Page 191
Using Intelligent Input Terminals Operations and Monitoring 4–30 The figure below shows the operation during an overload restriction event. The overload restriction level is set by B022 and B025. The overl oad restriction constant is the time to decel- erate to 0Hz from maximum frequency. When this fu nction operates, the acceleration time will be longer than the normal acceleration time. NOTE: The Overload Advance Notice function for intelligent outputs is related to Overload Restriction operatio...
Page 192
SJ7002 Inverter Operations and Monitoring 4–31 When the torque limit enable function [TL] is assigned to an intelligent input terminal, torque limiting occurs only when [TL] is ON. Both the 4-quadrant mode and terminal switching mode of torque limiting use input [TL] for enable/disab le. When the [TL] input is OFF, the inverter always uses the default torque control limit of 200% maximum. That torque limit value corre- sponds to 200% of the maximum inverter output current. Therefore, the output...
Page 193
Using Intelligent Input Terminals Operations and Monitoring 4–32 External Brake Control Function The External Brake Control function enables the inverter to control external electromechanical brake systems with a particular safety characteristic. For example, elevator control systems maintain the brake on the load until the drive motor has reached a releasing frequency (point at which the external mechanical brake is released). This ensures that the load does not have an opportunity to begin...
Page 194
SJ7002 Inverter Operations and Monitoring 4–33 The following table lists the parameters related to the External Brake Control function. The diagram below shows the event sequence de scribed in the steps on the previous page. CodeFunctionData or RangeDescription B120 Brake control enable 00=Disable 01=Enable Enables external brake control function within the inverter B121 Brake waiting time for release 0.00 to 5.00 sec. Sets the time delay after arrival at release frequency (B125) before the inverter...
Page 195
Using Intelligent Input Terminals Operations and Monitoring 4–34 Expansion Card Input Signals Other inputs listed below require the expansion card SJ-FB Encoder Fe edback. Please see the SJ-FB manual for more information. The diagram below shows how the Input/Output connections for the SJ–FB feedback board. The inverter’s internal connections and paramete r configuration make these signals available on intelligent input and output terminals. The information on outputs related to the SJ-FB...
Page 196
SJ7002 Inverter Operations and Monitoring 4–35 Force Terminal Mode The purpose of this intelligent input is to allow a device to force the inverter to allow control of the following two parameters via the control terminals: A001 - Frequency source setting (01 = control terminals [FW] and [RV]) A002 - Run command source setting (0 1 = control terminals [O] or [OI]) Some applications will require one or both settings above to use a source other than the terminals. You may prefer to normally use...
Page 197
Using Intelligent Input Terminals Operations and Monitoring 4–36 The following block diagram shows the torque control operation. If the measured speed exceeds the speed limit, the motor speed is controlled in proportional control mode. Clear Cumulative Power Value When D015 cumulative power monitoring functi on is selected, the inverter displays the cumulative value of electric power input to the inverter. You can also convert the value to other engineering units by setting th e related parameter...
Page 198
SJ7002 Inverter Operations and Monitoring 4–37 Speed Servo ON The servo-ON function allows you to set the inve rter in a speed-servo-lock state with an intelligent input during operation. This function is available when A044=05 vector control with sensor for the characteristic V/f curve. To use the servo-ON function, assign option code 54 to an intelligent input. After making the input assignment, the inverter will accept an operation command only when the [SON] terminal is ON. If the [SON]...
Page 199
Using Intelligent Input Terminals Operations and Monitoring 4–38 General Purpose Inputs 1–8 Refer to the Easy Sequence Inst ruction Manual for information on how to configure and use the general purpose inputs MI1 to MI8. Analog Holding Command The analog holding function causes the inve rter to sample and hold the analog command (external analog input). The hol d operation begins when the intelligent input [AHD] (assign option code 65) turns ON. While [AHD] terminal is ON, th e Up/Down...
Page 200
SJ7002 Inverter Operations and Monitoring 4–39 Multi-stage Position Select 1, 2, and 3 Three Multi-stage Position Select inputs are bina ry-encoded to select one of eight settings, P060 to P067. Input [CP1] is the LSB; [CP3] is the MSB. If no position select inputs are assigned, P060 becomes the default position setting. The three multi-stage position select inputs [C F1, [CF2], and [CF3] are binary-encoded. When more than one input changes state to select a position, it is possible that skewing...