CHAPTER 6:  COMMISSIONING 6.3 GENERAL CONSIDERATIONS, POWER SUPPLY NETWORK
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 6-3
6.3  General considerations, power supply network
All devices running on AC current are affected by frequency. As a non-sine wave is the result of a fundamental wave plus a 
series of harmonics from this fundamental wave, we can infe r that devices running on AC current are influenced by the 
applied waveform.
For a correct testing of relays running on AC current, it is fundamental to...

Page 172

6-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF
6.4 ISOLATION TESTS CHAPTER 6:  COMMISSIONING
6.4  Isolation tests
During all tests, the screw located on the rear of the relay must be grounded.
For verifying isolation, independent groups are created, and voltage is applied as follows: 
2200 RMS volts will be applied progressively among all terminals in a group, short-circuited between them and the 
case, during one second.
2200 RMS volts will be applied progressively between groups, during one second....

Page 173

CHAPTER 6:  COMMISSIONING6.5 INDICATORS
GEK-113000-AFF650 DIGITAL BAY CONTROLLER 6-5
6.5  Indicators
Feed the relay and verify that when commanding a LED reset operation, all LED indicators light up and they are turned off 
when pressing the ESC key for more than 3 seconds.
6.6  Power supply testing
Feed the relay with the minimum and maximum voltage. For each voltage value, verify that the alarm relay is activated 
when there is voltage, and it is deactivated when there is no feed. If the power supply...

Page 174

6-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF
6.8 VERIFICATION OF MEASUREMENT CHAPTER 6:  COMMISSIONING
6.8  Verif ication of measurement
Set the relay as follows
NOTE:
ALL ANGLES INDICATED ARE LAGGING ANGLES 
ALL VALUES OBTAINED IN THIS TEST MUST BE  THE ONES CORRESPONDING TO THE PHASOR ONES
6.8.1  Voltages
Apply the following voltage and frequency values to the relay:
Verify that the relay measures the values with an error of ±1 % of the applied value from 10V to 208V.
6.8.2  Phase currents
Apply the...

Page 175

CHAPTER 6:  COMMISSIONING6.8 VERIFICATION OF MEASUREMENT
GEK-113000-AFF650 DIGITAL BAY CONTROLLER 6-7
Percent of Load-to-Trip
The relevant actual values displays are shown below:
Actual > Metering > Primary Values > Current > % of Load-to-trip
Note Percent of load-to-trip is calculated from the phase with the highest current reading. It is the ratio of this current to 
the lowest pickup setting among the phase time and instantaneous overcurrent protection features. If all of these features 
are disabled,...

Page 176

6-8F650 DIGITAL BAY CONTROLLER GEK-113000-AF
6.8 VERIFICATION OF MEASUREMENT CHAPTER 6:  COMMISSIONING
6.8.4  Frequency
Frequency measure on channel VII (terminals A7-A8):
Apply 50 Vac at 50 Hz on channel VI I. Maximum admissible error:± 10 mHz.
Apply 50 Vac at 60 Hz on channel VII. Maximum admissible error: ± 12 mHz.
Frequency measure on channel Vx (terminals A11-A12):
Apply 50 Vac at 50 Hz on channel Vx . Maximum admissible error:± 10 mHz.
Apply 50 Vac at 60 Hz on channel Vx. Maximum admissible error:...

Page 177

CHAPTER 6:  COMMISSIONING6.9 INPUTS AND OUTPUTS
GEK-113000-AFF650 DIGITAL BAY CONTROLLER 6-9
6.9  Inputs and outputs
During all tests, the screw on the rear of the relay must be grounded.
6.9.1  Digital inputs
During this test, the user determines the activation/deactivation points for every input in the relay for the set voltage value  
of 30 Volts.
Verify that the error does not exceed ± 10% (+10% on activation, -10% on deactivation).
Default board settings for the input test can be modified in...

Page 178

6-10F650 DIGITAL BAY CONTROLLER GEK-113000-AF
6.9 INPUTS AND OUTPUTS CHAPTER 6:  COMMISSIONING
6.9.2  Contact outputs
The correct activation of every output to be verified.
For every output, activation command of a single contact must be given, and then verify that only that contact is 
activated. Go to EnerVista 650 Setup Software (Setpoint > Inputs/Outputs > Force Outputs).
For switched contacts, the change of state of both contacts shall be verified.
6.9.3  Circuit continuity supervision inputs...

Page 179

CHAPTER 6:  COMMISSIONING6.10 CONNECTIONS FOR TESTING PROTECTION ELEMENTS
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 6-11
6.10   Connections for testing protection elements
Connect current sources to the relay according to the wiring diagram. Current and voltage input terminals are as follows:
PhaseConnections
Current
IAB1-B2
IB B3-B4
IC B5-B6
IG B9-B10
ISG
B11-B12
Voltage
VI A5-A6
VII A7-A8
VIII A9-A10
VX A11-A12 

Page 180

6-12F650 DIGITAL BAY CONTROLLER GEK-113000-AF
6.11 INSTANTANEOUS OVERCURRENT (50PH, 50PL, 50N, 50G, 50 SG) CHAPTER 6:  COMMISSIONING
6.11   Instantaneous overcurrent (50PH, 50PL, 50N, 50G, 50SG)
Set the relay to trip for the protection element being tested . Configure any of the outputs to be enabled only by the 
protection element being tested.
Apply 0.9 times the Pickup current and check that the relay does not trip.
Gradually increase the current value and verify that the relay operates between 1 and...