Important Safety instructions I personnel. Grounding instructions must be followed explicitly to ensure the safety of Table 13 AC Systems Grounding Cables (External) Item Gauge Function From To Remarks 1. 10 AWG. Safety ground The nearest The Safety Cable supplied by See source. electrical utility Ground stud on the installation Note 1. ground external to the floor of the company. the cabinet. control cabinet. 2. IOAWG Safety ground. The Safety The Safety Cable is supplied Ground stud in Ground stud in in peripheral one cabinet. adjacent cabinet. cabinet. See Note 4. 3. 14AWG Safety ground The Safety The Protective See Figure l-l 1. jumper. Ground stud on Earth stud (GND2) the cabinet floor. on the back of the PDU. 4. 6-l 0 AWG. System ground Site building System Ground See Figure l-9, See source. ground. Terminal on rear Figure l-l 0 and Note 2. panel of each Figure l-1 1. cabinet Power Distribution Unit. See Note 3. Notes: 1. a) See Figure l-l 1. b) Cable length must not exceed 50 feet. 2. This cable is supplied by the installation company. The cable must be a continuous conductor which has a total resistance of less than 0.5 ohms when measured between its point of origin; (i.e., ground source), and the system ground of each cabinet. 3. On systems operating in the U.K., the system ground cable is terminated on the Functional Earth termi- nal of the TB3 terminal block (see Figure l-l 1). 4. The sequence for connection of the external grounding cables in multicabinet systems is: Cabinet #2 to Cabinet #l , Cabinet #3 to Cabinet #2 and Cabinet #4 to Cabinet #3. 912!5-06&203-NA Issue 1 Revision 0 203 I-17
![](/img/blank.gif)
Table 1-4 DC System Grounding Cables (External) Item Gauge Function From To Remarks 1. 1 OAWG. Safety ground The nearest The Safety Cable supplied by See source. electrical utility Ground Terminal the installation Note 1. ground external to on the rear of company. the cabinet. Control Cabinet Power Distribution Unit. 2. 14AWG Safety ground The Safety The Protective See Figure l-l 2. jumper. Ground stud on Earth stud (GND2) the cabinet floor. on the back of the Power Distribution Unit. 3. 10AWG Safety ground. The Safety The Safety Cable is supplied Ground stud in Ground stud in in peripheral one cabinet. adjacent cabinet. cabinet. See Note 4. 4. 6 AWG. See Note 2. System ground Site building System Ground See Figure l-9, source. ground. Terminal on rear Figure l-l 0 and panel of each Figure l-l 2. cabinet Power Distribution Unit. See Note 3. Safety Instructions Notes: 1. a) See Figure l-l 0. b) Cable length must not exceed 50 feet. 2. This cable is supplied by the installation company. The cable must be a continuous conductor which has a total resistance of less than 0.5 ohms when measured between its point of origin; (i.e., ground source), and the system ground of each cabinet. 3. On systems operating in the U.K., the system ground cable is terminated on the Functional Earth termi- nal of the TB3 terminal block (see Figure l-l 2). 4. The sequence for connection of the external grounding cables in multicabinet systems is: Cabinet #2 to Cabinet #1 , Cabinet #3 to Cabinet #2 and - Cabinet #4 to Cabinet #3. 203 l-18 Revision 0 9125-060-203-NA Issue 1
![](/img/blank.gif)
Important Safety Instructions -. .-- - - I ---o b 0 0 - DG DG I DG EDG I I0 EDG 0 FGZ I & - DG DG DG EDG ECG 7 5 3 4 NA. only I_ NA. ordy I FAN UNK I TB3 POWER DISTFIIB~ION UNIT “Ll ” ” I EDG ‘\=, I I 6 I - TO BUILDING TO AX. MAINS GROUND GROUND (AC. SYSTEMS ONLY) N.A. : 1 POVAC /4WDC PDU DG : DIGKAL GROUND EDG : ENERGY DUMPING 1, GROUND - :FRAMrn - GROUND HARD r-l DlSK MODULE 0 Figure l-9 SX-2000 S System Ground Connections 912!5-060-203-NA Issue 1 Revision 0 203 1-19
![](/img/blank.gif)
Safetv Instructions DC POWER DlSTFWLmON LJNrr / I TERMINAL AC INPIJT SWITCH AC SOCKET SScoP6 Figure I-IO SX-2000S System AC and DC Power Distribution Units (Rear Panel) 203 l-20 Revision 0 9125-060-203-NA Issue 1
![](/img/blank.gif)
Important Safety Instructions SHELF1 82 ClRCulT BREAKERS 1 @+I SURGE PPmEcTlON f 120 vat SUPPLY TO SHELF CONVERTERS TERMINAL BLOCK - INTERNAL WIRING STUD BBOMSRl Figure 1-11 SX-2000 S System AC Power Distribution Unit Terminal Blocks 9125-060-203-NA Issue 1 Revision 0 203 l-21
![](/img/blank.gif)
Safety Instructions I SCREW-MIWN CABLETIGHENER CABLE CABLE FASTENER BODY NUT II c c c I I FUSES c L c D Ex-rERNAl 48 Vdc SUPPLY I II I AUXlWRY /IV - TEFIMINAL BLOCK t-W PROTECTlVE EARTH STUD W’W ENEiGY DUMPING AND DIGITAL GROUND: SiFEW GROUND STUD BBW24Rl Figure 1-12 SX-2000 S System DC Power Distribution Unit Terminal Blocks 203 l-22 Revision 0 9125-060-203-N/4 Issue 1
![](/img/blank.gif)
Important Safety Instructions SX-2000 VS Grounding The SX-2000 VS systems operating in North America require only one external ground, the safety ground. A ground clip, attached to the EMI shield, links the safety ground to the system ground on the System Filter Assembly Card. The System Filter Assembly card, plugged into the backplane, provides a common point for all grounds in the system (DGI). Refer to Figure 1-I 3 for ground references on the SX-2000 VS system. Grounding cables are to be installed in accordance with the information that is listed in Table I-5. Table l-5 SX-2ooO VS System Cabinet Grounding Cables (External) Item Gauge Function From To Remarks 1. 2-6 AWG Safety Ground The nearest electri- The Safety Ground The cable is (See Note) cal utility ground terminal on the back supplied by the that is external to of the System cabi- installation the system cabinet. net, beside the PDU. company. Note: The cable length must not exceed 50 feet. 9125-060-203-NA Issue 1 Revision 0 203 l-23
![](/img/blank.gif)
Safety Instructions EMI , SHIELD L- I J7 J3 I I K CABLE GUIDES WARNING Jl 0 AC INPUT 3 DSU PORTS / I I SYSTEM FILTER ASSEMBLY CARD PROTECTIVE - SHIELD SAPEN GROUND STUD I MDF CAR, E ..-. -. --- ENTRY PORT - DIGITAL GROUND DGI BB0061 R2 203 l-24 Figure I-1 3 SX-2000 VS System Grounds Revision 0 9125-060-203-NA Issue 1
![](/img/blank.gif)
Important Safety Instructions POWER SELECTOR MITCH POWER SUPPLY UNKi fr - / - \. II f!I iiiNTEN4NCEB I I PI -ii.imN~htE~ A@ll@ll@l -u-Y JlO REMOTE ALARMS MAlNMAtKETERMlk4LPORT - EMISHEU) NON-REDUNDANT CONTFiOL NODE NON-REDUNDANT CONTROL NODE POWER SWITCH AC INPUT 2-WIRE CONNECTlON (POWER AND GROUND) POWER SELECTOR SWlTCH POWER SWCH JlO 1 cl a $ 8 . I h4AlNTEN4NCETERMlNALPORT I C-GYSTEM GROUNDTERMINAL PERIPHERAL NODE AC INPUT S-WIRE CONNECTION (POWER AND GROUND) - EMI SHIELD - MAlNTEN4NCETERMlNALPORTS MAlNTEN4NCETERMlNALPORTS POWER SUPPLY UNK DSU NODE Figure l-l 4 SX-2000 FD System Grounds 9125-06&203-NA Issue 1 Revision 0 203 1-25
![](/img/blank.gif)
Safety Instructions SX-2000 FD Grounding The SX-2000 FD systems operating in North America require only one external ground, the system ground. Refer to Figure 1-14 for ground references on the SX-2000 FD system. A 14 AWG gauge system ground cable is installed between the system ground terminal on the backplate of each Peripheral Node and the site building ground. Grounding cables are to be installed in accordance with the information listed in table Table 1-S. Table 14 SX-2000 FD System Peripheral Cabinet Grounding Cables (External) Item Gauge Function From To Remarks 1. 14AWG System The nearest electri- The System Ground The cable is Ground cal utility ground terminal on the back supplied by the that is external to of each Peripheral installation the system cabinet. cabinet. company. Note: GroundinginformationappliesonlytotheSX-Z0~0FDPeripheralCabinet(s). ItisnotrequiredfortheSX-ZOOOFD Control Cabinet or DSU Cabinet(s). Approved Configurations of Product (United States of America) 1.6 These products have been evaluated and listed with Underwriters’ Laboratories Incorporated to their Standard for Safety 1459, “Telephone Equipment”, Second Edition. The following assemblies have been investigated and determined suitable for use in this product: Table l-7 SX-2000 SG System Sub-assemblies Marketing Number Description / Common Name Engineering Mlnimum Number Revision MAO1 8CA TRANSFER SWITCH ASSEMBLY KIT 1070186CA A I MAOBOCA 1 CONTROL CABINET PDU 1 1070306CA 1 A 1 MA031 CA MA078BA MA079BA PERIPHERAL CABINET PDU CONTROL MAINTENANCE UNIT PERIPHERAL MAINTENANCE UNIT 1070316CA A 1070786BA A 1070796BA A Page 1 of 3 203 l-26 Revision 0 9125-060-203-NA Issue 1