Page 201

CHAPTER 8:  F650 TROUBLESHOOTING GUIDE8.1 SYMPTOMS AND RECOMMENDED ACTIONS
GEK-113000-AFF650 DIGITAL BAY CONTROLLER 8-3
CategorySymptomPossible causeRecommended action
Communications Cannot see properly 
the web 

server in F650 
with Windows XP. 
Some windows are in 
gr
 ey with a red cross 
mark. 1.- Disabled Java options in Advanced 
In

ternet Explorer properties or high 
level of security
2.- Nor Java Virtual Machine installed. 1.1- Go to Advanced in Internet 
options
for Internet explorer and...

Page 202

8-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF
8.1 SYMPTOMS AND RECOMMENDED ACTIONS CHAPTER 8:  F650 TROUBLESHOOTING GUIDE
CategorySymptomPossible causeRecommended action
Bootware The relay gets stuck at 
“Send

ing f ile 
imagen_kernel...” -The Ethernet connection does not 
work pr
operly. Serial communications work properly 
and the fla
sh memory has been 
erased but Ethernet communication 
does not work properly, check:
•   R
J45 cable used (crossover cable for 
back-to-back connection and straight...

Page 203

CHAPTER 8:  F650 TROUBLESHOOTING GUIDE8.1 SYMPTOMS AND RECOMMENDED ACTIONS
GEK-113000-AFF650 DIGITAL BAY CONTROLLER 8-5
FirmwareIt is not possible to to 
upgra
de models 
without IEC 61850 to 
models with IEC 61850 
automatically - IEC 61850 upgrade from standard 
mo
dels is password protected. • 
To upgrade from a standard model 
to a 6 model, ask the factory for an 
upgrade package, depending on the 
hardware the existing unit has. If it is 
hardware 00 a hardware and 
firmware change is required...

Page 204

8-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF
8.1 SYMPTOMS AND RECOMMENDED ACTIONS CHAPTER 8:  F650 TROUBLESHOOTING GUIDE 

Page 205

GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-1
F650 Digital Bay Controller
Appendix A:  
GE
Grid Solutions
LOGIC OPERANDS
A.1  Operands - F650 - model FX - GX
OPERANDS - F650 - MODEL FX - GX
Internal System Status
autocheck internal states (critical)
DSP Internal States (Critical to metering and 
pr

otection) DSP COMM ERROR
DSP Communication Error: (0) Rignt communications 
between DSP and ma

in processor; (1) Communication 
Error between DSP and main processor
MAGNETIC MODULE 
ERR
 OR Magnetic Module...

Page 206

A-2F650 DIGITAL BAY CONTROLLER GEK-113000-AF
A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A:  
IEC61850 Internal StatesICD STATUSUNKNOWN: when the relay has not the IEC61850 
pr

otocol in the relay model the ICD status is unknow to 
the unit
ICD ERROR: There is an error in the ICD file and the 
re
 lay ICD is not operative. To solve this issue it is 
necessary to send a correct ICD to the relay using the 
IEC61850 configurator tool. When the ICD error is raised 
the IEC 61850 will not be operative (the...

Page 207

APPENDIX A:  A.1 OPERANDS - F650 - MODEL FX - GX
GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-3
Note: It is advisable to use the critical alarms to raise an event or to light a warning LED for maintenance purposes. See 
the example below, the Board X Status depends on the relay model.
Figure A–1: Protection Alarm Signal
Conf igurable Logic Outputs (512 elements) VIRTUAL OUTPUT 000
Configurable logic output 000
VIRTUAL OUTPUT 001 Configurable logic output 001
... ...
VIRTUAL OUTPUT 511 Configurable logic...

Page 208

A-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF
A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A:  
Control Event Bits (128 elements)CONTROL EVENT 1
Control Event 1 Activation Bit
CONTROL EVENT 2 Control Event 2 Activation Bit
... ...
CONTROL EVENT 128 Control Event 128 Activation Bit
Latched Virtual Inputs (32 elements) LATCHED VIRT IP 1
Latched virtual input 1
LATCHED VIRT IP 2 Latched virtual input 2
... ...
LATCHED VIRT IP 32 Latched virtual input 32
Self Reset Virtual Inputs (32 elements) SELF-RST VIRT...

Page 209

APPENDIX A:  A.1 OPERANDS - F650 - MODEL FX - GX
GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-5
Contact Inputs Type 5 Board (Digital Values)CONT IP_X_CC1
Input 1 (CC1) in Board X
CONT IP_X_CC2 Input 2 (CC2) in Board X
... ...
CONT IP_X_CC16 Input 16 (CC16) in Board X
Contact Inputs Type 5 Board (Analog Values) ANALOG_INP_X_01
Analog Input 01 in Board X
ANALOG_INP_X_02 Analog Input 02 in Board X
ANALOG_INP_X_03 Analog Input 03 in Board X
... ...
ANALOG_INP_X_08 Analog Input 08 in Board X
Contact Outputs...

Page 210

A-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF
A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A:  
Switchgear states (16 elements)SWITCH 1 OPEN
switchgear 1 open
SWITCH 1 CLOSED switchgear 1 closed
SWITCH 1 00_ERROR Error 00 switchgear 1 (contact A = 0, contact B = 0)
SWITCH 1 11_ERROR Error 11 switchgear 1 (contact A = 1, contact B = 1)
SWITCH 2 OPEN Switchgear 2 open
SWITCH 2 CLOSED Switchgear 2 closed
SWITCH 2 00_ERROR Error 00 switchgear 2 (contact A = 0, contact B = 0)
SWITCH 2 11_ERROR Error 11...