Page 121
“B” Group: Fine-Tuning Functions Configuring Drive Parameters 3–38 Software Lock ModeThe software lock function keeps personnel fro m accidentally changing parame ters in the inverter memory. Use B031 to select from various protection levels. The table below lists all combinati ons of B031 option codes and the ON/OFF state of the [SFT] input. Each Check ✔ or Ex ✘ indicates whether the corresponding parameter(s ) can be edited. The Standard Parameters column below lists Low and High level access for...
Page 122
SJ7002 Inverter Configuring Drive Parameters 3–39 Miscellaneous SettingsThe miscellaneous settin gs include scaling factors, initialization mode s, and others. This section covers some of th e most important settings you may need to configure. Function Display SettingsThe inverter has the (optional) capability to su ppress the display and editing of certain parame- ters. Use B037 to select the display options. The purpose of this feature is to hide particular secondary parameters that become unused...
Page 123
“B” Group: Fine-Tuning Functions Configuring Drive Parameters 3–40 A002 01, 03, 04, 05B087 Stop key function A019 00 A028 – A035 Multi-speed function C001 – C008 02, 03, 04, 05 Function CodeDataResulting Non-displayed Functions (when B37 = 01)Notes A044, A244 02 B100 – B113 Control methods A051 01 A052 – A059 DC braking A071 01 A072 – A076, C044 PID function A094 01 A095 – A096 2-stage adjustable frequency A294 01 A0295 – A296 B013, B213, B313 02 B015 – B020 Electric thermal characteris- tic B021...
Page 124
SJ7002 Inverter Configuring Drive Parameters 3–41 B098 01, 02 B099, C085 Thermistor function B050 01 B051 – B054 Instantaneous power failure B120 01 B121 – B126 External brake control Function CodeDataResulting Non-displayed Functions (when B37 = 01)Notes C021 – C025, C026 02, 06 C042, C043 Frequency arrival signal 03 C040, C041 Overload advance notice 07 C055 – C058 Over-torque 21 C063 Zero-speed detection signal 24, 25 C045, C046 Frequency arrival signal 26 C011 Overload advance notice 2 H002 00...
Page 125
“B” Group: Fine-Tuning Functions Configuring Drive Parameters 3–42 Controlled Deceleration at Power Loss – When enabled, this feature permits the inverter to control final motor deceleration upon loss of inverter input power. First, you must make a wiring change to the inverter. See “ Optional Controlled Decel and Alarm at Power Loss” on page 4–4 for complete instructions including wiring and signal timing diagrams for using the controlled decelera tion at power loss feature. After making the...
Page 126
SJ7002 Inverter Configuring Drive Parameters 3–43 If an instantaneous power failure has occurred while the inverter is operating the motor and the output voltage falls to the DC bus voltage trigger level dur ing power loss (b051) or less, the inverter reduces the output frequency by the initial output frequency decrease during power loss (b054) once, and then decelerates the motor for th e deceleration time setting during power loss (b053). If the voltage increases to an overvoltage le vel...
Page 127
“B” Group: Fine-Tuning Functions Configuring Drive Parameters 3–44 Window ComparatorsThe window comparator function controls digi tal outputs based on the comparison of analog input values to user-defined upper and lower limits. Miscellaneous FunctionsB083: Carrier frequency adjustment – The internal switching frequency of the inverter circuitry (also called the chopper frequency). It is called the carrier frequency because the lower AC output frequency of the inverter “rides” the carrier. The...
Page 128
SJ7002 Inverter Configuring Drive Parameters 3–45 B084, B085: Initialization codes – These functions allow you to restore the factory default settings. Please refer to “ Restoring Factory Default Settings” on page 6–16. B086: Frequency display scaling – You can convert the output frequency monitor on D001 to a scaled number (e ngineering units) monitore d at function D007. For example, the motor may run a conveyor that is monitored in fe et per minute. Use this formula: B091/B088: Stop Mode /...
Page 129
“B” Group: Fine-Tuning Functions Configuring Drive Parameters 3–46 NOTE: Other events can cause (or be configured to cause) a free-run stop, such as power loss (see “ Automatic Restart Mode and Phase Loss” on page 3–30), and inverter trip events in general (see “ Miscellaneous Functions” on page 3–62). If all free-run stop behavior is impor- tant to your applicat ion (such as HVAC), be sure to configure each event accordingly. Some additional parameters further configure all instances of a...
Page 130
SJ7002 Inverter Configuring Drive Parameters 3–47 B090: Dynamic braking usage ratio – This parameter limits the amount of time the inverter can use the dynamic braking accessory device with out entering the Trip Mode. Please refer to “ Dynamic Braking” on page 5–6 for more information on dynamic braking accessories. NOTE: When cooling fan control is enabled (B092=01) the inverter always turns the fan ON for five minutes immediately after powerup. This will cool the inverter in case the inverter /...