Page 121

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.2 HUMAN-MACHINE INTERFACE (HMI)
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-59
Pressing the up-down key or rotating the shuttle key to the left (L) or right (R) the user can access all the Metering values in 
the screen. 
3.2.7.3  All events screen
This screen shows all events that have been produced in the relay. The top of the screen shows its name (All Events), and 
the relative and total number of events contained in the screen.
All Events (1/479) or...

Page 122

3-60F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.2 HUMAN-MACHINE INTERFACE (HMI)CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
Esc: Prev.
Pressing the ESC key, the user returns to the previous screen (Metering screen) 
Intro: Menu.
Pressing the enter/shuttle key, the user accesses the Events menu that offers the following options at the bottom of the 
screen: 
nextprevreloaddetailsAt
To access the different options in the snapshot events graphic menu the user must move the cursor from up to down or...

Page 123

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.2 HUMAN-MACHINE INTERFACE (HMI)
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-61
Intro: Meters.
To access the metering values in the moment of the event, the user must press the enter/shuttle key. A new metering 
screen is displayed, containing the primary metering values in the snapshot event, such as:
Once inside the Metering screen, a new legend is shown for each event (Intro or ESC: Prev. U-D (L-R: Scroll); press ESC 
or the shuttle key to return to...

Page 124

3-62F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.2 HUMAN-MACHINE INTERFACE (HMI)CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
3.2.7.5  Alarms panel
Alarms panel can be viewed in all F650 models using communication software En erVista 650 Setup, however, only models 
with graphic display allow access to the alarms panel from the HMI.
First line shows the relative and total number of alarms existing  in that screen. The relative number refers to the alarm on 
which the cursor is located, and the total...

Page 125

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.2 HUMAN-MACHINE INTERFACE (HMI)
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-63

This option acknowledges all alarms. Alarm acknowledgement through the graphic HMI is considered as through 
communication port COM2, as it is considered to be Local in both cases.
When an alarm has been acknowledged, a selection mark appears to the right of its status. Inactive alarms disappear 
from the screen once they are acknowledged.
3.2.7.6  Input/output monitoring...

Page 126

3-64F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.2 HUMAN-MACHINE INTERFACE (HMI)CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
Figure 3-38: Input/output viewing screen

This option brings the system back to the one-line diagram.

This option shows the real status of all inputs and outputs in the selected board. Dependin g on the type of board, with 
or without supervision, the screen varies depending on the board characteristics.
The first line of this screen shows the slot where the board is located,...

Page 127

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.2 HUMAN-MACHINE INTERFACE (HMI)
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-65
Esc: Exit Text.
The ESC option returns to the general I/O board menu.
Enter: Chg Input.
Pressing the enter/shuttle key on the blinking input, this input is activated in emulation mode.
Note: input emulation can only be executed through the TEST INPUT tool on the graphic display.

This option allows testing the output activation in emulation mode. The displayed screen is...

Page 128

3-66F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.3 WEB SERVERCHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
3.3   Web server
3.3.1  Home
The web server in the F650 can be accessed running the  Windows explorer, and typing http://xxx.xxx.xx.xxx, where 
xxx.xxx.xxx.xxx is the relay IP addre ss, which must be configured in Setpoint > Product Setup > Communication Settings 
> Ethernet. 
The main screen of the F650 web server shows the different monitoring possibilities for snapshot events, events, alarms,...

Page 129

CHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES 3.3 WEB SERVER
GEK-113000-AF F650 DIGITAL BAY CONTROLLER 3-67
3.3.2  Snapshot events
The Snapshot events screen shows all Snapshot events produced in the relay. This screen is refreshed automatically every 
minute.
The information provided in this screen includes: first, the relative event index, the lowest index corresponding to the most 
recent event; next, the event text that shows the reason for th e event, its status, active (ON) or inactive (OFF),...

Page 130

3-68F650 DIGITAL BAY CONTROLLER GEK-113000-AF
3.3 WEB SERVERCHAPTER 3:  INTERFACES, SETTINGS & ACTUAL VALUES
3.3.3  Control events
The control events screen provides access to all events that ha ve been configured in the Control Events screen inside the 
Relay Configuration menu of EnerVista 650 Setup.
Figure 3-41: Control events screen
Unlike the case of Snapshot events, in this screen the highest  index corresponds to the most recent event. The information 
provided is the control event index, the text...