Page 241
Introduction Motor ControlAccessories 5–2 Introduction A motor speed control system will obviously incl ude a motor and inverter, as well as fuses for safety. If you are connecting a motor to the inverter on a test bench just to get started, that’s all you may need for now. But a fully developed sy stem can also have a variety of additional components. Some can be for noise suppressi on, while others may enhance the inverter’s braking performance. The figure below shows a system with several...
Page 242
SJ7002 Inverter Motor ControlAccessories 5–3 Component Descriptions AC Reactors, Input SideThis is useful in suppressing harmonics induced on the power su pply lines, or when the main power voltage imbalance exceeds 3% (and power s ource capacity is more than 500 kVA), or to smooth out line fluctu ations. It also improves the power factor. In the following cases for a general-purpose inve rter, a large peak current flows on the main power supply side, and is able to destroy the inverter module: If...
Page 243
Component Descriptions Motor ControlAccessories 5–4 Zero-phase Reactor (RF Noise Filter)Electrical noise interference may occur on nearby equipment such as a radio receiver. The zero-phase reactor helps reduce radiated noise from the inverter wiring. It can be used on the input or output side of the inverter. The example zero-phase reactor shown to the right comes with a mounting bracket. The wiring must go through the opening to reduce the RF component of the electri- cal noise. Loop the...
Page 244
SJ7002 Inverter Motor ControlAccessories 5–5 Expansion CardsThe SJ–FB Encoder Feedback Board installs in the inverter’s expansion bay, which can accept up to two expansion cards. The encoder card accepts two-channel incremental encoder signals. Position feedback is essential for certain torque-control algorithms, and is useful for improving low-speed performance. The card can also generate linear acceleration/deceleration ramps for velocity control. All wiring associated with this card connects...
Page 245
Dynamic Braking Motor ControlAccessories 5–6 Dynamic Braking IntroductionThe purpose of dynamic braking is to improve the ability of the inverter to stop (decelerate) the motor and load. This becomes necessary when an application has some or all of the following characteristics: High load inertia compared to the available motor torque The application requi res frequent or sudden changes in speed System losses are not great enough to slow the motor as needed When the inverter reduces its output...
Page 246
SJ7002 Inverter Motor ControlAccessories 5–7 Dynamic Braking Selection TablesThe SJ7002 Series 200V and 400V class inverter models in the 1/2 to 30 HP range have internal braking units. Additional stopping torque is avai lable by adding external resistors. The required braking torque depends on your part icular application. Other tables in this section will help you choose the prop er resistor. NOTE: For inverters larger than 30 HP (22kW), an external braking unit will be required. Contact your...
Page 248
Troubleshooting and Maintenance In This Chapter....page — Troubleshooting................................................................................ 2 — Monitoring Trip Events, History, & Conditions................................... 5 — Restoring Factory Default Settings................................................. 16 — Maintenance and Inspection........................................................... 17 —...
Page 249
Troubleshooting Troubleshooting and Maintenance 6–2 Troubleshooting Safety MessagesPlease read the following safety messages be fore troubleshooting or performing maintenance on the inverter and motor system. WARNING: Wait at least ten (10) minutes after turning OFF the input power supply before performing mainte nance or an inspection. Otherwise, th ere is the danger of electric shock. WARNING: Make sure that only qualified personnel will perform maintenance, inspection, and part replacement....
Page 250
SJ7002 Inverter Troubleshooting and Maintenance 6–3 Troubleshooting TipsThe table below lists typical symptoms and the corresponding solution(s). Symptom/conditionProbable CauseSolution The motor will not run. The inverter outputs U, V, W are not supplying voltage. • Is the frequency command source A001 parameter setting correct? • Is the Run command source A002 parameter setting correct? • Make sure the parameter setting A001 is correct. • Make sure the parameter setting A002 is correct. • Is...