Page 291
ASCII Mode Communications Appendix B B–8 0000000004000000 [CAS] control gain switching function 0400000000000000 [MI3] General-purpose input 3 0000000008000000 [UP] remote control increment speed 0800000000000000 [MI4] General-purpose input 4 0000000010000000 [DWN] remote control decrement speed 1000000000000000 [MI5] General-purpose input 5 0000000020000000 [UDC] remote control clear up/down 2000000000000000 [MI6] General-purpose input 6 0000000040000000 [OPE] Forcible operation 4000000000000000 [MI7]...
Page 292
SJ7002 Inverter Appendix B B–9 The arrangement of the terminal assignment data permits you to assign all inputs in a single command. The example below shows a transmission to the inverter at address Node 1 to set the Forward command, Multi-sp eed 1 and Multi-speed 2. Command – 03The 03 command reads the monitor data as a single block. The frame format of command 03 follows the diagram and specification table. The transmit frame has no data field. The receive frame has a 104-byte data field,...
Page 293
ASCII Mode Communications Appendix B B–10 The data in the receive frame contains 8-byte values for 13 items, listed in the table below: The eight bytes for intelligent inpu t or intelligent output data have a bit set in the data field for each I/O point that is ON, according to the following table: No.Monitor ItemUnitsMultiplierData SizeNotes 1 Output frequency Hz 100 8 bytes Dec. ASCII code 2 Output current A 10 8 bytes Dec. ASCII code 3 Direction of rotati on — — 8 bytes 0 = Stop 1 = FWD 2 = REV 4...
Page 294
SJ7002 Inverter Appendix B B–11 Command – 04The 04 command reads the status of the inverter. The frame format of command 04 follows the diagrams and specification tables. The transmit frame has no data field. The receive frame has an 8-byte data field, containing values for three trip items (plus a reserved field). Trip data is organized as shown. The table below lists the codes and their meanings. ElementDescriptionSizeVa l u e STX Control code (STart of TeXt) 1 byte STX (0x02) Node Node...
Page 295
ASCII Mode Communications Appendix B B–12 Command – 05The 05 command reads the inverter’s trip history. The frame format of command 05 follows the diagrams and specification tables. The transmit frame has no data field. The receive frame has a 440-byte data field. This consists of an 8-byte total accumulated number of trip events, followed by six 72-byte strings for the six most recent trip events as shown below. The nine bytes of data for each trip event histor y is listed below. The data...
Page 296
SJ7002 Inverter Appendix B B–13 For Command 05, bytes 2, 3, and 4 of the event history are status codes A, B, and C, respectively. The tables below provide status code descriptions. CodeStatus A DefinitionStatus C Definition 00 Initial status On reset 01 —On stopping 02 On Stopping On deceleration 03 On running Constant speed 04 On free-run stop On acceleration 05 On jog On 0 Hz running 06 On dynamic braking On running 07 On retry On dynamic braking 08 On trip On overload restriction 09 On...
Page 297
ASCII Mode Communications Appendix B B–14 Command – 06The 06 command reads a single parameter value from the inverter, which is specified by the data field this read command. The receive frame includes an ACK (acknowledge) character, followed by an 8-byte data field. Use the codes in the table below to return parameters for H003 and H203 (motor capacity selection). ElementDescriptionSizeVa l u e STX Control code (STart of TeXt) 1 byte STX (0x02) Node Node (station) address of inverter 2 bytes 01 to...
Page 298
SJ7002 Inverter Appendix B B–15 Command – 07The 07 command sets a parameter value equal to the value specified in the transmission. The frame format of command 07 follows the diagram and specification table. Note that the parameter F001, the output frequency, can be set more directly with host command 01 instead of with this command. Use the codes in the following table for setting parameters associated with H003 and H203. ElementDescriptionSizeVa l u e STX Control code (STart of TeXt) 1 byte STX...
Page 299
ASCII Mode Communications Appendix B B–16 Command – 08The 08 command initializes the inverter parameters to the factory default values. First, you must set B84 (use command 07) to specify whethe r you want to clear the trip history at the same time. Also, set B85 to specify the country code for th e initialization (use command 07). The frame format of command 08 follows the diagram and specification table. Command – 09The 09 command verifies whether or not it is possible to set a particular...
Page 300
SJ7002 Inverter Appendix B B–17 Command – 0AThe 0A command sets a value in the EEPROM. The frame format of command 0A follows the diagram and specification table. Command – 0BThe 0B command recalculates the inverter’s internal motor constants. Use this function after the base frequency or any Hxxx parameters are changed via the serial link commands. The frame format of command 0B follows the diagram and specification table. ElementDescriptionSizeVa l u e STX Control code (STart of TeXt) 1 byte STX...