    							PQMII POWER QUALITY METER  – INSTRUCTION MANUAL4–1
    PQMII Power Quality Meter
    Chapter 4: Software
    Digital Energy
    Softw are
    4.1 Introduction
    4.1.1 Overview
    Although setpoints can be manually entered using the front panel keys, it is far more 
    eff icient and easier to use a computer to download values through the communications 
    port . The no-charge EnerVista PQMII Setup Software included with the PQMII makes this a 
    quick and convenient process. With the EnerVista PQMII Setup Software running on your 
    PC, it is possible to:
    • Program and modify setpoints
    • Load/save setpoint f iles from/to disk
    • Read actual values and monitor status
    • Perform waveform capture and log data
    • Perform harmonic analysis
    • Trigger trace memory
    • Get help on any topic
    The EnerVista PQMII Setup Software allows immediate access to all the features of the 
    PQMII through pull-down menus in the familiar Windows environment . The software can 
    also run without a PQMII connected. This allows you to edit and save setpoint f iles for later 
    use. If a PQMII is connected to a serial port on a computer and communication is enabled, 
    the PQMII can be programmed from the setpoint screens. In addition, measured values, 
    status and alarm messages can be displayed with the actual screens. 
    						
    							4–2PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 4: SOFTWARE
    4.1.2 Hardware
    Communications from the EnerVista PQMII Setup Software to the PQMII can be 
    accomplished three ways: RS232, RS485, and Ethernet (requires the MultiNET adapter) 
    communications. The following f igures below illustrate typical connections for RS232 and 
    RS485 communications. For details on Ethernet communications, please see the MultiNET 
    manual.
    FIGURE 4–1: Communications using The Front RS232 Port 
    						
    							CHAPTER 4: SOFTWARE
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL4–3
    FIGURE 4–2: Communications using Rear RS485 Port
    4.1.3 Installing the EnerVista PQMII Setup Software
    The following minimum requirements must be met for the EnerVista PQMII Setup Software 
    to operate on your computer.
    • Microsoft Windows 95 or higher operating system
    • 64 MB of RAM (256 MB recommended)
    • Minimum of 50 MB hard disk space (200 MB recommended)
    After ensuring these minimum requirements, use the following procedure to install the 
    EnerVista PQMII Setup Software from the enclosed GE EnerVista CD.
    Insert the GE EnerVista CD into your CD-ROM drive.
    Click the Install Now button and follow the installation instructions to 
    install the no-charge EnerVista software on the local PC. 
    						
    							4–4PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 4: SOFTWARE
    When installation is complete, start the EnerVista Launchpad 
    application.
    Click the IED Setup section of the Launch Pad window.
    In the EnerVista Launch Pad window, click the Install Software button 
    Select the “PQMII Power Quality Meter” from the Install Software 
    window as shown below. 
    Select the “Web” option to ensure the most recent software release, or 
    select “CD” if you do not have a web connection. 
    Click the Check Now button to list software items for the PQMII.
    Select the PQMII software program and release notes (if desired) from 
    the list.
    Click the Download Now button to obtain the installation program from 
    the Web or CD. 
    EnerVista Launchpad will obtain the installation program. 
    						
    							CHAPTER 4: SOFTWARE
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL4–5
     
    Once the download is complete, double-click the installation program to 
    install the EnerVista PQMII Setup Software.
    The program will request the user to create a backup 3.5 floppy-disk 
    set. If this is desired, click on the Start Copying button; otherwise, 
    Click on the CONTINUE WITH PQMII VERSION 1.O1 
    INSTALLATION button.
    Select the complete path, including the new directory name, where the 
    EnerVista PQMII Setup Software will be installed.
    Click on Next to begin the installation. 
    The files will be installed in the directory indicated and the installation 
    program will automatically create icons and add EnerVista PQMII 
    Setup Software to the Windows start menu. 
    						
    							4–6PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 4: SOFTWARE
    Click Finish to end the installation. 
    The PQMII device will be added to the list of installed IEDs in the 
    EnerVista Launchpad window, as shown below. 
    						
    							CHAPTER 4: SOFTWARE
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL4–7
    4.2 Conf iguring Serial Communications
    4.2.1 Description
    Before starting, verify that the serial cable is properly connected to either the RS232 port 
    on the front panel of the device (for RS232 communications) or to the RS485 terminals on 
    the back of the device (for RS485 communications). See 4.1.2: Hardware for connection 
    details.
    Install and start the latest version of the EnerVista PQMII Setup 
    Software (available from the GE EnerVista CD). See the previous 
    section for the installation procedure.
    Click on the Device Setup button to open the Device Setup window.
    Click the Add Site button to define a new site.
    Enter the desired site name in the Site Name field. If desired, a short 
    description of site can also be entered along with the display order of 
    devices defined for the site. 
    Click the OK button when complete.
    The new site will appear in the upper-left list in the EnerVista PQMII 
    Setup Software window.
    Click the Add Device button to define the new device.
    Enter the desired name in the Device Name field and a description 
    (optional) of the site.
    Select “Serial” from the Interface drop-down list. 
    This will display a number of interface parameters that must be entered 
    for proper RS232 functionality.
    Enter the relay slave address and COM port values (from the 
    S1 PQMII 
    SETUP  FRONT PANEL RS232 SERIAL PORT
     setpoints menu) in the Slave 
    Address and COM Port fields.
    Enter the physical communications parameters (baud rate and parity 
    settings) in their respective fields.
    Click the Read Order Code button to connect to the PQMII device and 
    upload the order code. 
    If a communications error occurs, ensure that the PQMII serial 
    communications values entered in the previous step correspond to the 
    relay setting values.
    Click OK when the relay order code has been received. 
    The new device will be added to the Site List window (or Online 
    window) located in the top left corner of the main EnerVista PQMII 
    Setup Software window.
    The PQMII Site Device has now been conf igured for serial communications. 
    						
    							4–8PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 4: SOFTWARE
    4.3 Upgrading Firmware
    4.3.1 Description
    To upgrade the PQMII f irmware, follow the procedures listed in this section. Upon 
    successful completion of this procedure, the PQMII will have new f irmware installed with 
    the original setpoints.
    The latest f irmware f iles are available from the GE Multilin website at 
    http://www.GEmultilin.com.
    4.3.2 Saving Setpoints to a File
    Before upgrading f irmware, it is important to save the current PQMII settings to a f ile on 
    your PC. After the f irmware has been upgraded, it will be necessary to load this f ile back 
    into the PQMII.
    To save setpoints to a file, select the File > Read Device Settings menu 
    item.
    The EnerVista PQMII Setup Software will read the device settings and 
    prompt the user to save the setpoints file. 
    Select an appropriate name and location for the setpoint file.
    Click OK.
    The saved file will be added to the “Files” pane of the EnerVista PQMII 
    Setup Software main window.
    4.3.3 Loading New Firmware
    Select the Commands > Upgrade Firmware menu item.
    A warning will appear. 
    Select Ye s to proceed or No the abort the process. 
    Do not proceed unless you have saved the current setpoints as shown in 
    the previous section. 
    						
    							CHAPTER 4: SOFTWARE
    PQMII POWER QUALITY METER  – INSTRUCTION MANUAL4–9
    Locate the firmware file to load into the PQMII. 
    The firmware filename has the following format:
    Select the required file.
    Click on OK to proceed or Cancel to abort the firmware upgrade.
    One f inal warning will appear. This will be the last chance to abort the f irmware 
    upgrade. 
    Select Ye s to proceed, No to load a different file, or Cancel to abort the 
    process.
    The EnerVista PQMII Setup Software now prepares the PQMII to receive the new 
    f irmware f ile. The PQMII will display a message indicating that it is in Upload Mode. 
    While the f ile is being loaded into the PQMII, a status box appears showing how 
    much of the new f irmware f ile has been transferred and how much is remaining. 
    The entire transfer process takes approximately f ive minutes.
    73 D 210   C4 . 000
    Modification number (000 = none)
    For GE Multilin use only
    Product firmware revision (e.g. 100 = 1.00). This number
    must be larger than the current number of the PQMII. This
    number is found in actual values page A4 underSOFTWARE
    VERSIONS    MAIN PROGRAM VERSION
    Required product hardware revision. This letter must match
    the first character of the serial number located on the PQMII
    product label (on the back of the unit)
    Product Name (73 = PQMII) 
    						
    							4–10PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
    CHAPTER 4: SOFTWARE
    The EnerVista PQMII Setup Software will notify the user when the PQMII has 
    f inished loading the f ile. 
    Carefully read any displayed messages and click OK to return the main 
    screen.
    If the PQMII does not communicate with the EnerVista PQMII Setup Software, 
    ensure that the following PQMII setpoints correspond with the EnerVista PQMII 
    Setup Software settings:
    MODBUS COMMUNICATION ADDRESS
    BAUD RATE
    PARIT Y
     (if applicable)
    Also, ensure that the correct COM port is being used.
    4.3.4 Loading Saved Setpoints
    Select the previously saved setpoints file from the File pane of the 
    EnerVista PQMII Setup Software main window.
    Select the setpoint file to be loaded into the PQMII.
    Click OK.
    Select the File > Edit Settings File Properties menu item and change 
    the file version of the setpoint file to match the firmware version of the 
    PQMII.
    With the updated setpoint file selected in the File pane, select the File > 
    Write Settings to Device menu item and select the target PQMII to 
    receive the previously saved settings file.
    A dialog box will appear to confirm the request to download setpoints. 
    Click Ye s to send the setpoints to the PQMII or No to end the process.
    The EnerVista PQMII Setup Software will load the setpoint f ile into the PQMII. If new 
    setpoints were added in the f irmware upgrade, they will be set to factory defaults. 
    						