Page 251
Troubleshooting Troubleshooting and Maintenance 6–4 The motor speed will not reach the target frequency (desired speed). • If using the analog input, is there current or voltage at [O] or [OI]? • Check the wiring. • Check the potentiometer or signal generating device. • Is the load too heavy? •Reduce the load. • Heavy loads activate the overload restriction feature (reduces output as needed). • Is the inverter internally limiting the output frequency? • Check max frequency setting (A004) • Check...
Page 252
SJ7002 Inverter Troubleshooting and Maintenance 6–5 Monitoring Trip Events, History, & Conditions Fault Detection and ClearingThe microprocessor in the inverter detects a variety of fault conditions and captures the event, recording it in a history ta ble. The inverter output turns OFF, or “trips” similar to the way a circuit breaker trips due to an over-current condition. Most faults occur when the motor is running (refer to the diagram to the right). However, the inverter could have an internal...
Page 253
Monitoring Trip Events, History, & Conditions Troubleshooting and Maintenance 6–6 Error CodesAn error code will appear on the display automati cally when a fault causes the inverter to trip. The following table lists the cause associated with the error. OPE / SRW DisplayNameDescriptionTroubleshooting and Corrective Action E0 1.-Over-current protection If the motor is constrained or suddenly accelerated or decelerated, a high current will flow in the inverter and the inverter may fail. To avoid...
Page 254
SJ7002 Inverter Troubleshooting and Maintenance 6–7 Note 1: The inverter will not accept any reset command within about 90 seconds after tripping (i.e., after the prot ective function operates). Be sure to turn OFF the input power supply after waiting two minutes for cooling. Note 2: The inverter will not accept any reset co mmand after an EEPROM error occurs with error code displayed. Turn off the inverter power once. If error code E08 is displayed when the inverter power is turned on subs...
Page 255
Monitoring Trip Events, History, & Conditions Troubleshooting and Maintenance 6–8 Note 5: The inverter will not accept reset commands input via the [RS] terminal or entered by the STOP/RESET key. Therefore, turn off the inverter power. OPE / SRW DisplayNameDescriptionTroubleshooting and Corrective Action E 1 1.-CPU error (*5) If the internal CPU malfunctions or an error occurs in it, the inverter will shut OFF its output and display the error code shown on the left. Note: Reading abnormal data from...
Page 256
SJ7002 Inverter Troubleshooting and Maintenance 6–9 OPE / SRW DisplayNameDescriptionTroubleshooting and Corrective Action E23.-Gate array communica- tion error If an error occurs in the communication between the internal CPU and gate array, the inverter will trip.•Check for the noise sources located near the inverter (remove noise sources). •Check whether the communication cable has been disconnected (check the connec- tors). GA.COM E24.-Phase loss input protec- tion When the phase loss input...
Page 257
Monitoring Trip Events, History, & Conditions Troubleshooting and Maintenance 6–10 Note 6: The inverter will not accept reset commands input via the RS terminal or entered by the STOP/RESET key. Therefore, turn off the inverter power. Note 7: The inverter applied for 004 to 110L/H will not accept reset commands input via the RS terminal or entered by the STOP/RESET key. Therefore, turn off the inverter power. Note 8: The inverter will not accept the reset co mmand entered from the digital operator....
Page 258
SJ7002 Inverter Troubleshooting and Maintenance 6–11 Expansion Card Error CodesThe inverter monitors the operation of the expansion cards (optional) that may be installed in the expansion bay. On the inverter’s digital operator, error codes in the E60 range refer to the upper card position. Error codes in the E70 range refer to the lower card position. For the remote operator display, error codes are in the OP1 or OP2 ranges, respectively. If an error occurs, the inverter trips (displays the...
Page 259
Monitoring Trip Events, History, & Conditions Troubleshooting and Maintenance 6–12 Digital Input Card – Use the following table to diagnose errors caused by a digital input expansion card. Each error will cause the inverter to trip, turning OFF its output and displaying an error code. The input mode is determined by a combination of DIP switch and rotary switch settings. If the expansion card does not operate normally, use the following table to check the DIP switch and rotary switch settings. The...
Page 260
SJ7002 Inverter Troubleshooting and Maintenance 6–13 DeviceNet Expansion Card – Use the following table to diagnose errors caused by a DeviceNet expansion card. Each er ror will cause the inverter to trip (according to parameter settings P045 and P048), turning OFF it s output and displaying an error code. If the expansion card does not operate normally, use the following diagrams to check the DIP switch settings. For more details, refer to the expansion card instruction manual. DeviceNet Expansion...