Page 131

“B” Group: Fine-Tuning Functions
Configuring Drive Parameters
3–48
External Brake 
ControlThe brake control function in the inverter contro ls external braking used in systems such as 
elevators. The purpose of this function is to en sure the inverter is powering the motor before 
releasing external brakes that would permit the load to move or coast. This function requires the 
configuration and wiring of intellig ent input and output terminals. See  “
External Brake Control 
Function” on page 4–32 for...

Page 132

SJ7002 Inverter
Configuring Drive Parameters
3–49
Overvoltage  
FunctionsB130/B131: Over-voltage LADSTOP Enable / Over-voltage LADSTOP Level –  The over-
voltage LADSTOP function monitors the DC bu s voltage and actively changes the output 
frequency profile to maintain the DC bus voltage  within settable limits. Although “LAD” refers 
to “linear acceleration / deceleration,” the invert er only “STOPs” the deceleration slope so that 
regenerative voltage will not cause the DC bus to rise enough to cause...

Page 133

“C” Group: Intelligent Terminal Functions
Configuring Drive Parameters
3–50
“C” Group: Intelligent Terminal Functions
The eight input terminals [ 1], [2], [ 3], [4], [ 5], [6], [7],  and [ 8] can be configured for any of 44 
different functions. The next two  tables show how to configure the eight terminals. The inputs 
are logical, in that they are either OFF or  ON. We define these states as OFF=0, and ON=1.
The inverter comes with default options for th e eight terminals. These default settings are...

Page 134

SJ7002 Inverter
Configuring Drive Parameters
3–51
NOTE: An input terminal configured  for option code 18 ([RS] Reset command) cannot be 
configured for normally closed operation.
Intelligent Input 
Terminal 
OverviewEach of the eight intelligent terminals may be assigned any of  the options in the following 
table. When you program one of the option code s for terminal assignments C001 to C008, the 
respective terminal assumes the function role of  that option code. The terminal functions have a 
symbol...

Page 135

“C” Group: Intelligent Terminal Functions
Configuring Drive Parameters
3–52
08 SET Set (select) 2nd Motor  Data Switch from normal (1st) to 2
nd motor parameters for gener-
ating frequency output to motor
09 2CH 2-stage Acceleration and  Deceleration Frequency output uses 2nd-stag
e acceleration and decelera-
tion values
11 FRS Free-run Stop Causes output to turn OFF, allowing motor to free run (coast) 
to stop
12 EXT External Trip At OFF to ON transition, inverter latches trip event and 
displays E12...

Page 136

SJ7002 Inverter
Configuring Drive Parameters
3–53
29 UDC Remote Control Data  Clearing Clears the UP/DWN frequency memo
ry by forcing it to equal 
the set frequency parameter F001. Setting C101 must be 
set=00 to enable this function to work.
31 OPE Operator Control Forces the source of  the output frequency setting (A001) and 
the RUN command (A002) to be from the digital operator 
(F001 and the Run key, respectively)
32 SF1 Multi-speed bit 1 Multi ple speed select, Bit 1
33 SF2 Multi-speed bit 2 Multi...

Page 137

“C” Group: Intelligent Terminal Functions
Configuring Drive Parameters
3–54
55 FOC Current forcing Forces excitation current in motor at 0 speed; for use with V/f 
curve settings A044/A244 = 03, 04, and 05
56 MI1 General-purpose input 1 Easy  sequence function, general input 1
57 MI2 General-purpose input 2 Easy  sequence function, general input 2
58 MI3 General-purpose input 3 Easy  sequence function, general input 3
59 MI4 General-purpose input 4 Easy  sequence function, general input 4
60 MI5...

Page 138

SJ7002 Inverter
Configuring Drive Parameters
3–55
Output Terminal 
ConfigurationThe inverter provides configuration for logic (d iscrete) and analog outputs, shown in the table 
below.
NOTE: *Terminals [11] – [13] or [11] – [14] ar e automatically configured as AC0 – AC2 or
AC0 – AC3 when C62 is configured to enable alarm code output.
The output logic convention is programmable fo r terminals [11] – [15], and the alarm relay 
terminals. The open-collector  output terminals [11] – [15] default to normally...

Page 139

“C” Group: Intelligent Terminal Functions
Configuring Drive Parameters
3–56
Output Summary Table  - This table shows all twenty-two functions for the logic output 
terminals [11] – [15] at a glance. Detailed function descriptions, re lated parameters, settings, 
and example wiring diagrams are in  “
Using Intelligent Output Terminals” on page 4–43.
Output Function Summary Table
Option
CodeTerminal SymbolFunction NameDescription
00 RUN Run signal Inverter is in Run Mode, motor running
01 FA1 Frequency...

Page 140

SJ7002 Inverter
Configuring Drive Parameters
3–57
26 OL2 Overload notice advance  signal (2) Output current is more than the set Threshold 2 for the 
overload signal (set with C111)
27 Odc Analog [O] disconnect  detect Input signal level at terminal [O
] is below threshold (set with  
B070)
28 OIDc Analog [OI] disconnect  detect Input signal level at terminal [OI] is below threshold (set with  
B071)
29 O2Dc Analog [O2] disconnect  detect Input signal level at terminal [O2] is below threshold (set with...