Page 131
“B” Group: Fine-Tuning Functions Configuring Drive Parameters 3–48 External Brake ControlThe brake control function in the inverter contro ls external braking used in systems such as elevators. The purpose of this function is to en sure the inverter is powering the motor before releasing external brakes that would permit the load to move or coast. This function requires the configuration and wiring of intellig ent input and output terminals. See “ External Brake Control Function” on page 4–32 for...
Page 132
SJ7002 Inverter Configuring Drive Parameters 3–49 Overvoltage FunctionsB130/B131: Over-voltage LADSTOP Enable / Over-voltage LADSTOP Level – The over- voltage LADSTOP function monitors the DC bu s voltage and actively changes the output frequency profile to maintain the DC bus voltage within settable limits. Although “LAD” refers to “linear acceleration / deceleration,” the invert er only “STOPs” the deceleration slope so that regenerative voltage will not cause the DC bus to rise enough to cause...
Page 133
“C” Group: Intelligent Terminal Functions Configuring Drive Parameters 3–50 “C” Group: Intelligent Terminal Functions The eight input terminals [ 1], [2], [ 3], [4], [ 5], [6], [7], and [ 8] can be configured for any of 44 different functions. The next two tables show how to configure the eight terminals. The inputs are logical, in that they are either OFF or ON. We define these states as OFF=0, and ON=1. The inverter comes with default options for th e eight terminals. These default settings are...
Page 134
SJ7002 Inverter Configuring Drive Parameters 3–51 NOTE: An input terminal configured for option code 18 ([RS] Reset command) cannot be configured for normally closed operation. Intelligent Input Terminal OverviewEach of the eight intelligent terminals may be assigned any of the options in the following table. When you program one of the option code s for terminal assignments C001 to C008, the respective terminal assumes the function role of that option code. The terminal functions have a symbol...
Page 135
“C” Group: Intelligent Terminal Functions Configuring Drive Parameters 3–52 08 SET Set (select) 2nd Motor Data Switch from normal (1st) to 2 nd motor parameters for gener- ating frequency output to motor 09 2CH 2-stage Acceleration and Deceleration Frequency output uses 2nd-stag e acceleration and decelera- tion values 11 FRS Free-run Stop Causes output to turn OFF, allowing motor to free run (coast) to stop 12 EXT External Trip At OFF to ON transition, inverter latches trip event and displays E12...
Page 136
SJ7002 Inverter Configuring Drive Parameters 3–53 29 UDC Remote Control Data Clearing Clears the UP/DWN frequency memo ry by forcing it to equal the set frequency parameter F001. Setting C101 must be set=00 to enable this function to work. 31 OPE Operator Control Forces the source of the output frequency setting (A001) and the RUN command (A002) to be from the digital operator (F001 and the Run key, respectively) 32 SF1 Multi-speed bit 1 Multi ple speed select, Bit 1 33 SF2 Multi-speed bit 2 Multi...
Page 137
“C” Group: Intelligent Terminal Functions Configuring Drive Parameters 3–54 55 FOC Current forcing Forces excitation current in motor at 0 speed; for use with V/f curve settings A044/A244 = 03, 04, and 05 56 MI1 General-purpose input 1 Easy sequence function, general input 1 57 MI2 General-purpose input 2 Easy sequence function, general input 2 58 MI3 General-purpose input 3 Easy sequence function, general input 3 59 MI4 General-purpose input 4 Easy sequence function, general input 4 60 MI5...
Page 138
SJ7002 Inverter Configuring Drive Parameters 3–55 Output Terminal ConfigurationThe inverter provides configuration for logic (d iscrete) and analog outputs, shown in the table below. NOTE: *Terminals [11] – [13] or [11] – [14] ar e automatically configured as AC0 – AC2 or AC0 – AC3 when C62 is configured to enable alarm code output. The output logic convention is programmable fo r terminals [11] – [15], and the alarm relay terminals. The open-collector output terminals [11] – [15] default to normally...
Page 139
“C” Group: Intelligent Terminal Functions Configuring Drive Parameters 3–56 Output Summary Table - This table shows all twenty-two functions for the logic output terminals [11] – [15] at a glance. Detailed function descriptions, re lated parameters, settings, and example wiring diagrams are in “ Using Intelligent Output Terminals” on page 4–43. Output Function Summary Table Option CodeTerminal SymbolFunction NameDescription 00 RUN Run signal Inverter is in Run Mode, motor running 01 FA1 Frequency...
Page 140
SJ7002 Inverter Configuring Drive Parameters 3–57 26 OL2 Overload notice advance signal (2) Output current is more than the set Threshold 2 for the overload signal (set with C111) 27 Odc Analog [O] disconnect detect Input signal level at terminal [O ] is below threshold (set with B070) 28 OIDc Analog [OI] disconnect detect Input signal level at terminal [OI] is below threshold (set with B071) 29 O2Dc Analog [O2] disconnect detect Input signal level at terminal [O2] is below threshold (set with...