Here you can view all the pages of manual Lucent Technologies DEFINITY Enterprise Communication Server Release 8.2 Installation And Test For Multi-Carrier Cabinets Manual. The Lucent Technologies manuals for Communications System are available online for free. You can easily download all the documents as PDF.

Page 31

DEFINITY ECS Release 8.2 Installation and Test
for Multi-Carrier Cabinets  555-233-114  Issue 1
April 2000
Install and Connect Cabinets 
1-11 Connect AC Power and Ground 
1
Figure 1-2. Typical Cabinet Grounding Wiring Diagram Figure Notes
1. PPN Cab inet
2. EPN Cab inet (if Installed )
3. 6 AWG (#40) (16 mm
2) CABINET 
GROUND Wire
4. Sing le-Point Ground Bloc k5. 6 AWG (#40) (16 mm
2) Ground Wire
6. AC Load Center Sing le-Point Ground
7. Over 50 ft (15.2 m)
8. Cab inet Ground Terminal Bloc k
6
122
333
5...

Page 32

DEFINITY ECS Release 8.2 Installation and Test
for Multi-Carrier Cabinets  555-233-114  Issue 1
April 2000
Install and Connect Cabinets 
1-12 Connect AC Power and Ground 
1
Connect Battery Leads (J58890CH-1)
Fi g u re  1 - 3 shows a typ ic al op tional small b attery hold over assemb ly. These 
assemb lies may ship  with the b attery lead s d isc onnec ted  to p revent the b atteries 
from discharging.
1. Plug  the b attery c onnec tor into the -48 VDC Batteries c onnec tor on the 
rear of the J58890CH-1...

Page 33

DEFINITY ECS Release 8.2 Installation and Test
for Multi-Carrier Cabinets  555-233-114  Issue 1
April 2000
Install and Connect Cabinets 
1-13 Connect AC Power and Ground 
1
Figure 1-4. Power Distribution Unit (J58890CH)
2. Be sure the main p ower to the p ower d istrib ution unit is OFF.
3. At the power d istribution unit, set all c arrier c irc uit b reakers OFF.
Small Battery Holdover 
1. Connec t the small b attery hold over c ab le to J20. See Fi g u re  1 -4. Figure Notes
1. Connec t small battery...

Page 34

DEFINITY ECS Release 8.2 Installation and Test
for Multi-Carrier Cabinets  555-233-114  Issue 1
April 2000
Install and Connect Cabinets 
1-14 Connect AC Power and Ground 
1
Large Battery Holdover
When using  larg e b attery hold over, 1 b attery c ab inet is req uired  for every system 
c ab inet req uiring  hold over. The 24-c ell b attery c ab inet must have a float voltag e 
of 54.2 VDC. 
1. Connec t the -48 VDC c able to the larg e b attery c onnec tor. See Fi g u re  1 -4
.
2. Connec t the -48 VDC...

Page 35

DEFINITY ECS Release 8.2 Installation and Test
for Multi-Carrier Cabinets  555-233-114  Issue 1
April 2000
Install and Connect Cabinets 
1-15 Connect AC Power and Ground 
1
Figure 1-5. Shorting Cable Installation
1. Set the c irc uit breakers on the p ower d istrib ution unit OFF. See Fi g u re  1 -5
.
2. At the rear of the c ab inet, insert the shorting  c ab le (H600-442-G1) into 
J11. The c ab le is keyed  so it c an fit only 1 way.
Connect AC Power
1. Set the main c irc uit b reakers on the p ower d...

Page 36

DEFINITY ECS Release 8.2 Installation and Test
for Multi-Carrier Cabinets  555-233-114  Issue 1
April 2000
Install and Connect Cabinets 
1-16 Connect DC Power and Ground 
1
Connect DC Power and Ground
Power Distribution Unit (J58890CH-1 Only)
Rectifier Modules and Battery Interface Unit 
Eac h rec tifier mod ule op erates as an integ ral p art of a c omp lete p ower system 
with b attery b ac kup . The mod ules op erate in a red und ant, hig h reliab ility mod e to 
p rovid e -48 VDC at 850 Watts to a c...

Page 37

DEFINITY ECS Release 8.2 Installation and Test
for Multi-Carrier Cabinets  555-233-114  Issue 1
April 2000
Install and Connect Cabinets 
1-17 Connect DC Power and Ground 
1
1. Install the BU3200A Battery Interfac e Unit (c omc ode 107781502) in the 
first slot of the p ower d istrib ution unit. See Fig ure  1-6
. 
NOTE:
The BIU and  the rec tifier mod ules are keyed and  c an only install 1 
way.
2. Install the first 2 RM0850HA100 Rec tifier Modules (c omc od e 107793796) 
into the sec ond  and  third...

Page 38

DEFINITY ECS Release 8.2 Installation and Test
for Multi-Carrier Cabinets  555-233-114  Issue 1
April 2000
Install and Connect Cabinets 
1-18 Connect DC Power and Ground 
1
DC Power and Ground (J58890CF Only)
Fi g u re  1 - 7 shows a typ ic al p ower and  g round  layout for a DC-powered  c ab inet. 
The size of the wire required  for the -48 volt DC and  -48 volt return must ensure 
the voltage sup p lied  b y the b attery plant is maintained  b etween -42.5 and  -54.2 
volts DC at all times for p roper...

Page 39

DEFINITY ECS Release 8.2 Installation and Test
for Multi-Carrier Cabinets  555-233-114  Issue 1
April 2000
Install and Connect Cabinets 
1-19 Connect DC Power and Ground 
1
Connect DC Power and Ground
The g round ing  method s for the DC-p owered  system are more c omp lex than that 
of an AC-powered  system. The following  installation p roc ed ures refer to Fig ure 
1-7. The numbers 1-8 in Fi g u re  1 -7 matc h the following  sub sec tions 1-8. Other 
fig ures may b e referenc ed  as req uired ....

Page 40

DEFINITY ECS Release 8.2 Installation and Test
for Multi-Carrier Cabinets  555-233-114  Issue 1
April 2000
Install and Connect Cabinets 
1-20 Connect DC Power and Ground 
1
3. At the DC Power Cab inet, c onnec t the wire to the Ground  Disc harg e Bar.
4. Route the wire throug h 1 of the holes in the sid e of the c ab inets and  
terminate it on the Ground  Connec tion Terminal in the DC Battery Cabinet.
3. DC Power Cabinet Approved Ground
NOTE:
The wire must b e at least as larg e as the larg est d...