Knock) function is identical to the Intruder function, with the exception
that an alarm condition is activated only when there have been two activations from any Dual  zones (assigned
to the same group) within a 20 minute period while the system is set.
07 Entry
This function initiates the unsetting procedure in the same way as a Final zone. However, during the setting
routine an Entry zone operates as an Exit...

Page 84

Galaxy 3 Series Programming Manual
78
 If the system is set, operating a Keyswitch immediately unsets the assigned groups; there is no entry time
countdown.
The Part attribute of the Keyswitch function defaults to 0 (disabled); the standard Keyswitch function full
sets the system. To part set the system using the Keyswitch, the Part attribute must be enabled.
NOTE:The operation of a Keyswitch zone can be extended to the setting and unsetting of multiple groups
by pressing the 7 key when assigning a group...

Page 85

Galaxy 3 Series Programming Manual
79
13 PA
The PA (Personal Attack) function is continuously operational. Activation of this zone type overrides the Bell
Delay parameter and causes an instant full alarm condition that requires to be reset with a code authorized for
PA Reset — refer to Option 51 – PARAMETERS, 22 = PA Reset; the Intruder outputs are not acti-
vated by PA zones.
NOTE:If a PA zone is open, it is indicated on the keypad whenever a valid code is entered. The group that
the open PA is assigned...

Page 86

Galaxy 3 Series Programming Manual
80
17 Link
This zone type has no operational function; it is designed to be used as a source of a link - refer to option 54 =
LINKS. The activation (+) and de-activation (–) of Link zones is recorded in the event log.
18 Spare
The Spare function allows any zones that are not being used to be ignored by the system; the resistance
readings from the circuit - including the tamper conditions - do not activate an alarm condition.
NOTE:It is recommended that all unused zones...

Page 87

Galaxy 3 Series Programming Manual
81
24 Line Fail
The Line Fail function is used to monitor the communication line that a remote signalling device is connected
to for communications failure.
When the system is in the unset state, the first activation of a Line Fail zone causes a local alarm and the
message COMMS FAILURE is displayed, subsequent Line Fail activations do not sound the local alarm;
the only indication is the keypad display.
When the system is set, activation of the Line Fail zone overrides...

Page 88

Galaxy 3 Series Programming Manual
82
30 Intruder Delay
The Intruder Delay function is identical to the Intruder function, with the exception that the full alarm activa-
tion can be delayed for up to 50 minutes (0–3000 seconds); this is determined by the Delay Alarm param-
eter (option 51.31). The Intruder Delay zone must remain open for the period of the Delay Alarm param-
eter; while the zone is open the Entry/Exit Horns activate to remind the user that the Delay Alarm is count-
ing down. Unsetting the...

Page 89

Galaxy 3 Series Programming Manual
83
35 = Exit Guard
The Exitguard function allows a zone to be used to omit other zones on the system.  This is useful for permit-
ting access via doors programmed as 24 Hours or Security.
The Exitguard zone must be the source of a link (refer to option 54 = LINKS); the destination of the
Exitguard link is either a zone address or an output type.
When opened, the Exitguard omits the zone entered as the link destination; an alarm is not activated if the
Exitguard zone is...

Page 90

Galaxy 3 Series Programming Manual
84
38 PA Unset
This PA Unset function is identical to the PA Silent function, with the exception that it is only operational
when the system is unset; the function is inactive when the group is set.
39 Keyswitch Reset
The Keyswitch Reset function allows alarms to be cancelled and the system to rearm without unsetting the
Galaxy. The type of reset authorization is determined by the Keyswitch Level (option 51.14). The type
required to reset Intruder, PA and Tamper alarms...