Page 231
Setting Motor Constants for Vector Control Operations and Monitoring 4–70 The inverter has three separate motor constant sets named 1st, 2nd, and 3rd. The 1st motor constant set is the default, while the SET and SET2 intelligent inputs select the 2nd and 3rd constant sets, respectively. The torque control methods are valid to use only if a particular motor constant set includes parameters for th e selected control method. The following table lists the vector control methods and shows the ones...
Page 232
SJ7002 Inverter Operations and Monitoring 4–71 Auto-tuning of Motor ConstantsThe SJ7002 inverter features auto-tuning, which detects and records the motor characteristic parameters to use in all vector control mode s. Auto-tuning determines the resistance and inductance of motor windings. Therefore, the moto r must be connected to the inverter for this procedure. Note that the auto-tuning feature is not associated with PID loop operation, which is common on some control devices. The auto-tuning...
Page 233
Setting Motor Constants for Vector Control Operations and Monitoring 4–72 Preparation for Auto-tuning Procedure – Be sure to study the preparation items and verify the related inverter configuration befo re going further in this procedure. 1. Adjust the motor base frequency (A003) and th e motor voltage selection (A082) to match the specifications of the motor used in the auto-tuning procedure. 2. Verify that the motor is not more than one fra me size smaller than the rated size for he inverter....
Page 234
SJ7002 Inverter Operations and Monitoring 4–73 If the auto-tuning procedure is successful, the inverter updates the motor characteristic parameters and indicates normal termi- nation of the procedure as shown. Pressing any key on the keypad will clear the result from the display. Trip during auto-tuning – A trip event will cause the auto- tuning sequence to quit . The display will show the error code for the trip rather than the ab normal termination indication. After eliminating the cause of the...
Page 235
Setting Motor Constants for Vector Control Operations and Monitoring 4–74 Manual Setting of Motor ConstantsWith vector control, the inverter uses the output current, output voltage, and motor constants to estimate the motor torque and speed. It is possibl e to achieve a high starting torque and accurate speed control at low frequency Sensorless Vector Control – improved torque control at output frequencies down to 0.5 Hz. Use A044=03 (1st motor) or A244=03 (2nd motor) to select sensorless vector...
Page 236
SJ7002 Inverter Operations and Monitoring 4–75 PID Loop Operation In standard operation, the inverter uses a refe rence source selected by parameter A001 for the output frequency, which may be a fixed value (F 001), a variable set by the front panel potenti- ometer, or value from an analog input (voltage or current). To enable PID operation, set A071 = 01. This causes the inverter to calculate the target frequency, or setpoint. An optional intelligent input assignment (code 23), PID Disable, will...
Page 237
Configuring the Inverter for Multiple Motors Operations and Monitoring 4–76 Configuring the Inverter for Multiple Motors Simultaneous ConnectionsFor some applications, you may need to connect two or more motors (wired in parallel) to a single inverter’s output. For example, this is common in conveyor applications where two separate conveyors need to have approximatel y the same speed. The use of two motors may be less expensive than making the mechanical link for one motor to drive multiple...
Page 238
SJ7002 Inverter Operations and Monitoring 4–77 Parameters for the second motor and third motors have function codes of the form x2xx and x3xx respectively. They appear immediately after the first motor’s parameter in the menu listing order. The following table lists the pa rameters that have the second/third parameter registers for programming. Function Name Parameter Codes 1st motor2nd motor3rd motor Acceleration time setting (Acceleration 1) F002 F202 F302 Deceleration time setting (Deceleration 1)...
Page 239
Configuring the Inverter for Multiple Motors Operations and Monitoring 4–78 Motor constant J setting (Standard, Auto tuning) H024/H034 H224/H234 — PI proportional gain H050 H250 — P proportional gain setting H052 H252 — 0Hz SLV limit for 1st motor H060 H260 — Function Name Parameter Codes 1st motor2nd motor3rd motor Phone: 800.894.0412
Page 240
Inverter System Accessories In This Chapter....page — Introduction....................................................................................... 2 — Component Descriptions.................................................................. 3 — Dynamic Braking....................................................... ........................ 6 5 Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]