Page 151
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-13 Figure 5-2: Select f irmware f ile 3. Once the new f irmware f ile has been selected, click Upg rade to continue. Figure 5-3: Upgrade f irmware selected f ile 4. Fill in the device IP address, serial nu mber, and order code as needed. (The order code is not required for f irmware versions below 1.70).
Page 152
5-14F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE Figure 5-4: Relay serial number 5. If the relay is not an enhanced model or one with control functionality, click Upgrade Firmware to continue the process (see the following f igure). At this point, proceeding with the upgrade erases all data stored in the equipment, including the calibration settings in firmware versions below 1.50. It is necessary to save all settings...
Page 153
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-15 Click Yes to continue. A message is displayed indicating that a local network reboot is necessary (see following figure). Proceed as follows: • In the Windows Control Panel ( Start > Control Panel), navigate to Network Connection > Local Network . Right-click and select Disable. Conf irm that the Local Network status is now Disabled. Restart the local network in the same...
Page 154
5-16F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE Figure 5-5: Advisory for local network reboot 6. When upgrading models with Enhanced protection or contr ol functionality (see model selection), the upgrade program requires a password to continue (as shown). Figure 5-6: Relay upgrade password
Page 155
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-17 For a model with specialized functionality and a password requirement, contact GE Multilin. The following parameters must be clearly indicated in the order: • Unit serial number • Current model option (befor e memory upgrade) • Desired model option (after memory upgrade) • Unit MAC address (available in the identif ication label) 7. Once the upgrade parameters have been...
Page 156
5-18F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE Figure 5-7: Firmware f ile selection 9. A voltage range selection window appears (see following f igu r e). This voltage range is closely related to the serial number of the relay. For relays manufactured with f irmware version 5.70 or higher (from May 2015 onwards), the EnerVista 650 Setup program automatically selects the approp riate voltage range for the unit based on...
Page 157
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-19 Figure 5-9: Initiate upgrade During the upgrade process, the program displays the files that are being upgraded. Figure 5-10: Firmware f ile selection
Page 158
5-20F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE 12. When the f ile transfer is f inished, a message is displayed indicating that it is necessary to wait before resetting the unit , in order to start working with the new f irmware version in the relay (f igure below). 13. When the whole process has f inished a message is displa yed a sking to switch the F650 on and off (f igure below). Figure 5-11: Firmware f ile...
Page 159
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00. GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-21 2. Connect a RS-232cable to the front port relay and connect an Ethernet cable to the rear Ethernet port (crossover cable for back-to-back connection and straight-through Ethernet cable for hub or switch) . 3. Save all calibration settings to a f ile. 4. Save all data from the relay (settings, oscillography, events). 5. In the EnerVista 650 Setup software, select C...
Page 160
5-22F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.2 FIRMWARE UPGRADE VERSION 7.00 OR ABOVE CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE 5.2 Firmware upgrade version 7.00 or above This section explains how to upgrade the F650 firmware code for version V7.00 or higher. BOOT CODE RELEASE NOTES It is mandatory to maintain version compatibility between fi rmware and boot code in the upgrade procedure, otherwise the relay will not start after upgrading. BEFORE PERFORMING THE UPGRADE PROCEDURE CHECK THAT BOOT AND...