CHAPTER 6:  COMMISSIONING6.17 RECLOSER (79)
GEK-113000-AFF650 DIGITAL BAY CONTROLLER 6-23
6.17.2  Recloser status
BLOCK
Activate the block input and verify that the recloser is in BLOCK status.
Close the breaker and wait for 5 seconds.
Command a trip and verify that the breaker opens but there is no reclose.
INHIBITION BY RECLOSING CONDITIONS
Close the breaker and wait for 5 seconds.
Command a trip, verify that the breaker opens and wait for the first shot.
Activate the inhibition input and command a new...

Page 192

6-24F650 DIGITAL BAY CONTROLLER GEK-113000-AF
6.18 THERMAL IMAGE ELEMENT (49) CHAPTER 6:  COMMISSIONING
6.18   Thermal image element (49)
Disable all protection elements except for Thermal Model (49).
Set the pickup level to 2 A.
Set the time constant t1 to 3 minutes and t2 to one time t1.
Apply currents of 2, 5, and 10 times the tap and ensure that the operation times are within the range described on the 
following table:
After each measuring, the thermal element must be reset to zero in order to start...

Page 193

GEK-113000-AFF650 DIGITAL BAY CONTROLLER 7-1
F650 Digital Bay Controller
Chapter 7:  Frequently asked questions
GE
Grid Solutions
FREQUENTLY ASKED QUESTIONS
7.1  Communications
Q1. Does the F650 support DNP and ModBus over the Ethernet port?
A1. F650 units support both protocol
 s over both the asynchronous serial ports and the Ethernet LAN synchronous port 
using TCP/IP and UDP/IP la yers over the Ethernet. 
Q2. Does this equipment support dual IP access?
A2. Yes, it supports two independent IP...

Page 194

7-2F650 DIGITAL BAY CONTROLLER GEK-113000-AF
7.1 COMMUNICATIONS CHAPTER 7:  FREQUENTLY ASKED QUESTIONS
Q7. How many different communication Ethernet sessions can be opened through the LAN port?
A7. ModBus TCP/IP:4 sockets 
DNP TCP/IP:3 sessions (from version 1.72 on) 
Q8. May I use the cooper 10/100 BaseTX connection included in the basic model with all protocols?
A8. Yes, it may be used with all protocols. In noisy substation  en
 vironments and/or long distances, it is recommended to use 
f iber optic...

Page 195

CHAPTER 7:  FREQUENTLY ASKED QUESTIONS7.2 PROTECTION
GEK-113000-AFF650 DIGITAL BAY CONTROLLER 7-3
A17. The cable has some advantages that the f iber does not have, and it is that the signal attenuation in short and medium 
distances, is worthless and this is truth for low and high frequency signals. By the contrary, the light in one f iber optic is 
highly attenuated, being much worse in case of high frequenc ies than in the low ones. The 10-BASE-FL f iber transmission 
is performed in a wavelength of...

Page 196

7-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF
7.3 CONTROL & HMI CHAPTER 7:  FREQUENTLY ASKED QUESTIONS
7.3  Control & HMI
Q1. What is the difference between Get/Send info from/to relay and Upload/Download info files to/from relay?
A1. Get/Send are used for settings and configuration storage  that al
 though both are in a unique file, are sent separately 
in two times. Upload/Download are used for projec t or PLC files group storage. These files are the 
setting_configuration file source. To operate, the...

Page 197

CHAPTER 7:  FREQUENTLY ASKED QUESTIONS7.4 RELAY CONFIGURATION
GEK-113000-AFF650 DIGITAL BAY CONTROLLER 7-5
7.4  Relay conf iguration
Q1. Does the Service contact on the Power Supply board cover all possible failures or do I have to create an 
output on the I/O board that includes all the internal errors I can access in the logic?
A1. The power supply ready contact only monitor hardware failur es i
 n the power supply, to monitor the internal error of 
the unit it is necessary to configure a virtual...

Page 198

7-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF
7.4 RELAY CONFIGURATION CHAPTER 7:  FREQUENTLY ASKED QUESTIONS 

Page 199

GEK-113000-AFF650 DIGITAL BAY CONTROLLER 8-1
F650 Digital Bay Controller
Chapter 8:  F650 troubleshooting guide
GE
Grid Solutions
F650 TROUBLESHOOTING GUIDE
8.1  Symptoms and recommended actions
F650 units have been designed and verified using the most advanced and reliable equipment. Mounting and testing 
automation ensure a high consistency of the final product.  Before sending a unit back to the factory, we strongly 
suggest you follow the recommendations below. These actions may solve the problem,...

Page 200

8-2F650 DIGITAL BAY CONTROLLER GEK-113000-AF
8.1 SYMPTOMS AND RECOMMENDED ACTIONS CHAPTER 8:  F650 TROUBLESHOOTING GUIDE
Ge n e r a l When feeding the 
unit
, no indicator is lit 
up -Insufficient power supply
- Wrong versions
-Fuse failure
- Loose fuse
-Incorrect wiring -Verify the voltage level using a 
multi
meter in the power supply 
terminals, and check that it is within 
the model range
-Check relay and ENERVISTA 650 
Setup v

ersions are the same
-Remove power supply, dismount the 
pow
 er supply...
Start reading GE F650 Manual
All GE manuals