Hitachi Sj7002 Owners Manual
Here you can view all the pages of manual Hitachi Sj7002 Owners Manual. The Hitachi manuals for Inverter are available online for free. You can easily download all the documents as PDF.
Page 71
Using the Front Panel Keypad Inverter Mountingand Installation 2–30 Function Key – This key is used to navigate through the lists of parameters and functions for setting and monitoring parameter values. Up/Down ( , ) Keys – Use these keys alternately to move up or down the lists of parameter and func tions shown in the display, and increment/decrement values. Store ( ) Key – When the unit is in Program Mode and the operator has edited a parameter value, press the Store key to write the...
Page 72
SJ7002 Inverter Inverter Mountingand Installation 2–31 Keypad Navigational MapThe SJ7002 Series inverter drives have many programmable functions and parameters. Chapter 3 will cover these in detail, but you ne ed to access just a few items to perform the powerup test. The menu structure makes use of function codes and para meter codes to allow programming and monitoring with only a 4-digit display and a few keys and LEDs. So, it is important to become familiar wi th the basic navigational map of...
Page 73
Using the Front Panel Keypad Inverter Mountingand Installation 2–32 Selecting Functions and Editing Parame- tersIn order to run the motor for the powerup test, this section will show how to: select the inverter’s maximum output frequency to the motor select the keypad potentiometer as the source of motor speed command select the keypad as the source of the RUN command set the number of poles for the motor enable the RUN command The following series of programming tables are designed for...
Page 74
SJ7002 Inverter Inverter Mountingand Installation 2–33 Select the Potentiometer for Speed Command - The motor speed may be controlled from the following sources: Potentiometer on front pa nel keypad (if present) Control terminals Remote panel Then follow the steps in the table below to select the potentiometer for the speed command (the table resumes action from the end of the previous table). Select the Keypad for the RUN Command - The RUN command causes the inverter to accel- erate the motor to...
Page 75
Using the Front Panel Keypad Inverter Mountingand Installation 2–34 Configure the Inverter for the Number of Motor Poles - The number of magnetic poles of a motor is determined by the motor’s internal wi nding arrangement. The specifications label on the motor usually indica tes its number of poles. For prope r operation, verify the parameter setting matches the motor poles. Many industrial motors have four poles, corresponding to the default setting in the inverter. Follow the steps in the table...
Page 76
SJ7002 Inverter Inverter Mountingand Installation 2–35 Monitoring Parameters with the DisplayAfter using the ke ypad for parameter editing, it’s a good idea to switch the inverter from Program Mode to Monitor Mode. This will turn out the PRG LED, and the Hertz, Volt, Ampere, or % LED indicates the display units. For the powerup test, monitor the motor speed indirectly by viewing the inverter’s output frequency. The output frequency must not be confused with base frequency (50/60 Hz) of the...
Page 77
Using the Front Panel Keypad Inverter Mountingand Installation 2–36 St ep 1 0: Reading this section will help you make so me useful observations when first running the motor. Error Codes - If the inverter displays an error code (LED format is “ E--”), see “Monitoring Trip Events, History, & Conditions” on page 6–5 to interpret and clear the error. Acceleration and Deceleration - The SJ700 2 inverter has programmable acceleration and deceleration values. The test procedure left these at the...
Page 78
SJ7002 Inverter Inverter Mountingand Installation 2–37 Emergency Stop Function IntroductionThe SJ700 series inverter has the function of “uncontrolled stopping by removal of motor power” in accordance with Stop Category 0 defined by EN60204-1. The inverter is also designed to comply with Safety Category 3 of EN954-1. This func tion is generally called Safe Stop function. The emergency stop function shuts off the inverter output (i.e. stops the switch- ing operation of the main circuit elements) in...
Page 79
Emergency Stop Function Inverter Mountingand Installation 2–38 When the emergency stop function is enabled, intelligent input terminals [1] and [3] are used exclusively for this function, and no other functions can be assigned to these terminals. Even if other functions have been assigned to these te rminals, these are automatically disabled and these terminals are used exclusiv ely for the emergency stop function. Terminal [1] function – This terminal always serves as the “a” (N.O.) contact for...
Page 80
SJ7002 Inverter Inverter Mountingand Installation 2–39 turned OFF, terminal [2] function C002 and terminal [1] function C001 will remain as NO (no function assigned) and [RS] (code 18), respectively. Note 4: Function [EMR] (code 64) canno t be assigned to input terminal 3 by an operation from the digital operator. The function is au tomatically assigned to the terminal when slide switch SW1 is set to ON. Note 5: After slide switch SW1 has been set to ON once, function assignments to intelligent...
All Hitachi manuals