ModBus Data Listing Appendix B B–58 B088 — Restart mode after FRS R/W 00 . Restart from 0Hz01 . Restart from frequency detected from actual speed of motor 02 . Restart from active matching frequency135Bh 04955 0, 1, 2 — — (Reserved) ——135Ch 04956 — — B090 — Dynamic braking usage ratio R/W 0.0 to 100.0 (%) Set = 0.0 to disable dynamic braking 135Dh 04957 0 to 1000 0.1 % B091 — Stop mode selection R/W 00 . DEC (decelerate and stop) 01 . FRS (free run to stop)135Eh 04958 0, 1 — B092 —...
Page 342
SJ7002 Inverter Appendix B B–59 — (Reserved)——1375h to 137Ah 04981 to 04986 —— B120 — Brake Control Enable R/W 00 . Disable 01 . Enable137Bh 04987 0, 1 — B121 — Brake Wait Time for Release R/W Sets time delay between arrival at release frequency and the brake release signal 137Ch 04977 0 to 500 0.01 sec. B122 — Brake Wait Time for Acceleration R/W Sets time delay from receipt of brake confirmation signal to start of motor acceleration 137Dh 04979 0 to 500 0.01 sec. B123 — Brake Wait Time for...
Page 343
ModBus Data Listing Appendix B B–60 Holding Registers, “C” Group Intelligent Terminal Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. C001 — Terminal [1] function R/W See “Input Terminal Configuration” on page 3–50 1401h 05121 1 to 9, 11 to 18, 20 to 24, 26 to 29, 31 to 48, no — C002 — Terminal [2] function R/W 1402h 05122 C003 — Terminal [3] function R/W 1403h 05123 C004 — Terminal [4] function R/W 1404h 05124 C005 — Terminal [5] function R/W 1405h 05125 C006 — Terminal...
Page 344
SJ7002 Inverter Appendix B B–61 — (Reserved)——1425h 05157 — — C038 — Low current indication output mode select R/W 00 . Output during accel/ decel and constant speed 01 . Output only during constant speed 1426h 05158 0, 1 — C039 — Low current indication detection level R/W 0.0 to 2.0 x rated inverter current 1427h 05159 0 to 1800 0.1 % C040 — Overload signal output mode R/W 00 . During accel / decel / constant speed 01 . During constant speed 1428h 05160 0, 1 — C041 — Overload...
Page 345
ModBus Data Listing Appendix B B–62 — (Reserved)——143Fh 05183 — — — (Reserved) ——1440h 05184 — — C061 — Electronic thermal warning level setting R/W Sets the threshold for intelligent output [THM] 1441h 05185 0 to 100 1 % C062 — Alarm code output R/W 00 ..Disable 01 ..Enable – 3-bit code 02 ..Enable – 4-bit code1442h 05186 0, 1, 2 — C063 — Zero speed detection level R/W 0.00 to 99.99 / 100.0 (Hz) 1443h 05187 0 to 10000 0.01 Hz C064 — Heatsink overheat warning level R/W Alarm temperature thresh- old...
Page 346
SJ7002 Inverter Appendix B B–63 C085 — Thermistor input tuning R/W 0.0 to 999.9., 10001459h 05209 —(Reserved) — — 145Ah to 145Eh 05210 to 05214 —— C091 — Debug mode enable R 00 . No display 01 . Display145Fh 05215 0, 1 — — — (Reserved) ——1460h to 1468h 05216 to 05224 —— C101 — Up/Down memory mode selection R/W 00 . Clear last freq. (return to default freq. F001) 01 . Keep last frequency adjusted by UP/DWN 1469h 05225 0, 1 — C102 — Reset mode selection R/W 00 . Cancel trip state, stop...
Page 347
ModBus Data Listing Appendix B B–64 C123 — [O2] input zero calibration R/W 0. to 9999., 1000 to 6553(10000 to 65530)147Fh 05247 0 to 65530 1 — (Reserved) — — 1480h to 1485h 05248 to 05253 —— C130 — Term. [11] ON-delay time R/W 0.0 to 100.0 (seconds) 1486h 05254 0 to 1000 0.1 sec. C131 — Term. [11] OFF-delay time R/W 0.0 to 100.0 (seconds) 1487h 05255 0 to 1000 0.1 sec. C132 — Term. [12] ON-delay time R/W 0.0 to 100.0 (seconds) 1488h 05256 0 to 1000 0.1 sec. C133 — Term. [12] OFF-delay time R/W 0.0 to...
Page 348
SJ7002 Inverter Appendix B B–65 C156 — Logic output 5 operator R/W 00 . AND01 . OR 02 . XOR (exclusive OR)14A0h 05280 0, 1, 2 — C157 — Logic output 6 function A R/W All programmable output functions available (except LOG1 to LOG6)14A1h 05281 — — C158 — Logic output 6 function B R/W 14A2h 05282 C159 — Logic output 6 operator R/W 00 . AND 01 . OR 02 . XOR (exclusive OR)14A3h 05283 0, 1, 2 — C160 — Terminal [1] input response time setting R/W 0. to 200. (x 2 milliseconds) 14A4h 05284 0 to 200 2 ms C161 —...
Page 349
ModBus Data Listing Appendix B B–66 Holding Registers, “H” Group Motor Constants Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. H001 — Auto-tuning setting R/W 00 ..Auto-tuning OFF 01 ..Auto-tune 02 ..Auto-tune (rotate motor)1501h 05377 0, 1, 2 — H002 — Motor data selection, 1st motor R/W 00 ..Standard motor data 01 ..Auto-tuning data 02 ..Adaptive tuning data 1502h 05378 0, 1, 2 — H202 — Motor data selection, 2nd motor R/W 00 ..Standard motor data 01 ..Auto-tuning data 02...
Page 350
SJ7002 Inverter Appendix B B–67 H221 H Motor constant R2, 2nd motor R/W 0.001 to 9.999, 10.00 to 65.53 (Ohms) 2517h 09495 1 to 65530 0.001 Ω H221 L R/W 2518h 09496 H022 H Motor constant L, 1st motor R/W 0.01 to 99.99, 100.0 - 655.3 (mH) 1519h 05401 1 to 65530 0.01 mH H022 L R/W 151Ah 05402 H222 H Motor constant L, 2nd motor R/W 0.01 to 99.99, 100.0 - 655.3 (mH) 2519h 09497 1 to 65530 0.01 mH H222 L R/W 251Ah 09498 H023 H Motor constant Io R/W 0.01 to 99.99, 100.0 - 655.3 (A)151Bh 05403 1 to 65530...