ModBus Data Listing
Appendix B
B–38
D081 —Trip monitor 1 R Factor code 0012h 00018 (see codes in 
next table)—
R Inverter status 0013h 00019 —
R Frequency (high) 0014h 00020 0 to 40000 0.01 Hz
R Frequency (low) 0015h 00021
R Current 0016h 00022 — 0.1 A
R Voltage 0017h 00023 — 1 V
R Run time (high) 0018h 00024 — 1 hour
R Run time (low) 0019h 00025
R ON time (high) 001Ah 00026 — 1 hour
R ON time (low) 001Bh 00027
D082 —
Trip monitor 2 R Factor code 001Ch 00028 (see codes in 
next table)—
R Inverter status...

Page 322

SJ7002 Inverter
Appendix B
B–39
D084 — Trip monitor 4R Factor code0030h 00048 (see codes in 
next table)—
R Inverter status 0031h 00049—
R Frequency (high) 0032h 00050 0 to 40000 0.01 Hz
R Frequency (low) 0033h 00051
R Current 0034h 00052 — 0.1 A
R Voltage 0035h 00053 — 1 V
R Run time (high) 0036h 00054 — 1 hour
R Run time (low) 0037h 00055
R ON time (high) 0038h 00056 — 1 hour
R ON time (low) 0039h 00057
D085 — Trip monitor 5 R Factor code003Ah 00058 (see codes in 
next table)—
R Inverter status 003Bh...

Page 323

ModBus Data Listing
Appendix B
B–40
Note 1:Assume that the inverter current rating is 1000 (for D002).
Note 2: When the value is 10000 (100.0 seconds),  a value in the second decimal place is 
ignored.
— — Write to EEPROM W 00 . Motor constant calculation 01 .  Set data storage in 
EEPROM
Other... Motor constant recalcu-
lation and set data storage in 
EEPROM 0900h 02304 0000,
0001,
other —
— (Reserved) ——0901h 
to 
1000h 02305 
to 
4096 ——
D102 — DC voltage monitoring Displays the DC Bus voltage 1026h...

Page 324

SJ7002 Inverter
Appendix B
B–41
Trip Factor Code, HIGH orderTrip Factor Code, LOW order (inverter status)
CodeNameCodeName
0 No trip 0 Reset
1 Over current event while at constant  speed 1Stop
2 Over current event during  deceleration 2 Deceleration
3 Over current event during acceleration 3 Constant speed
4 Over current event during other condi- tions 4 Acceleration
5 Overload protection 5 Run Command active with 0 Hz speed  reference
6 Braking resistor  overload 6 Starting
7 Over voltage protection 7...

Page 325

ModBus Data Listing
Appendix B
B–42
Holding Registers, “F” Group Main Profile Parameters
Func. CodeNameR/WDescription
Network Data
RegisterRangeRes.hexdec.
F001 H Output frequency setting R/W Standard default target  frequency that deter-
mines constant motor 
speed (when A001 = 03)0001h 00001 0 to 40000 0.01 Hz
F001 L R/W 0002h 00002
F002 H Acceleration (1) time  setting R/W Standard default acceler-
ation 1103h 04355 1 to 
3600000.01 sec.
F002 L R/W 1104h 04356
F202 H Acceleration (1) time  setting,...

Page 326

SJ7002 Inverter
Appendix B
B–43
       
Holding Registers, “A” Group  Standard Functions
Func. CodeNameR/WDescription
Network Data
RegisterRangeRes.hexdec.
A001 — Frequency source setting R/W 00 . Keypad potentiometer 01 . Control terminal
02 . Function F001 setting
03 . RS485 serial command
04 . Expansion board #1
05 . Expansion board #2
06 . Pulse train input
07 . Easy sequence
10 . Caltulate function input1201h 04609 00 to 07, 
10—
A002 — Run command source  setting R/W 01 . Input [FW] or [RV]
02 ....

Page 327

ModBus Data Listing
Appendix B
B–44
— (Reserved)——1207h 
to 
120Ah 04614 
to 
04618 ——
A011 H [O]–[L] input active range  start frequency R/W The output frequency corre-
sponding to the voltage input 
range starting point 120Bh 04619 0 to 40000 0.01 Hz
A011 L 120Ch 04620
A012 H [O]–[L] input active range  end frequency R/W The output frequency corre-
sponding to the voltage input 
range ending point 120Dh 04621 0 to 40000 0.01 Hz
A012 L 120Eh 04622
A013 — [O]–[L] input active range  start voltage R/W The...

Page 328

SJ7002 Inverter
Appendix B
B–45
A024 H Multi-speed 4 setting R/W Defines nth additional speed 121Eh 04638 0 or start freq. to 
max. freq. 0.01 Hz
A024 L 121Fh 04639
A025 H Multi-speed 5 setting R/W Defines nth additional speed 1220h 04640 0 or start  freq. to 
max. freq. 0.01 Hz
A025 L 1221h 04641
A026 H Multi-speed 6 setting R/W Defines nth additional speed 1222h 04642 0 or start  freq. to 
max. freq. 0.01 Hz
A026 L 1223h 04643
A027 H Multi-speed 7 setting R/W Defines nth additional speed 1224h 04644 0...

Page 329

ModBus Data Listing
Appendix B
B–46
A039 — Jog stop modeR/W 00 ..Free-run stop, jogging
      disabled during motor run
01 ..Controlled deceleration,
      jogging disabled during
      motor run
02 ..DC braking to stop,
      jogging  disabled during
      motor run
03 ..Free-run stop, jogging
      always enabled
04 ..Controlled deceleration,
      jogging always enabled
05 ..DC braking to stop,
      jogging  always enabled 1239h 04665 0 to 5 —
— (Reserved) ——123Ah 04666 — —
A041 — Torque boost method...

Page 330

SJ7002 Inverter
Appendix B
B–47
— (Reserved)——323Fh 
to 
326Ch 12863 
to 
12908 ——
A045 — V/f gain setting R/W Sets voltage gain of the 
inverter 123Fh 04671 20 to 200 1 %
A046 — Automatic torque boost  voltage gain R/W Voltage compensation gain 
for automatic  torque boost 1240h 04672 0 to 255 1
A246 — Automatic torque boost  voltage gain, 2nd motor R/W Voltage compensation gain 
for automatic  torque boost 2240h 08768 0 to 255 1
A047 — Automatic torque boost  slip gain R/W Slip compensa
tion gain for...