GE F650 Manual
Here you can view all the pages of manual GE F650 Manual. The GE manuals for Controller are available online for free. You can easily download all the documents as PDF.
Page 161
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.2 FIRMWARE UPGRADE VERSION 7.00 OR ABOVE GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-23 Note: To assure that the configuration is correctly setup it is possible to perform a ping command from the PC. Then the PC settings should be the same pattern as follows: IP Address:192.168.37.xxx Netmask:255.255.255.0 Gateway:192.168.37.10 (if desired) Where XXX is a number between 0 and 255 that is not assigned to any other device to avoid collisions. 5.2.2 Firmware...
Page 162
5-24F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.2 FIRMWARE UPGRADE VERSION 7.00 OR ABOVE CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE 3. Enter communication parameters for the relay being upgraded and click Upgrade. Figure 5-1: Relay communication parameters If the IP address is incorrect one, the following message is shown: 4. If the IP address is correctly set , then the message *.SFD Sending f ile is displayed. A sending f ile status bar shows the progress of the upgrade. 5. If the f ile is not sent...
Page 163
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.2 FIRMWARE UPGRADE VERSION 7.00 OR ABOVE GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-25 6. After sending the f ile successfully, the upgrade process starts: 7. When the flashing upgrade process f inishes, a message is displayed requesting a relay reboot . 8. User settings and logic f iles downloading When upgrading the firmware the entire settings and relay configuration are reset to factory default values. Then the User is committed to download the settings,...
Page 164
5-26F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.2 FIRMWARE UPGRADE VERSION 7.00 OR ABOVE CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE •Communication > Calibratio n > Set Calibration Files: to restore in the relay the calibration settings if necessary. • Fi le > Conf ig File (*.650) Converter : to convert the setting and conf iguration f ile *.650 for the relay (if it was in a previous version format). • Fil e > Send Info to Relay : to send the new settings and conf iguration f ile to the unit . 5.2.2.3...
Page 165
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.2 FIRMWARE UPGRADE VERSION 7.00 OR ABOVE GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-27 Figure 5-2: Set order code 3. This window only allows changing the last digit , which r efers to supported communications protocols options. Click Send: Figure 5-3: Password requir ement (special models) 4. The users must contact GE Multilin and prov ide the following parameters in their order: – Unit serial number – Current model option (before memory upgrade) –...
Page 166
5-28F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.2 FIRMWARE UPGRADE VERSION 7.00 OR ABOVE CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE Figure 5-4: Executed successfully 6. After the successful operation, the SEND button is disabled. It is not allowed to make another change from here, so it can be seen what changes have been made. The new order code appears on the status bar. Figure 5-5: New order code 5.2.3 Summary of main f irmware upgrade steps 1. Install the proper version of the EnerVista 650 Setup...
Page 167
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE5.2 FIRMWARE UPGRADE VERSION 7.00 OR ABOVE GEK-113000-AFF650 DIGITAL BAY CONTROLLER 5-29 through cable for hub or switch). 3. Set the appropriate IP address in the relay. 4. Set the appropriate IP address in the PC. 5. In the EnerVista 650 Setup software, select C ommunication > Upgrade Relay . 6. Select the appropriate f ile (D CL0 00CAXXX.SDF) for the upgrade. 7. Enter the IP address, serial number, and unit identif ier of the relay as prompted. 8. Click...
Page 168
5-30F650 DIGITAL BAY CONTROLLER GEK-113000-AF 5.2 FIRMWARE UPGRADE VERSION 7.00 OR ABOVE CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE
Page 169
GEK-113000-AFF650 DIGITAL BAY CONTROLLER 6-1 F650 Digital Bay Controller Chapter 6: Commissioning GE Grid Solutions COMMISSIONING 6.1 Visual inspection Verify that the relay has not suffered any damage during transportation, and that all screws are correctly fixed, and all relay terminal boards are in good condition. Verify that the information shown on the relay front plate corresponds to the data shown on the display, and to the requested relay model. Display information: Firmware version Kernel...
Page 170
6-2F650 DIGITAL BAY CONTROLLER GEK-113000-AF 6.2 OUT OF SERVICE SETTING CHAPTER 6: COMMISSIONING 6.2 Out of service setting The Relay Out Of Service setting is configured in Setpoint > System Setup > Miscellaneous. The unit also has an Out of Service status that is configured in Relay configuration > Protection elements. When active, these states stop all changes to PLC equations and functions, including changes to th e input/output boards, so if there is a change in any input or output the unit...
All GE manuals