Hitachi Sj7002 Owners Manual
Here you can view all the pages of manual Hitachi Sj7002 Owners Manual. The Hitachi manuals for Inverter are available online for free. You can easily download all the documents as PDF.
Page 351
ModBus Data Listing Appendix B B–68 H034 H Auto constant J, 1st motor R/W 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000 to 9999.152Ch 05420 1 to 99990000.001 H034 L R/W 152Dh 05421 H234 H Auto constant J, 1st motor R/W 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000 to 9999.252Ch 09516 1 to 99990000.001 H234 L R/W 252Dh 09517 — (Reserved) — — 152Eh to 153Ch 05422 to 05436 —— H050 — PI proportional gain for 1st motor R/W 0.0 to 999.9, 1000. 153Dh 05437 0 to 10000 0.1 % H250 — PI...
Page 352
SJ7002 Inverter Appendix B B–69 Use the codes in the table below to return parameters for H003 and H203 (motor capacity selection). H073 — Gain switching time R/W 0. to 999. (milliseconds) 155 4h 05460 0 to 9999 1 msec. — (Reserved) — — 1555h to 1600h 05461 to 05632 —— Holding Registers, “H” Group Motor Constants Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Code Data0001020304050607080910 Japan or U.S.A. mode (B085 = 00 or 02) 0.2 kW — 0.4 — 0.75 — 1.5 2.2 — 3.7 — EU...
Page 353
ModBus Data Listing Appendix B B–70 Holding Registers, “P” Group Expansion Card Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. P001 — Operation mode on expan- sion card 1 error R/W 00 ..Trip (stop motor) 01 ..Continuous operation 1601h 05633 0, 1 — P002 — Operation mode on expan- sion card 2 error R/W 00 ..Trip (stop motor) 01 ..Continuous operation 1602h 05634 0, 1 — — (Reserved) — — 1603h to 160Ah 05635 to 05642 —— P011 — Encoder pulse-per-revolu- tion (PPR) setting...
Page 354
SJ7002 Inverter Appendix B B–71 P028 — Numerator of motor gear ratio R/W 0. to 9999. 161Ch 05660 1 to 9999 1 P029 — Denominator of motor gear ratio R/W 1 to 9999 161Dh 05661 1 to 9999 1 — (Reserved) — — 161Eh 05662 — — P031 — Accel/decel time input selection R/W 00 . Inverter 01 . Expansion card 1 02 . Expansion card 2 161Fh 05663 0, 1, 2 — P032 — Positioning command input selection R/W 00 . Inverter 01 . Expansion card 1 02 . Expansion card 2 1620h 05664 0, 1, 2 — P033 — Torque command input...
Page 355
ModBus Data Listing Appendix B B–72 P047 — DeviceNet polled I/O: Input instance number R/W 70, 71, 101 1631h 05681 70, 71, 101— P048 — Inverter action on DeviceNet idle mode R/W 00 ..Trip 01 ..Decelerate and trip 02 ..Hold last speed 03 ..Free run stop 04 ..Decelerate and stop 1632h 05682 0 to 4 — P049 — Motor poles setting for RPM R/W 00 to 38 (even numbers only) 1633h 05683 0 to 19 1 = 2poles — — (Reserved) — — 1634h to 1638h 05684 to 05688 —— P055 — Pulse train frequency span R/W 1.0 to 50.0...
Page 356
SJ7002 Inverter Appendix B B–73 P070 — Low speed homing frequency R/W 0.00 to 10.00 (Hz) 1650h 05712 0 to 1000 0.01 Hz P071 — High speed homing frequency R/W 0.00 to 99.99 / 100.0 to maximum frequency setting, 1st motor (Hz) 1651h 05713 0 to 40000 0.01 Hz P072 H Forward position range setting R/W 0 to 536870912 (when P012 = 02), 0 to 2147483647 (when P013 = 03) (upper four digits) 1652h 05714 See descrip- tion 1 P072 L R/W 1653h 05715 P073 H Reverse position range R/W 0 to 536870912 (when P012 =...
Page 357
ModBus Data Listing Appendix B B–74 P116 — Easy sequence parameter (U16) R/W 0. to 9999., 1000 to 6553 (10000 to 65535) 1676h 05750 0 to 65530 1 P117 — Easy sequence parameter (U17) R/W 0. to 9999., 1000 to 6553 (10000 to 65535) 1677h 05751 0 to 65530 1 P118 — Easy sequence parameter (U18) R/W 0. to 9999., 1000 to 6553 (10000 to 65535) 1678h 05752 0 to 65530 1 P119 — Easy sequence parameter (U19) R/W 0. to 9999., 1000 to 6553 (10000 to 65535) 1679h 05753 0 to 65530 1 P120 — Easy sequence parameter...
Page 358
Drive Parameter Settings Tables In This Appendix....page — Introduction....................................................................................... 2 — Parameter Settings for Keypad Entry............................................... 2 C Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Page 359
Introduction Appendix C C–2 Introduction This appendix lists the user-programmable parameters for the SJ7002 series inverters and the default values for European, U. S. and Japanese product types. The right-most column of the tables is blank so you can record values you have changed from the default. This involves just a few parameters for most applications. Parameter Settings for Keypad Entry SJ7002 series inverters provide many functions an d parameters that can be configured by the user. We...
Page 360
SJ7002 Inverter Appendix C C–3 Standard Functions “A” Group ParametersDefault Setting User Setting Func. CodeNameFEF2, FE2 (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan) A001 Frequency source setting 01 01 02 A002 Run command source setting 01 01 02 A003 Base frequency setting 50. 60. 60. A203 Base frequency setting, 2nd motor 50. 60. 60. A303 Base frequency setting, 3rd motor 50. 60. 60. A004 Maximum frequency setting 50. 60. 60. A204 Maximum frequency setting, 2nd motor 50. 60. 60. A304 Maximum frequency...