Page 171
Connecting to PLCs and Other Devices Operations and Monitoring 4–10 Be sure to keep the control logic wiring separa ted from the power terminal wiring. In the case of model –3150Hxx, the drawing below sh ows how route control circuit wiring. 1. Separate the control circuit wiring into tw o bundles to make use of available space. 2. Route the wiring from the control terminal block to the wiring plate. Continue routing past the PCB attachment plate to the wiring exit area. 3. Secure the control wiring to...
Page 172
SJ7002 Inverter Operations and Monitoring 4–11 Input Terminal ListingUse the following table to locate pages for intelligent input material in this chapter. Intelligent INPUTSIntelligent INPUTS SymbolCodeNamePageSymbolCodeNamePage RV 01 Reverse Run/Stop 4–15 TRQ2 42 Torque limit select, bit 2 (MSB) 4–30 CF1 02 Multi-speed select, Bit 0 (LSB)4–15PPI 43 P / PI mode selection4–26 CF2 03 Multi-speed select, Bit 1 4–15BOK 44 Brake confirmation signal 4–32 CF3 04 Multi-speed select, Bit 24–15ORT 45...
Page 173
Connecting to PLCs and Other Devices Operations and Monitoring 4–12 Output Terminal ListingUse the following table to locate pages for intelligent output material in this chapter. Intelligent OUTPUTSIntelligent OUTPUTS SymbolCodeNamePageSymbolCodeNamePage RUN 00 Run signal 4–44 FBV 31 PID feedback second stage output4–56 FA1 01 Freq. arrival type 1 – constant speed 4–44NDc 32 Network detection signal 4–57 LOG1 33 Logic output 1 4–58 FA2 02 Freq. arrival type 2 – over-frequency 4–44LOG2 34 Logic output...
Page 174
SJ7002 Inverter Operations and Monitoring 4–13 Using Intelligent Input Terminals Intelligent terminals [1], [2], [3], [4], [5], [6 ], [7], and [8] are identical, programmable inputs for general use. The input circuits can use the in verter’s internal (isolated) +24V field supply (P24) to power the inputs. The input circuits conne ct internally to [PLC] as a common point. To use the internal supply to power the inputs, use the jumper as shown. Remove the jumper to use an external supply, or to...
Page 175
Using Intelligent Input Terminals Operations and Monitoring 4–14 Wiring Diagram ConventionsThe input wiring diagrams in this chapter ar e examples only. Default and non-default input terminal assignments are noted th roughout; your particular assignments may be different. The wiring diagrams show the –x FU/–xFR model default [P24]–[P LC] jumper position (U.S./Jpn versions), as shown below on the left. The common (return) for inputs is [CM1] in this case. The diagram on the right shows the default...
Page 176
SJ7002 Inverter Operations and Monitoring 4–15 Forward Run/ Stop and Reverse Run/Stop Commands When you input the Run command via the dedicate d terminal [FW], the inverter executes the Forward Run command (high) or Stop command (low). When you input the Run command via the programmable terminal [RV], the inverter executes the Reverse Run command (high) or Stop command (low). Note the following: When the Forward Run and Reverse Run commands are active at the same time, the inverter enters the...
Page 177
Using Intelligent Input Terminals Operations and Monitoring 4–16 The example with eight speeds in the figure below shows how input switches configured for CF1 – CF3 functions can change the motor speed in real time. Multi-speed Override Feature - The multi-speed function can selectively override the external analog speed reference input. When the Frequency Source Setting parameter A001=01, the control terminal inputs determin e the output frequency. At the same time, the inverter can use...
Page 178
SJ7002 Inverter Operations and Monitoring 4–17 Multi-Speed Select, Bit-level The Bit-level method of speed control uses up to seven intelligent inputs to select from up to ei ght speeds. Since the all-switches-OFF combination selects the first speed, you only need N–1 switches to select N speeds. With Bit- level speed control, only one input is normally active at a time. If multiple switches are ON, the lower numbered input takes precedence (determines the speed). The table and figure below...
Page 179
Using Intelligent Input Terminals Operations and Monitoring 4–18 Jogging Command The Jog input [JG] is used to command the motor to rotate slowly in small increments for manual operation. The speed is limited to 10 Hz. The frequency for the jogging operation is set by parameter A038. Jogging does not use an acceleration ramp. There- fore setting the jogging frequency A038 too high will cause inverter tripping. A jog command may arrive while the motor is running. You can program the inverter to...
Page 180
SJ7002 Inverter Operations and Monitoring 4–19 External Signal for DC Injection Braking When the terminal [DB] is turned ON, the DC braking [DB] feature is enabled (regardless of A051 setting). Set the follow- ing parameters when the external DC braking terminal is to be used: A053 – DC braking delay time setting. The range 0.0 to 5.0 seconds. A054 – DC braking force setting. The range is 0 to 100% for models -004xxx to -1500xxx; 0 to 35% for models -1850xxx to -4000xxx. The scenarios to...