Page 331
ModBus Data Listing Appendix B B–48 A261 H Frequency upper limit setting, 2nd motor R/W Sets a limit on output frequency less than the maximum frequency (A004) 224Fh 08783 0, 50 to 400000.01 Hz A261 L R/W 2250h 08784 A062 H Frequency lower limit setting R/W Sets a limit on output frequency greater than zero 1251h 04689 0, 50 to 400000.01 Hz A062 L R/W 1252h 04690 A262 H Frequency lower limit setting, 2nd motor R/W Sets a limit on output frequency greater than zero 2251h 08785 0, 50 to 400000.01...
Page 332
SJ7002 Inverter Appendix B B–49 A076 — PV source setting R/W 00 . [OI] (current input)01 . [O] (voltage input) 02 . Communication input 03 . Pulse train freq. input 10 . Calculate function output1264h 04708 0 to 3, 10 — A077 — Reverse PID action R/W 00 . PID input = SP – PV (normal) 01 . PID input = –(SP – PV) (reverse)1265h 04709 0, 1 — A078 — PID output limit R/W Range is 0.0 to 100.0 1266h 04710 0 to 1000 0.1 sec. A079 — PID feed forward select R/W 00 . Disable 01 . [O] (voltage input) 02...
Page 333
ModBus Data Listing Appendix B B–50 — (Reserved)——3271h to 330Bh 12913 to 13067 —— A094 — Select method to switch to Acc2/Dec2 profile R/W 00 ..[2CH] terminal input 01 ..transition frequency 02 ..when motor direction reverses 1278h 04728 0, 1, 2 — A294 — Select method to switch to Acc2/Dec2, 2nd motor R/W 00 ..[2CH] terminal input 01 ..transition frequency 02 ..when motor direction reverses 2273h 08819 0, 1, 2 — A095 H Acc1 to Acc2 frequency transition point R/W Output frequency at...
Page 334
SJ7002 Inverter Appendix B B–51 — (Reserved)——1288h to 128Ch 04744 to 0448 —— A111 H [O2]–[L] input active range start frequency R/W Output frequency corre- sponding to the bipolar voltage input range starting point 128Dh 04749 -40000 to 400000.01 Hz A111 L R/W128Eh 04750 A112 H [O2]–[L] input active range end frequency R/W Output frequency corre- sponding to the bipolar voltage input range ending point 128Fh 04751 -40000 to 400000.01 Hz A112 L R/W1290h 04752 A113 — [O2]–[L] input active...
Page 335
ModBus Data Listing Appendix B B–52 A145 H ADD frequencyR/W 0.00 to 99.99, 100.0 to 400.0 (Hz) 12B3h 04787 0 to 40000 0.01 Hz A145 L R/W12B4h 04788 A146 — ADD direction select R/W 0 0 ..Plus (adds A145 value to output frequency) 01 ..Minus (subtracts A145 value from output freq.) 12B5h 04789 0, 1 — — (Reserved) ——12B6h to 12B8h 04790t o 04792 —— A150 — EL-S curve acceleration ratio 1 R/W Range is 0. to 50. 12B9h 04793 0 to 50 1 % A151 — EL-S curve acceleration ratio 2 R/W Range is 0....
Page 336
SJ7002 Inverter Appendix B B–53 B003 — Retry wait time before motor restart R/W Time delay after a trip condition goes away before the inverter restarts the motor 1303h 04867 3 to 1000 0.1 sec. B004 — Instantaneous power failure / under-voltage trip alarm enable R/W 00 . Disable 01 . Enable 02 . Disable during stop and ramp to stop 1304h 04868 0, 1, 2 — B005 — Number of restarts on power failure / under- voltage trip events R/W 00 . Restart 16 times 01 . Always restart 1305h 04869 0, 1 — B006...
Page 337
ModBus Data Listing Appendix B B–54 B313 — Electronic thermal charac-teristic, 3rd motor R/W 00 . Reduced torque 01 . Constant torque 02 . Free-setting 330Dh 13069 0, 1, 2 — — (Reserved) — — 330Eh to 3506h 13070 to 13574 —— B015 — Free setting, electronic thermal frequency (1) R/W Data point coordinates for Hz axis (horizontal) in the free-form curve 1310h 04880 0 to 400 1 Hz B016 — Free setting, electronic thermal current (1) R/W Data point coordinates for Ampere axis (vertical) in the...
Page 338
SJ7002 Inverter Appendix B B–55 B029 — Scan time constant for active freq. matching R/W 10 to 3000 131Eh 04894 0.01 sec. 0.01 sec. B030 — Restart freq. select for active freq. matching R/W 00 . Frequency at last shutoff 01 . Maximum frequency 02 . Set frequency 131Fh 04895 B031 — Software lock mode selec- tion R/W 00 . Low-level access, [SFT] input blocks all edits 01 . Low-level access, [SFT] input blocks edits (except F001 and Multi-speed parameters) 02 . No access to edits 03...
Page 339
ModBus Data Listing Appendix B B–56 B042 — Torque limit (2) (reverse-regenerating in 4-quadrant mode) R/W 0. to 200. (%), no (disable torque limit) 132Ch 04908 0 to 200, 255= (no)1 % B043 — Torque limit (3) (reverse- driving in 4-quadrant mode) R/W 0. to 200. (%), no (disable torque limit) 132Dh 04909 0 to 200, 255= (no)1 % B044 — Torque limit (4) (forward- regenerating in 4-quadrant mode) R/W 0. to 200. (%), no (disable torque limit) 132Eh 04910 0 to 200, 255= (no)1 % B045 — Torque limit...
Page 340
SJ7002 Inverter Appendix B B–57 B064 — [OI] input min. limit level of window comparator R/W 0. to 100. (%) Lower limit = B063 – B066 / 2 1343h 04931 0 to 100 1 % B065 — [OI] input hysteresis width of window comparator R/W 0. to 10. (%) Lower limit = B063 – B064 / 2 1344h 04932 0 to 10 1 % B066 — [O/OI/O2] input maximum limit level of window comparator R/W –100. to 100. (%) Lower limit = B067 + B068 / 2 1345h 04933 0 to 100 1 % B067 — [O/OI/O2] input minimum limit level of window comparator R/W –100....