Page 141
“C” Group: Intelligent Terminal Functions Configuring Drive Parameters 3–58 Analog Summary Table - The following tables show all functions available for assignment to the three analog output te rminals [FM], [AM], [AMI] at a glan ce. Detailed descriptions, related parameters, and se ttings are in “ Analog Output Operation” on page 4–66. 56 WCO2 [O2] terminal window comparator [O2] input is within comparator window set by B066 and B067 Output Function Summary Table Option CodeTerminal...
Page 142
SJ7002 Inverter Configuring Drive Parameters 3–59 Output Function Adjustment ParametersThe following parameters work in conjunction with the intelligent output function, when configured. The overload level parameter (C041) sets the motor current level at which the overload signal [OL] turns ON. The range of settings is from 0% to 200% of the rated current for the inverter. This function is for generating an early warning logic output , without causing either a trip event or a restriction of...
Page 143
“C” Group: Intelligent Terminal Functions Configuring Drive Parameters 3–60 Func. CodeName/ Description Keypad Range and Settings DefaultsRun Mode Edit Lo HiSRWOPEFEF2FE2 (EU) FUF2FU2 (USA) FF2F2 (Jpn) C038 Low current indication output mode select ON00Output during accele ration/deceleration and constant speed operation 01 01 01 ✘ ✔ CRT 0 1Output only during constant speed C039 Low current indication detec tion level 0.0 to 1.80 x rated inverter current Rated current x 1.0✘ ✔ Low current threshold,...
Page 144
SJ7002 Inverter Configuring Drive Parameters 3–61 Serial CommunicationsThe following table configures the communications port of the SJ7002 inverter. You can have up to thirty-two devices on the serial communications network. The inverters are slaves and the computer or digital operator is the master. Thus , all inverters on the serial connection must use the same baud rate, data length, parity, and stop bits. However, each device on the serial network must have a unique node address. See “ Serial...
Page 145
“C” Group: Intelligent Terminal Functions Configuring Drive Parameters 3–62 Analog Signal Calibration SettingsThe functions in the following table configure the signals for the analog output terminals. Note that these settings do not change the current/vo ltage or sink/source characteristics – only the zero and span (scaling) of the signals. NOTE: See additional settings for analog calibrat ion: Parameter B080 [AM] Terminal Analog Meter Adjustment (gain), parameter B081 [FM] Terminal Analog Meter...
Page 146
SJ7002 Inverter Configuring Drive Parameters 3–63 occurred, the inverter and motor will enter free-run stop (coasting) operati on. In some applica- tions, the motor and load will still be coasting when the inverter returns to normal Run Mode operation. For that situation, you can configure the inverter output (C103=00) to resume opera- tion from 0 Hz and accelerate normally. Or, yo u can configure the inverter (C103=01) to resume operation from the cu rrent speed of the motor (frequency...
Page 147
“C” Group: Intelligent Terminal Functions Configuring Drive Parameters 3–64 C139 Terminal [15] OFF-delay time — — 0.0 to 100.0 (seconds) 0.0 0.0 0.0✘ ✔ C140 Relay output ON-delay time — — 0.0 to 100.0 (seconds) 0.0 0.0 0.0✘ ✔ C141 Relay output OFF-delay time — — 0.0 to 100.0 (seconds) 0.0 0.0 0.0✘ ✔ C142 Logic output 1 function A — — All programmable output functions available (except LOG1 to LOG6)00 (output frequency) ✘ ✔ C143 Logic output 1 function B — — ✘ ✔ C144 Logic output 1 operator AND...
Page 148
SJ7002 Inverter Configuring Drive Parameters 3–65 Input Signal Terminal Functions Func. CodeName/ DescriptionRange and Settings DefaultsRun Mode Edit Lo Hi FEF2FE2 (EU) FUF2FU2 (USA) FF2F2 (Jpn) C160 Terminal [1] input response time 0. to 200. (x 2 ms) 0.0 0.0 0.0 ✘ ✔ C161 Terminal [2] input response time 0. to 200. (x 2 ms) 0.0 0.0 0.0 ✘ ✔ C162 Terminal [3] input response time 0. to 200. (x 2 ms) 0.0 0.0 0.0 ✘ ✔ C163 Terminal [4] input response time 0. to 200. (x 2 ms) 0.0 0.0 0.0 ✘ ✔ C164 Terminal...
Page 149
“H” Group: Motor Constants Functions Configuring Drive Parameters 3–66 “H” Group: Motor Constants Functions IntroductionThe “H” Group parame ters configure the inverter for the motor characteristics. You must manually set H003 and H004 values to match the motor. Most of the remaining parameters are related to vector control, and are in use only when function A044 is set for one of the vector control modes as shown in the diagram. The procedure in “ Auto-tuning of Motor Constants” on page 4–71...
Page 150
SJ7002 Inverter Configuring Drive Parameters 3–67 Func. CodeName/ Description Keypad Range and Settings DefaultsRun Mode Edit Lo HiSRWOPEFEF2FE2 (EU) FUF2FU2 (USA) FF2F2 (Jpn) H005 Motor speed constant, 1st motor 0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000) 1.590 1.590 1.590 ✔ ✔ Motor proportional gain constant, factory set H205 Motor speed constant, 2nd motor 0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000) 1.590 1.590 1.590 ✔ ✔ Motor proportional gain constant, factory set H006 Motor...