Page 91

Galaxy 3 Series Programming Manual
85
52 - Program Zones (cont’d)
48-51 ATM-1, ATM-2, ATM-3 & ATM-4
There are four AT M (Automatic Teller Machine) zone types. These zone functions are continuously opera-
tional and are designed for the special maintenance and restocking requirements of ATM’s.
A single AT M zone type can be omitted for the duration of the period entered in the ATM Timeout param-
eter (option 51.39). The ATM Delay parameter (option 51.38) determines the delay before the selected
AT M zones...

Page 92

Galaxy 3 Series Programming Manual
86
Option 53 – Program Outputs
This option is used by the engineer to modify the programming of the outputs on the system. The option also
allows the attributes of the outputs to be changed. The programmable options are:
Table 19. Output Attributes
Selecting Outputs
On entering the option, the first output on the system is displayed; the output address, function and mode are
displayed on the top line, the polarity and assigned groups are displayed on the bottom line....

Page 93

Galaxy 3 Series Programming Manual
87
Keypad Outputs
The keypad outputs are fully programmable.  The address of the keypad output is the keypad address pre-
fixed with a star, for example the output for keypad 06 is 606.  The function of keypad outputs default to
Entry/Exit Horn.
The valid addresses of the keypads on each of the panels and the respective output addresses are indicated in
the following table:
Table 20. Addresses of Valid Keypad Outputs
It is possible to add additional keypads at any...

Page 94

Galaxy 3 Series Programming Manual
88
2 = Output Mode
Each output function defaults to a specific, logical output mode.  However, the output mode of each function
can be modified to meet special requirements: when reprogrammed, the new mode applies to all outputs
assigned to that function.  The output modes are:
1 = Latch: the output remains active until a valid code is entered.
2 = Reflex: the output follows the activity of the triggering event, for example, the Set output follows the
setting and...

Page 95

Galaxy 3 Series Programming Manual
89
Use the A or B key to select the required group (A1–D8). When the end of a block is reached, the next
block of eight groups is selected; press keys 1–8 to toggle the status of the relevant group in the current block
to the output; press the ent key to accept the selection.
Group Status
This group attribute offers an additional feature that makes the operation of the output conditional on the set
status of each of the system groups. An output assigned Group Status...

Page 96

Galaxy 3 Series Programming Manual
90
Output Functions
The following table shows all the outputs and the zone functions and conditions that result in their activation.
53 - Program Outputs (cont’d)
Key:
S = Activates when system is set? = Activation dependant on system programming
P = Activates when system is Part SetX= Activates during Exit Time
U = UnsetE= Activates during Entry Time
A = Activated in any conditionL= Switches output off if linked to destination output
-  = No effectT= Activates if zone...

Page 97

Galaxy 3 Series Programming Manual
91
53 - Program Outputs (cont’d)
Key:
S = Activates when system is set? = Activation dependant on system programming
P = Activates when system is Part SetX= Activates during Exit Time
U = UnsetE= Activates during Entry Time
A = Activated in any conditionL= Switches output off if linked to destination output
-  = No effectT= Activates if zone resistance is less than value for tamper s/c
O= Activates when zone is omitted    or greater than value for tamper o/c
Table 22B....

Page 98

Galaxy 3 Series Programming Manual
92
53 - Program Outputs (cont’d)
Key:
S = Activates when system is set? = Activation dependant on system programming
P = Activates when system is Part SetX= Activates during Exit Time
U = UnsetE= Activates during Entry Time
A = Activated in any conditionL= Switches output off if linked to destination output
-  = No effectT= Activates if zone resistance is less than value for tamper s/c
O= Activates when zone is omitted    or greater than value for tamper o/c
Table 22C....

Page 99

Galaxy 3 Series Programming Manual
93
53 - Program Outputs (cont’d)
Key:
S = Activates when system is set? = Activation dependant on system programming
P = Activates when system is Part SetX= Activates during Exit Time
U = UnsetE= Activates during Entry Time
A = Activated in any conditionL= Switches output off if linked to destination output
-  = No effectT= Activates if zone resistance is less than value for tamper s/c
O= Activates when zone is omitted    or greater than value for tamper o/c
Table 22D....

Page 100

Galaxy 3 Series Programming Manual
94
01 Bells (Latch)
The Bells output is activated on a full alarm event when the system is set. This output is subject to the Bell
Time, Bell Delay and No. Rearm parameters.
02 Strobe (Latch)
The Strobe output is activated on a full alarm event during the set state. This output is subject to the Bell
Delay. The Strobe output follows the Bell Time, but latches on after the last rearm.
03 PA (Latch)
The PA output is activated whenever any of the PA zone types activate....