Page 201
CHAPTER 8: F650 TROUBLESHOOTING GUIDE8.1 SYMPTOMS AND RECOMMENDED ACTIONS GEK-113000-AFF650 DIGITAL BAY CONTROLLER 8-3 CategorySymptomPossible causeRecommended action Communications Cannot see properly the web server in F650 with Windows XP. Some windows are in gr ey with a red cross mark. 1.- Disabled Java options in Advanced In ternet Explorer properties or high level of security 2.- Nor Java Virtual Machine installed. 1.1- Go to Advanced in Internet options for Internet explorer and...
Page 202
8-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF 8.1 SYMPTOMS AND RECOMMENDED ACTIONS CHAPTER 8: F650 TROUBLESHOOTING GUIDE CategorySymptomPossible causeRecommended action Bootware The relay gets stuck at “Send ing f ile imagen_kernel...” -The Ethernet connection does not work pr operly. Serial communications work properly and the fla sh memory has been erased but Ethernet communication does not work properly, check: • R J45 cable used (crossover cable for back-to-back connection and straight...
Page 203
CHAPTER 8: F650 TROUBLESHOOTING GUIDE8.1 SYMPTOMS AND RECOMMENDED ACTIONS GEK-113000-AFF650 DIGITAL BAY CONTROLLER 8-5 FirmwareIt is not possible to to upgra de models without IEC 61850 to models with IEC 61850 automatically - IEC 61850 upgrade from standard mo dels is password protected. • To upgrade from a standard model to a 6 model, ask the factory for an upgrade package, depending on the hardware the existing unit has. If it is hardware 00 a hardware and firmware change is required...
Page 204
8-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF 8.1 SYMPTOMS AND RECOMMENDED ACTIONS CHAPTER 8: F650 TROUBLESHOOTING GUIDE
Page 205
GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-1 F650 Digital Bay Controller Appendix A: GE Grid Solutions LOGIC OPERANDS A.1 Operands - F650 - model FX - GX OPERANDS - F650 - MODEL FX - GX Internal System Status autocheck internal states (critical) DSP Internal States (Critical to metering and pr otection) DSP COMM ERROR DSP Communication Error: (0) Rignt communications between DSP and ma in processor; (1) Communication Error between DSP and main processor MAGNETIC MODULE ERR OR Magnetic Module...
Page 206
A-2F650 DIGITAL BAY CONTROLLER GEK-113000-AF A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A: IEC61850 Internal StatesICD STATUSUNKNOWN: when the relay has not the IEC61850 pr otocol in the relay model the ICD status is unknow to the unit ICD ERROR: There is an error in the ICD file and the re lay ICD is not operative. To solve this issue it is necessary to send a correct ICD to the relay using the IEC61850 configurator tool. When the ICD error is raised the IEC 61850 will not be operative (the...
Page 207
APPENDIX A: A.1 OPERANDS - F650 - MODEL FX - GX GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-3 Note: It is advisable to use the critical alarms to raise an event or to light a warning LED for maintenance purposes. See the example below, the Board X Status depends on the relay model. Figure A–1: Protection Alarm Signal Conf igurable Logic Outputs (512 elements) VIRTUAL OUTPUT 000 Configurable logic output 000 VIRTUAL OUTPUT 001 Configurable logic output 001 ... ... VIRTUAL OUTPUT 511 Configurable logic...
Page 208
A-4F650 DIGITAL BAY CONTROLLER GEK-113000-AF A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A: Control Event Bits (128 elements)CONTROL EVENT 1 Control Event 1 Activation Bit CONTROL EVENT 2 Control Event 2 Activation Bit ... ... CONTROL EVENT 128 Control Event 128 Activation Bit Latched Virtual Inputs (32 elements) LATCHED VIRT IP 1 Latched virtual input 1 LATCHED VIRT IP 2 Latched virtual input 2 ... ... LATCHED VIRT IP 32 Latched virtual input 32 Self Reset Virtual Inputs (32 elements) SELF-RST VIRT...
Page 209
APPENDIX A: A.1 OPERANDS - F650 - MODEL FX - GX GEK-113000-AFF650 DIGITAL BAY CONTROLLER A-5 Contact Inputs Type 5 Board (Digital Values)CONT IP_X_CC1 Input 1 (CC1) in Board X CONT IP_X_CC2 Input 2 (CC2) in Board X ... ... CONT IP_X_CC16 Input 16 (CC16) in Board X Contact Inputs Type 5 Board (Analog Values) ANALOG_INP_X_01 Analog Input 01 in Board X ANALOG_INP_X_02 Analog Input 02 in Board X ANALOG_INP_X_03 Analog Input 03 in Board X ... ... ANALOG_INP_X_08 Analog Input 08 in Board X Contact Outputs...
Page 210
A-6F650 DIGITAL BAY CONTROLLER GEK-113000-AF A.1 OPERANDS - F650 - MODEL FX - GX APPENDIX A: Switchgear states (16 elements)SWITCH 1 OPEN switchgear 1 open SWITCH 1 CLOSED switchgear 1 closed SWITCH 1 00_ERROR Error 00 switchgear 1 (contact A = 0, contact B = 0) SWITCH 1 11_ERROR Error 11 switchgear 1 (contact A = 1, contact B = 1) SWITCH 2 OPEN Switchgear 2 open SWITCH 2 CLOSED Switchgear 2 closed SWITCH 2 00_ERROR Error 00 switchgear 2 (contact A = 0, contact B = 0) SWITCH 2 11_ERROR Error 11...