Page 191
Troubleshooting - TABLE Al-l (Cont’d) FAULT REPORTS Alarm Code Action Required ONS card passed at 02 01 01 00 ext 2101 Card installed Alarm Code = 103 Information only. Stn line card passed at 03 01 01 00 ext 3101 Card installed Alarm Code = 103 COV card passed at 01 05 01 00 ext 1501 Card installed Alarm Code = 103 Superset card passed at 03.01 01 00 ext 3101 Card installed Alarm Code = 103 LS/GS trk card passed at 02 02 01 00 Card installed Alarm Code = 103 CO trunk card passed at 02 02...
Page 192
Troubleshooting TABLE Al-l (Cont’d) FAULT REPORTS Alarm Code Message Action Required eneric Generic 1000 1001 21 105 COV card failed at 01 05 01 00 ext 1501 The specified extension has been unplugged. If Superset Unplugged Alarm Code = 105 this is not the case, check wiring. Superset card failed at 03 01 01 00 ext 3101 Superset Unplugged Alarm Code = 105 22 106 Database failed at 00 00 04 00 This is a warning. Stop CDE programming activity. Serious ram shortge Alarm Code = 106 Wait for a low...
Page 193
Troubleshooting TABLE Al-l (Cont’d) FAULT REPORTS Action Required Alarm Code Message ieneric 1001 &neric 1000 28 No release signal was received from the Central Office. Verify wiring. Refer to Section MITL9108-093-200-N& Shipping, Receiving, and Installation for details. LS/GS trk card failed at 02 02 01 00 Can’t release trunk Alarm Code = 112 CO trunk card failed at 02 02 01 00 Can’t release trunk Alarm Code = 112 E&M trunk card failed at 02 02 01 00 Can’t release trunk Alarm Code =...
Page 194
Troubleshooting TABLE A-l (Cont’d) FAULT REPORTS Alarm Code Message Action Required neric Generic 000 1001 37 121 PFT sense failed at 00 00 08 00 The digital bays have gone into Power Fail Bay has cut through Alarm Code = 121 Transfer mode. Use SHOW ALARMS command and BAY failed at 03 00 00 00 examine logs further to find the actual cause of Bay has cut through Alarm Code = 121 the cut through. The specified analog bay has gone into Power Fail Transfer mode. Check for messages indicating that...
Page 195
Troubleshooting TABLE Al-l (Cont’d) FAULT REPORTS Alarm Code Action Required DISK failed at 00 00 03 00 Disk corrupt Alarm Code = 126 Disk has been corrupted. Check to see if disk is properly installed. Attempt to access the disk by logging into CDE or Maintenance. Reset the system at the earliest low traffic period. New Reseat the affected Universal card. ** anything ** failed at 00 00 00 00 Plid to Swid failed Alarm Code = 129 urther occurrences. If aded substantially, Disk VS Ram Failed...
Page 196
Troubleshooting Generic 1000 ’ n/a Generic 1001 138 TABLE Al-l (Cont’d) FAULT REPORTS Message UPS sense failed at 00 00 09 00 AC/battery/charger Alarm Code = 138 Action Required There is no line AC voltage. Also, the battery is failing, or the charger is/was not functioning properly. Examine battery, charger and wiring. Also, refer to the instructions provided by the manufacturer of the UPS. Page A&t1
Page 197
Troubleshooting TABLE Al-2 ALARM LOG REPORTS Alarm Code Tot alarm went from MINOR to MAJOR Due to threshold change of Use SHOW ALARMS command for more detailed information. Also see the applicable entry in Table Al-3. Tot alarm went from MINOR to No Alarm This is an improvement in service. Information only. Page A-12
Page 198
Troubleshooting TABLE Ala3 ALARM RESET REASONS Alarm Level Change Reason 4larm level change due to control Action Required If system is not processing calls, reset the system iinmediately. Otherwise refer to the Main Control card Part of this Section. 41arm level change due to bay 03 PCM channels Check the status of the specified bay via the SHOW ALARMS and SHOW STATUS commands. Refer to the ‘Analog Peripheral Subsystem’ Part of this Section. Alarm level change due to bay 03 control Check the...
Page 199
Troubleshooting TABLE Al-4 RESET LOG REPORTS Main Control was reset due to pushbutton was pushed. Investigate. Main Control was reset due to msg link failure Main Control was reset due to software error Process 00 at address 012345 Main Control was reset due to software error RAM parity error at address = 012345 Main Control was reset due to software error Process 00 has overflowed its stack Main Control was reset due to software error Page A-l 4/l 4
Page 200
Troubleshooting APPENDllX 5 PART NUMBERS 81.01 Table Bl-1 shows the marketing part numbers for the circuit cards and modules of the SX-200@ DIGITAL PABX. For further information, refer to Section MITL9108-093-150-NA, Ordering Informa- tion. TABLE Bl-1 PART NUMBERS Card Type Part Number ONS Line Card 9109-OlO-OOO-NA OPS Line Card 9 109-040-OOO-NA COV Line Card 9 109-Q20-OOO-NA 8 Station Line Card 91 IO-I IO-OOO-NA SUPERSET Line Card 91 IO-410-OOO-NA LWGS Trunk Card 9109-01 I-OOO-NA DID...