Hitachi Sj7002 Owners Manual
Here you can view all the pages of manual Hitachi Sj7002 Owners Manual. The Hitachi manuals for Inverter are available online for free. You can easily download all the documents as PDF.
Page 321
ModBus Data Listing Appendix B B–38 D081 —Trip monitor 1 R Factor code 0012h 00018 (see codes in next table)— R Inverter status 0013h 00019 — R Frequency (high) 0014h 00020 0 to 40000 0.01 Hz R Frequency (low) 0015h 00021 R Current 0016h 00022 — 0.1 A R Voltage 0017h 00023 — 1 V R Run time (high) 0018h 00024 — 1 hour R Run time (low) 0019h 00025 R ON time (high) 001Ah 00026 — 1 hour R ON time (low) 001Bh 00027 D082 — Trip monitor 2 R Factor code 001Ch 00028 (see codes in next table)— R Inverter status...
Page 322
SJ7002 Inverter Appendix B B–39 D084 — Trip monitor 4R Factor code0030h 00048 (see codes in next table)— R Inverter status 0031h 00049— R Frequency (high) 0032h 00050 0 to 40000 0.01 Hz R Frequency (low) 0033h 00051 R Current 0034h 00052 — 0.1 A R Voltage 0035h 00053 — 1 V R Run time (high) 0036h 00054 — 1 hour R Run time (low) 0037h 00055 R ON time (high) 0038h 00056 — 1 hour R ON time (low) 0039h 00057 D085 — Trip monitor 5 R Factor code003Ah 00058 (see codes in next table)— R Inverter status 003Bh...
Page 323
ModBus Data Listing Appendix B B–40 Note 1:Assume that the inverter current rating is 1000 (for D002). Note 2: When the value is 10000 (100.0 seconds), a value in the second decimal place is ignored. — — Write to EEPROM W 00 . Motor constant calculation 01 . Set data storage in EEPROM Other... Motor constant recalcu- lation and set data storage in EEPROM 0900h 02304 0000, 0001, other — — (Reserved) ——0901h to 1000h 02305 to 4096 —— D102 — DC voltage monitoring Displays the DC Bus voltage 1026h...
Page 324
SJ7002 Inverter Appendix B B–41 Trip Factor Code, HIGH orderTrip Factor Code, LOW order (inverter status) CodeNameCodeName 0 No trip 0 Reset 1 Over current event while at constant speed 1Stop 2 Over current event during deceleration 2 Deceleration 3 Over current event during acceleration 3 Constant speed 4 Over current event during other condi- tions 4 Acceleration 5 Overload protection 5 Run Command active with 0 Hz speed reference 6 Braking resistor overload 6 Starting 7 Over voltage protection 7...
Page 325
ModBus Data Listing Appendix B B–42 Holding Registers, “F” Group Main Profile Parameters Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. F001 H Output frequency setting R/W Standard default target frequency that deter- mines constant motor speed (when A001 = 03)0001h 00001 0 to 40000 0.01 Hz F001 L R/W 0002h 00002 F002 H Acceleration (1) time setting R/W Standard default acceler- ation 1103h 04355 1 to 3600000.01 sec. F002 L R/W 1104h 04356 F202 H Acceleration (1) time setting,...
Page 326
SJ7002 Inverter Appendix B B–43 Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. A001 — Frequency source setting R/W 00 . Keypad potentiometer 01 . Control terminal 02 . Function F001 setting 03 . RS485 serial command 04 . Expansion board #1 05 . Expansion board #2 06 . Pulse train input 07 . Easy sequence 10 . Caltulate function input1201h 04609 00 to 07, 10— A002 — Run command source setting R/W 01 . Input [FW] or [RV] 02 ....
Page 327
ModBus Data Listing Appendix B B–44 — (Reserved)——1207h to 120Ah 04614 to 04618 —— A011 H [O]–[L] input active range start frequency R/W The output frequency corre- sponding to the voltage input range starting point 120Bh 04619 0 to 40000 0.01 Hz A011 L 120Ch 04620 A012 H [O]–[L] input active range end frequency R/W The output frequency corre- sponding to the voltage input range ending point 120Dh 04621 0 to 40000 0.01 Hz A012 L 120Eh 04622 A013 — [O]–[L] input active range start voltage R/W The...
Page 328
SJ7002 Inverter Appendix B B–45 A024 H Multi-speed 4 setting R/W Defines nth additional speed 121Eh 04638 0 or start freq. to max. freq. 0.01 Hz A024 L 121Fh 04639 A025 H Multi-speed 5 setting R/W Defines nth additional speed 1220h 04640 0 or start freq. to max. freq. 0.01 Hz A025 L 1221h 04641 A026 H Multi-speed 6 setting R/W Defines nth additional speed 1222h 04642 0 or start freq. to max. freq. 0.01 Hz A026 L 1223h 04643 A027 H Multi-speed 7 setting R/W Defines nth additional speed 1224h 04644 0...
Page 329
ModBus Data Listing Appendix B B–46 A039 — Jog stop modeR/W 00 ..Free-run stop, jogging disabled during motor run 01 ..Controlled deceleration, jogging disabled during motor run 02 ..DC braking to stop, jogging disabled during motor run 03 ..Free-run stop, jogging always enabled 04 ..Controlled deceleration, jogging always enabled 05 ..DC braking to stop, jogging always enabled 1239h 04665 0 to 5 — — (Reserved) ——123Ah 04666 — — A041 — Torque boost method...
Page 330
SJ7002 Inverter Appendix B B–47 — (Reserved)——323Fh to 326Ch 12863 to 12908 —— A045 — V/f gain setting R/W Sets voltage gain of the inverter 123Fh 04671 20 to 200 1 % A046 — Automatic torque boost voltage gain R/W Voltage compensation gain for automatic torque boost 1240h 04672 0 to 255 1 A246 — Automatic torque boost voltage gain, 2nd motor R/W Voltage compensation gain for automatic torque boost 2240h 08768 0 to 255 1 A047 — Automatic torque boost slip gain R/W Slip compensa tion gain for...