Honeywell Galaxy 3 User Manual
Here you can view all the pages of manual Honeywell Galaxy 3 User Manual. The Honeywell manuals for Control panel are available online for free. You can easily download all the documents as PDF.
Page 71
Galaxy 3 Series Programming Manual 65 51 - Parameters (cont’d) 47 = Set Confirm This parameter allows the system to emit a short double beep when the system/group has set. There are three options. 0 = Off No indication 1 = Alert on Set A double beep when the system has set Alert on Comm A double beep after a successful signal to the ARC that setting has occurred. 48 = Alarm Limits This parameter allows the user to program the maximum number of alarms, per group, which may be transmit- ted to an Alarm...
Page 72
Galaxy 3 Series Programming Manual 66 51 - Parameters (cont’d) 49 = Confirm Time This option is the maximum time between two separate zones for a confirmed alarm to be generated up to a maximum of 99 minutes, which is equivalent to the complete set period, with a default of 30 minutes. 50 = RF Bat Delay This option allows a warning to be given at the Galaxy panel if an RF low battery is detected. An additional option is given at the panel that allows a delay up to a maximum of 100 hours (default) before...
Page 73
Galaxy 3 Series Programming Manual 67 51 - Parameters (cont’d) 3 = Reduce Reset: This option allows user reset following an unconfirmed alarm. 0 = Off. Full system reset is required for any intruder alarm. 1 = On Unconfirmed. The system can be reset by user, if the alarm is unconfirmed. If the alarm is classed as confirmed, a full system reset will be required. 56 = Force Restore This option dictates when intruder restore signals are transmitted. 1 = Unset/Unconfirm: On unset or at the end of the...
Page 74
Galaxy 3 Series Programming Manual 68 65 = Reset levels This parameter determines the type of user that can reset specific fault types. The default values are shown in the table below. Table 13. User Type Reset Level 51 - Parameters (cont’d) 62 = Lockout This parameter prevents code guessing on the Galaxy system. 1=Lockout This parameter determines the number of invalid code attempts, which can be tried before keypad lockout occurs. Keypad lockout prevents any entry via all keypads associated to the...
Page 75
Galaxy 3 Series Programming Manual 69 51 - Parameters (cont’d) 66 = Min Pin Size This parameter determines the minimum size of each user code. This can be set from four to six digits. The default is five digits. 67 = Level Format This parameter determines the format used for user code authorization levels. 1 = EN.Galaxy (Default) Uses new EN Galaxy user types 1.0 to 3.8. 2 = Galaxy Uses standard Galaxy levels 0-8. 68 = Line Fail This parameter allows the programming of the period between the panel being...
Page 76
Galaxy 3 Series Programming Manual 70 Option 52 – Program Zones This option is used by the engineer to modify the programming of the zones on the system. The option also allows the attributes of the zone to be changed. The programmable options are shown in the table that follows: Table 14. Zone Attributes Selecting Zones On entering the option, the first zone on the system is displayed; the zone address, function and group as- signed are displayed on the top line, the descriptor is displayed on the...
Page 77
Galaxy 3 Series Programming Manual 71 1 = Function Entering the Function attribute displays the address and the current function of the selected zone along with the zone function reference number. The zone functions can be stepped through, forwards or backwards, using the A and B keys. Alternatively a zone function can be directly selected by entering the zone function reference number, for example, entering the 19 displays zone function 19 = FIRE. Once the required zone function is displayed, it is...
Page 78
Galaxy 3 Series Programming Manual 72 The A or B keys can be used to toggle the status of the Omit attribute - pressing 1 or 0 will also select the required status; press the ent key to accept the programming. 5 = Part If the Part attribute is set to 1 (enabled) the zone will be included in the setting procedure when one of the part setting options is used to set the system (13 = PART SET, 17 = INSTANT PART). The Part attribute defaults to 1 (enabled) for all zone functions except zones programmed as 09...
Page 79
Galaxy 3 Series Programming Manual 73 8 = Activity Mon. This attribute allows a zone to be checked for activity during a set time period or set/unset cycles. The options are: • 0 = None • 1 = Type1 • 2 = Type2 • 3 = Type3 • 4 = Type4 • 5 = Type5 • 6 = Type6 The default option is 0 = None. If the zone does not activate at least once within the programmed criteria a zone masked fault is indicated at the panel. The fault is logged as a masked event which indicates that the zone has been inactive for the...
Page 80
Galaxy 3 Series Programming Manual 74 52 - Program Zones (cont’d) e n o Zmr a l Ano i t p i r c s e D 1 0 0 0TT A B U Cwo l y r e t t a b t i n u l o r t n o C 2 0 0 0CA U Cli a f C A t i n u l o r t n o C 3 0 0 0RE P M A T D I Lre p m a t d i l t i n u l o r t n o C 4 0 0 0RE P M A T X U Anr u t e r r e p m a t t i n u l o r t n o C Table 16. Control Panel Alarms Use the A or B key to select the required group (A1–D8). When the end of a block is reached, the next block of eight groups is displayed; use...