CHAPTER 4 ND-70185 (E) Page 46 Revision 3.0 INSTALLATION Connecting Cables 4.3.3 When not using the cable unit SR1201 ETIF CAU-n When your system doesn’t use the cable unit classified as SR1201 ETIF CAU-n, perform the 10 BASE- T connections as instructed below: 1. Depending on your system configuration, connect the 10 BASE-T straight cable(s) between the HUB (PA-M96) and LANI (PZ-PC19) cards. Use the cable UTP CTG5 ST CA-O, which must be provided by the user. When a single LANI is used for each CPR (Slot 00 only) and the HUB is in a dual configuration, connect HUB#0 to LANI#0 and HUB#1 to LANI#1, using two 10 BASE-T cables. When dual LANIs are used in both Slot 00 and 03 of CPR#0/CPR#1, use at least two HUB cards as separate 10 BASE-T connection terminals: One HUB for the internal LANI (LANI-A in Slot 00 0f each CPR) and the other for the external LANI (LANI-B: in Slot 03 of each CPR) The external LANI is available for Series 7300 Release 3 software or later. 2. When HUB is in a dual configuration, connect the 10 BASE-T cross cable between the HUB cards. Use the cable UTP CTG5 CRS CA-F, which must be provided by the user. When using more than two HUB cards, connect the cross cable(s) for the remaining HUB cards, except the HUB card used for the MAT connection. 3. Connect the 10 BASE-T straight cable(s) between the HUB and FCH (PA-FCHA) cards. Use the following cables, which must be provided by the user. UTP CTG5 ST CA-F: When the HUB and FCH are in the same PIM (PIM0) UTP CTG5 ST CA-O: When the HUB and FCH are in different PIMs When FCH is in a dual configuration, connect FCH#0 to the HUB#0 side, and FCH#1 to the HUB#1 side. 4.3.4 Procedure for 4-IMG System When your system is 4-IMG type, the procedure for 10 BASE-T connection is as follows. Because the HUB (PA-M96) can be mounted anywhere in a PIM of any IMG, the Ethernet cables must be arranged by the user, depending on the system configuration. 1. Depending on your system configuration, connect the 10 BASE-T straight cable(s) between the HUB (PA-M96) and LANI (PZ-PC19) cards. Use the following cable, prepared by the user. UTP CTG5 ST CA-O: When the HUB and LANI are in the same IMG (IMG0) UTP CTG5 ST CA-X: When the HUB and LANI are in different IMGs When a single LANI is used for each CPR (Slot 00 only) and the HUB is in a dual configuration, connect HUB#0 and HUB#1 to LANI#1 using two 10 BASE-T cables.
ND-70185 (E) CHAPTER 4 Page 47 Revision 3.0 INSTALLATION Connecting Cables When dual LANIs are used in both Slot 00 and 03 of CPR#0/CPR#1, be sure to use at least two HUB cards as separate 10 BASE-T connection terminals. Use one HUB for the internal LANI (LANI-A: in Slot 00 of each CPR) and use the other for the external LANI (LANI-B in Slot 03 of each CPR). 2. When the HUB is in a dual configuration, connect the 10 BASE-T cross cable between the HUB cards. Use the following cables, which are provided by the user. UTP CTG5 CRS CA-F:When the HUB and HUB are in the same PIM UTP CTG5 CRS CA-O:When the HUB and HUB are in different PIMs but in the same IMG UTP CTG5 CRS CA-X:When the HUB and HUB are in different IMG stacks When using more than two HUB cards, also connect the cross cable(s) for the remaining HUB card(s), except the HUB for the MAT connection. This step is not necessary when your system uses dual LANIs for CPU#0/CPU#1 and FCH is also in a dual configuration. 3. Connect the 10 BASE-T straight cable(s) between the HUB and FCH (PA-FCHA) cards. Use the following cable, which must be provided by the user. UTP CTG5 ST CA-F: When the HUB and FCH are in the same PIM UTP CTG5 ST CA-O: When the HUB and FCH are in different PIMs but in the same IMG UTP CTG5 ST CA-X:When the HUB and FCH are in different IMG stacks When FCH is in a dual configuration, connect FCH#0 to the HUB#0 side, and FCH#1 to the HUB#1 side. 4.3.5 Procedure for IMX-U System When your system is the IMX-U type (configured to a maximum of 4 Local Nodes + 1ISW), the pro- cedure for the 10 BASE-T connection is as follows. Because this system already has a Fusion Link via the HUB (PA-M96) cards, this section gives details related only to the connection between the HUB and FCH (PA-FCHA) cards. 1. Refer to the NEAX2400 IMX Installation Manual (IMX-U Type) to make sure that the necessary 10 BASE-T (both straight and cross) connections between the ISW and each LN (Local Node) are all securely provided. 2. Connect the 10 BASE-T straight cable(s) between the HUB (PA-M96) and FCH (PA-FCHA) cards. Use the following cable, which must be provided by the user. UTP CTG5 ST CA-F: When the HUB and FCH are in the same PIM UTP CTG5 ST CA-O:When the HUB and FCH are in different PIMs but in the same IMG UTP CTG5 ST CA-X:When the HUB and FCH are in different IMG stacks but in the same LN UTP CTG5 ST CA-A0:When the HUB and FCH are in different LNs
CHAPTER 4 ND-70185 (E) Page 48 Revision 3.0 INSTALLATION Connecting Cables When dual FCH is provided for the HUB dedicated to each internal LANI card (LANI-A: in Slot 00 of each CPR), connect FCH#0 to HUB#0 and FCH#1 to HUB#1. When your system also uses the external LANI cards (LANI-B in Slot 03 of each CPR), prepare another set of FCH cards for the HUB dedicated to the external LANI cards. Then, if the FCH is in dual configuration, connect one FCH to the HUB for No. 0 system of the external LANI, and the other to the HUB for the No. 1 system of the external LANI. Figure 4-12 shows an example of a HUB in a dual configuration and the FCH card mounted in PIM 1 of the 1 IMG system. Figure 4-12 Connecting 10 BASE-T Cables (example) ATTENTIONContents Static Sensitive Handling Precautions Required DTI 2 3 3 Connect HUB and FCH using a 10 BASE-T straight cable. Refer to figures listed on the following pages. DTI FCH This figure shows an example where HUB is provided in a dual configuration and FCH card is mounted in PIM1 of 1-IMG system. LANI LANI PIM 1 PIM 0 HUB (PA-M96 ) HUB (PA-M96) GT GT 2 Connect two HUB cards using a 10 BASE-T cross cable. (When HUB is in dual configuration.) Note - 1 1 Connect the LANI and the HUB card using a 10 BASE-T straight cable. Eight 10 BASE-T connectors (TP0-X - TP7-X) are furnished on the front edge of the HUB card. Use one of the connectors. 1 Note Note Note:This step can be skipped when dual LANIs (LANI-A and LANI-B) are used for each CPU and FCH is provided in a dual configuration.
ND-70185 (E) CHAPTER 4 Page 49 Revision 3.0 INSTALLATION Connecting Cables Figure 4-13 shows some typical examples, where 10 BASE-T cables are connected to the FCH card(s) mounted in PIM0 of 1-IMG system, under the following conditions: Note 1:Cables Contained in each cable unit are as follows. SR1201 ETIF CAU-A: UTP CTG5 ST CA-D, UTP CTG5 ST CA-J SR1201 ETIF CAU-DA: UTP CTG5 ST CA-D, UTP CTG5 ST CA-J, UTP CTG5 CRS CA-F Note 2:The cables cited in Figure 4-13 can be used in the 1-IMG system only. Refer to Page 45 through Pa g e 4 8 for more details. Figure 4-13 Examples of Ethernet Cable Connection-FCH in PIM0 (1-IMG System) (1/2)Configuration of CPUConfiguration of LANUsed Cable Unit (Note 1, Note 2)Number of HUB/ FCH Pattern 1 Single Single SR1201 ETIF CAU-A × 1 HUB× 1, FCH× 1 Pattern 2 Dual SingleSR1201 ETIF CAU-A × 1 SR1201 ETIF CAU-DA × 1HUB× 2, FCH× 2 Pattern 3 Single Dual SR1201 ETIF CAU-A × 2 HUB× 2, FCH× 2 Pattern 4 Dual DualSR1201 ETIF CAU-A × 2 SR1201 ETIF CAU-DA × 2HUB× 2, FCH× 2 ATTENTIONContents Static Sensitive Handling Precautions Required BSCM 06 04 05 03 02 01 0006 04 05 03 02 01 00 CNCN HUB BASEU PIM 1 PIM 2 PIM 3 UTP CTG5 ST CA-J PIM 0 LPM FANU FCH CNCN UTP CTG5 ST CA-D TOPU FCH (PA-FCHA)HUB (PA-M96) TP0-X TP1-X TP2-X TP3-X TP4-X TP5-X TP6-X TP7-X 10 BASE-T Connectors for 10 BASE-T FRONT VIEWFRONT VIEW CN= 10 BASE-T Connector Use 10 BASE-T connectors. BSCM06 04 05 03 02 01 00 06 04 05 03 02 01 00 CN CN CN CN UTP CTG5 ST CA-J CNFCH HUB CN CNHUB BASEU PIM 1 PIM 2 PIM 3 LPM CN PIM 0 UTP CTG5 CRS CA-F CN FCHCN UTP CTG5 ST CA-D TOPU FANU
CHAPTER 4 ND-70185 (E) Page 50 Revision 3.0 INSTALLATION Connecting Cables Figure 4-13 Examples of Ethernet Cable Connection-FCH in PIM0 (1-IMG System) (2/2) ATTENTIONContents Static Sensitive Handling Precautions Required 06 04 05 03 02 01 0006 04 05 03 02 01 00 CN CNCN CN HUB CN CNHUB BASEU PIM 1 PIM 2 PIM 3 UTP CTG5 ST CA-J PIM 0 LPMTOPU FANU BSCM CN FCH CN UTP CTG5 ST CA-J FCH CNCN UTP CTG5 ST CA-D 06 04 05 03 02 01 00 06 04 05 03 02 01 00 CN CN CN CN CNCN CNUTP CTG5 ST CA-J CN FCH HUB CN CNHUB BASEU PIM 1 PIM 2 PIM 3 LPM CN CN TOPU FANU PIM 0CNFCHCN UTP CTG5 ST CA-D UTP CTG5 ST CA-J BSCM Note: When dual LANIs are used in both slot 00 and 03 of CPR (Pattern 3 or 4), be sure to use at least two HUB cards: One HUB for internal LANI (in slot 00) and the other for external LANI (in slot 03: available for Release 3 or later software). However, if this is the case and FCH is also in a dual configuration, the 10 BASE-T “cross” connection between the HUBs is not required.
ND-70185 (E) CHAPTER 4 Page 51 Revision 3.0 INSTALLATION Connecting Cables Figure 4-14 shows some typical examples, where 10 BASE-T cables are connected to the FCH card(s) mounted in PIM1 of 1-IMG system, under the following conditions: Note 1:Cables contained in each cable unit are as follows. SR1201 ETIF CAU-B: UTP CTG5 ST CA-K, UTP CTG5 ST CA-J SR1201 ETIF CAU-DB: UTP CTG5 ST CA-I, UTP CTG5 ST CA-J, UTP CTG5 CRS CA-F Note 2:The cables cited in Figure 4-14 can be used in the 1-IMG system only. Refer to Page 45 through Pa g e 4 8 for more details. Figure 4-14 Examples of Ethernet Cable Connection-FCH in PIM1 (1-IMG System)Configuration of CPUConfiguration of LANUsed Cable Unit (Note 1, Note 2)Number of HUB/ FCH Pattern 1 Single Single SR1201 ETIF CAU-B × 1 HUB× 1, FCH× 1 Pattern 2 Dual SingleSR1201 ETIF CAU-B × 1 SR1201 ETIF CAU-DB × 1HUB× 2, FCH× 2 Pattern 3 Single Dual SR1201 ETIF CAU-B × 2 HUB× 2, FCH× 2 Pattern 4 Dual DualSR1201 ETIF CAU-B × 2 SR1201 ETIF CAU-DB × 2HUB× 2, FCH× 2 ATTENTIONContents Static Sensitive Handling Precautions Required 06 04 05 03 02 01 0006 04 05 03 02 01 00 CNCN HUB BASEU PIM 1 PIM 2 PIM 3 UTP CTG5 ST CA-J PIM 0 LPM TOPU FANU BSCM FCH CN CN UTP CTG5 ST CA-K BSCM06 04 05 03 02 01 00 06 04 05 03 02 01 00 CN CN CN CN UTP CTG5 ST CA-J CNFCH HUB CN CN HUB BASEU PIM 1 PIM 2 PIM 3 LPM CN TOPU FANU PIM 0 UTP CTG5 CRS CA-F CNFCH CNUTP CTG5 ST CA-K UTP CTG5 ST CA-I FCH (PA-FCHA)HUB (PA-M96) TP0-X TP1-X TP2-X TP3-X TP4-X TP5-X TP6-X TP7-X 10 BASE-T Connectors for 10 BASE-T FRONT VIEWFRONT VIEW CN= 10 BASE-T Connector Use 10 BASE-T connectors.
CHAPTER 4 ND-70185 (E) Page 52 Revision 3.0 INSTALLATION Connecting Cables Figure 4-15 shows some typical examples, where 10 BASE-T cables are connected to the FCH card(s) mounted in PIM2 of 1-IMG system, under the following conditions: Note 1:Cables contained in each cable unit are as follows. SR1201 ETIF CAU-C: UTP CTG5 ST CA-M, UTP CTG5 ST CA-J SR1201 ETIF CAU-DC: UTP CTG5 ST CA-K, UTP CTG5 ST CA-J, UTP CTG5 CRS CA-F Note 2:The cables cited in Figure 4-15 can be used in the 1-IMG system only. Refer to Page 45 through Pa g e 4 8 for more details. Figure 4-15 Examples of Ethernet Cable Connection-FCH in PIM2 (1-IMG System) (1/2)Configuration of CPUConfiguration of LANUsed Cable Unit (Note 1, Note 2)Number of HUB/ FCH Pattern 1 Single Single SR1201 ETIF CAU-C × 1 HUB× 1, FCH× 1 Pattern 2 Dual SingleSR1201 ETIF CAU-C × 1 SR1201 ETIF CAU-DC × 1HUB× 2, FCH× 2 Pattern 3 Single Dual SR1201 ETIF CAU-C × 2 HUB× 2, FCH× 2 Pattern 4 Dual DualSR1201 ETIF CAU-C × 2 SR1201 ETIF CAU-DC × 2HUB× 2, FCH× 2 ATTENTIONContents Static Sensitive Handling Precautions Required 06 04 05 03 02 01 0006 04 05 03 02 01 00 CNCN HUB BASEU UTP CTG5 ST CA-J FANU BSCM FCH CN CN UTP CTG5 ST CA-M TOPU PIM 1 PIM 2 PIM 3 PIM 0 LPM 06 04 05 03 02 01 00 06 04 05 03 02 01 00 CN CN CN CN UTP CTG5 ST CA-J CNFCH HUB CN CNHUB BASEU PIM 1 PIM 2 PIM 3 LPM CN FANU PIM 0UTP CTG5 CRS CA-F CNFCH CN UTP CTG5 ST CA-M UTP CTG5 ST CA-K BSCM TOPU FCH (PA-FCHA)HUB (PA-M96) TP0-X TP1-X TP2-X TP3-X TP4-X TP5-X TP6-X TP7-X 10 BASE-T Connectors for 10 BASE-T FRONT VIEWFRONT VIEW CN= 10 BASE-T Connector Use 10 BASE-T connectors.
ND-70185 (E) CHAPTER 4 Page 53 Revision 3.0 INSTALLATION Connecting Cables Figure 4-15 Examples of Ethernet Cable Connection-FCH in PIM2 (1-IMG System) (2/2) ATTENTIO NContents Static Sensitive Handling Precautions Required 06 04 05 03 02 01 00 06 04 05 03 02 01 00 CN CN CN CNCN CNUTP CTG5 ST CA-J CNFC H HUB CN HUB BASEU PIM 1 PIM 2 PIM 3 LPM CN CN FANU PIM 0 CN FCH CN UTP CTG5 ST CA-M UTP CTG5 ST CA-K UTP CTG5 ST CA-J TO PU 06 04 05 03 02 01 0006 04 05 03 02 01 00 CN CNCN CN HUB CN CNHUB BASEU PIM 1 PIM 2 PIM 3 UTP CTG5 ST CA-J PIM 0 LPMFANU BSCM BSCM CN FC H CN FCH CN CN UTP CTG5 ST CA-MUTP CTG5 ST CA-J TO PU < F C H in P IM 2 (P attern 3)> Note:When dual LANIs are used in both Slot 00 and 03 of CPR (Pattern 3 or 4), be sure to use at least two HUB cards: One HUB for internal LANI (in Slot 00) and the other for external LANI (in Slot 03). However, if this is the case and FCH is also in a dual configuration, the 10 BASE-T “cross” connection between the HUBs is not required.
CHAPTER 4 ND-70185 (E) Page 54 Revision 3.0 INSTALLATION Connecting Cables Figure 4-16 shows some typical examples, where 10 BASE-T cables are connected to the FCH card(s) mounted in PIM3 of 1-IMG system, under the following conditions: Note 1:Cables contained in each cable unit are as follows. SR1201 ETIF CAU-D: UTP CTG5 ST CA-N, UTP CTG5 ST CA-J SR1201 ETIF CAU-DD: UTP CTG5 ST CA-L, UTP CTG5 ST CA-J, UTP CTG5 CRS CA-F Note 2:The cables cited in Figure 4-16 can be used in the 1-IMG system only. Refer to Page 45 through Pa g e 4 8 for more details. Figure 4-16 Examples of Ethernet Cable Connection-FCH in PIM3 (1-IMG System) (1/2)Configuration of CPUConfiguration of LANUsed Cable Unit (Note 1, Note 2)Number of HUB/ FCH Pattern 1 Single Single SR1201 ETIF CAU-D × 1 HUB× 1, FCH× 1 Pattern 2 Dual SingleSR1201 ETIF CAU-D × 1 SR1201 ETIF CAU-DD × 1HUB× 2, FCH× 2 Pattern 3 Single Dual SR1201 ETIF CAU-D × 2 HUB× 2, FCH× 2 Pattern 4 Dual DualSR1201 ETIF CAU-D × 2 SR1201 ETIF CAU-DD × 2HUB× 2, FCH× 2 ATTENTIONContents Static Sensitive Handling Precautions Required 06 04 05 03 02 01 0006 04 05 03 02 01 00 CNCN HUB BASEU UTP CTG5 ST CA-J FANU BSCM FCH CN CN UTP CTG5 ST CA-N PIM 1 PIM 2 PIM 3 PIM 0 LPM TOPU 06 04 05 03 02 01 00 06 04 05 03 02 01 00 CN CN CN CN UTP CTG5 ST CA-J CNFCH HUB CN CN HUB BASEU PIM 1 PIM 2 PIM 3 LPM CN TOPU FANU PIM 0 BSCM UTP CTG5 CRS CA-F CNFCH CN UTP CTG5 ST CA-N UTP CTG5 ST CA-L FCH (PA-FCHA)HUB (PA-M96) TP0-X TP1-X TP2-X TP3-X TP4-X TP5-X TP6-X TP7-X 10 BASE-T Connectors for 10 BASE-T FRONT VIEWFRONT VIEW CN= 10 BASE-T Connector Use 10 BASE-T connectors.
ND-70185 (E) CHAPTER 4 Page 55 Revision 3.0 INSTALLATION Connecting Cables Figure 4-16 Examples of Ethernet Cable Connection-FCH in PIM3 (1-IMG System) (2/2) ATTENTIONContents Static Sensitive Handling Precautions Required 06 04 05 03 02 01 0006 04 05 03 02 01 00 CN CNCN CN HUB CN CNHUB BASEU PIM 1 PIM 2 PIM 3 UTP CTG5 ST CA-J PIM 0 LPMFANU BSCM BSCM CN FCH CN UTP CTG5 ST CA-J FCH CN CN UTP CTG5 ST CA-N TOPU 06 04 05 03 02 01 00 06 04 05 03 02 01 00 CN CN CN CNCN CNUTP CTG5 ST CA-J CN FC H HUB CN HUB BASEU PIM 1 PIM 2 PIM 3 LPM CN CN FANU PIM 0 CN FCH CN UTP CTG5 ST CA-N UTP CTG5 ST CA-L UTP CTG5 ST CA-J TOPU Note:When dual LANIs are used in both Slot 00 and 03 of CPR (Pattern 3 or 4), be sure to use at least two HUB cards: One HUB for internal LANI (in Slot 00) and the other for external LANI (in Slot 03). However, if this is the case and FCH is also in a dual configuration, the 10 BASE-T ”cross” connection between the HUBs is not required.