    							PQMII POWER QUALITY METER  – INSTRUCTION MANUALA–1
    PQMII Power Quality Meter
    Appendix A
    Digital Energy
    Appendix A
    A.1 Mod 506: Capacitor Bank Switching
    A.1.1 Description
    The standard PQM software has been altered to allow the four output relays to be used for 
    4 step capacitor bank switching.
    A.1.2 Setpoints
    The following messages have been added to the PQMII setpoint structure to 
    accommodate this modif ication. The messages are located in setpoints page 
    S4 ALARMSCONTROLMOD 506 SETPOINTS (after the MISCELLANEOUS heading).
    PATH: SETPOINTS  S4 ALARMS/CONTROL  MOD 506 SETPOINTS
     MOD 506 []
    SETPOINTSSTEP 1 RELAY:
    OFFRange: Alarm, Aux1, Aux2, Aux3, Off
    MESSAGESTEP 1 PICKUP ≥
    +600 kvarRange: 0.1 to 6500.0 kvar in steps of 
    0.1
    MESSAGESTEP 1 DROPOUT ≤
    0.0 kvarRange: –3250.0 to 3250.0 kvar in steps 
    of 0.1
    MESSAGESTEP 1 PICKUP
    DELAY: 1.0 minRange: 0.1 to 60.0 min in steps of 0.1
    MESSAGESTEP 1 DISABLE
    TIME: 5.0 minRange: 0.1 to 60.0 min in steps of 0.1
    MESSAGESTEP 2 RELAY:
    OFFRange: Alarm, Aux1, Aux2, Aux3, Off
    MESSAGESTEP 2 PICKUP ≥
    +600 kvarRange: 0.1 to 6500.0 kvar in steps of 
    0.1 
    						
    							A–2PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
       APPENDIX A
    •STEP 1(4) RELAY: The state of the output relay assigned in this message will be 
    controlled by the 
    STEP it is assigned to. Once a relay has been assigned to a particular 
    step, it will not activate upon any other PQMII conditions (i.e. pulse output , alarm, etc.). 
    If a particular relay has not been assigned to any 
    STEP, it will function as per standard 
    PQMII implementation.
    •STEP 1(4) PICKUP: When the three-phase kvar value is positive and it becomes equal 
    to or exceeds the value set in this setpoint the output relay assigned to the 
    STEP will 
    energize providing the conditions in all other setpoints are met .
    MESSAGESTEP 2 DROPOUT ≤
    0.0 kvarRange: –3250.0 to 3250.0 kvar in steps 
    of 0.1
    MESSAGESTEP 2 PICKUP
    DELAY: 1.0 minRange: 0.1 to 60.0 min in steps of 0.1
    MESSAGESTEP 2 DISABLE
    TIME: 5.0 minRange: 0.1 to 60.0 min in steps of 0.1
    MESSAGESTEP 3 RELAY:
    OFFRange: Alarm, Aux1, Aux2, Aux3, Off
    MESSAGESTEP 3 PICKUP ≥
    +600 kvarRange: 0.1 to 6500.0 kvar in steps of 
    0.1
    MESSAGESTEP 3 DROPOUT ≤
    0.0 kvarRange: –3250.0 to 3250.0 kvar in steps 
    of 0.1
    MESSAGESTEP 3 PICKUP
    DELAY: 1.0 minRange: 0.1 to 60.0 min in steps of 0.1
    MESSAGESTEP 3 DISABLE
    TIME: 5.0 minRange: 0.1 to 60.0 min in steps of 0.1
    MESSAGESTEP 4 RELAY:
    OFFRange: Alarm, Aux1, Aux2, Aux3, Off
    MESSAGESTEP 4 PICKUP ≥
    +600 kvarRange: 0.1 to 6500.0 kvar in steps of 
    0.1
    MESSAGESTEP 4 DROPOUT ≤
    0.0 kvarRange: –3250.0 to 3250.0 kvar in steps 
    of 0.1
    MESSAGESTEP 4 PICKUP
    DELAY: 1.0 minRange: 0.1 to 60.0 min in steps of 0.1
    MESSAGESTEP 4 DISABLE
    TIME: 5.0 minRange: 0.1 to 60.0 min in steps of 0.1
    MESSAGESYSTEM STABILIZATION
    TIME: 5.0 minRange: 0.1 to 60.0 min in steps of 0.1
    MESSAGELOW VOLTAGE LEVEL:
    100 VRange: 30 to 65000 V in steps of 10 or 
    OFF
    MESSAGELOW VOLTAGE DETECT
    DELAY: 1.0 sRange: 0.5 to 600.0 s in steps of 0.5
    MESSAGESTEP PRIORITY:
     1, 2, 3, 4Range: 24 combinations 
    						
    							APPENDIX A
    PQMII POWER QUALITY METER  – INSTRUCTION MANUALA–3
    •STEP 1(4) DROPOUT: When the three-phase kvar value becomes less than or equal to 
    the value set in this setpoint the output relay assigned to the 
    STEP will de-energize. 
    Since over compensation is possible, the dropout value can be set to negative vars.
    •STEP 1(4) PICKUP DELAY: The 
    STEP will turn on after the delay set in this setpoint has 
    elapsed assuming all other conditions have been met .
    NoteThis delay setting will start counting down once the SYSTEM STABILIZATION TIME setting 
    has elapsed.
    STEP 1(4) DISABLE TIME: When 
    STEP turns off, it is not allowed to turn back on until the 
    time set in this setpoint has elapsed. This allows the capacitors to discharge before 
    being re-energized again.
    •SYSTEM STABILIZATION TIME: When any action is performed (turning 
    STEPS on/off or 
    low voltage is detected), the system must be allowed to stabilize for the time set in this 
    setpoint before any further actions can be performed. This time is necessary to allow 
    the system to stabilize without the capacitors trying to recharge
    •LOW VOLTAGE LEVEL: When the system voltage (average three-phase voltage) 
    becomes equal to or less than this setpoint , all 
    STEPS are turned off. Upon recovery 
    (three-phase voltage is greater than this setpoint) the time set in the 
    SYSTEM 
    STABILIZATION TIME
     setpoint must have elapsed before any actions will be performed. If 
    this feature is not required, set it to “Off ”.
    •LOW VOLTAGE DETECT DELAY: In some cases where noise or spikes are present on 
    the line it may not be desirable to detect low voltage right away, therefore, this 
    setpoint can be used to delay the detection until voltage is def initely low.
    •STEP PRIORITY: The 
    STEP PRIORITY setpoint determines the sequence the STEPS are 
    allowed to turn on in a case where the condition may be satisf ied by more than one 
    STEP. Therefore, the STEP with the highest priority will be energized f irst . If the STEP 
    with highest priority is already energized, the 
    STEP with second highest priority will be 
    used, and so forth. The 
    STEP priority is set from highest to lowest (left to right) when 
    viewing this setpoint . For example, “1,2,3,4” signif ies that 
    STEP 1 has the highest 
    priority and 
    STEP 4 has the lowest priority. Note that only one STEP is allowed to turn 
    on or off at a time.
    NoteEnervista PQMII setup software does not support any MODs. The settings and metering
    values under this MOD can be accessed using the unit front panel or the Modbus analyzer
    tools. 
    A.1.3 Actual Values
    The following messages have been added to the PQMII actual values structure to 
    accommodate this modif ication. The messages are located in actual values page 
    A2 STATUSMOD 506 ACTUAL VALUES. 
    						
    							A–4PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
       APPENDIX A
    PATH: ACTUAL VALUES  A2 STATUS  MOD 506 ACTUAL VALUES
    •PICKUP TIMERS: These timers are loaded with the STEP 1(4) PICKUP DELAY setpoint 
    settings when the required conditions are met . The timers are displayed beginning 
    with 
    STEP 1 on the left and ending with STEP 4 on the right .
    •DISABLE TIMERS: These timers are loaded with the 
    STEP 1(4) DISABLE TIME setpoint 
    settings when the required conditions are met . The timers are displayed beginning 
    with 
    STEP 1 on the left and ending with STEP 4 on the right .
    •SYSTEM STABILIZATION TIMER: This timer is continuously loaded with the 
    SYSTEM 
    STABILIZATION TIME
     setpoint setting and will only start to count down to 0 when the 
    system becomes stable.
    •LOW VOLTAGE DETECT TIMER: This timer is loaded with the 
    LOW VOLTAGE DETECT DELAY 
    setpoint setting when low voltage is detected and will start to count down to 0.
    NoteIf the power to the PQMII is removed all timers are cleared to 0.
    A.1.4 Conditions Required to Energize a STEP
    The following conditions are required to energize STEP 1. The same conditions apply to 
    STEPS 2 through 4.
    • Three-phase voltage is greater than the 
    LOW VOLTAGE LEVEL setting.
    • The system kvars are equal to or have exceeded the setting in 
    STEP 1 PICKUP 
    setpoint .
    • The programmed 
    SYSTEM STABILIZATION TIME has elapsed.
    • The programmed 
    STEP 1 PICKUP DELAY has elapsed.
    •
    STEP 1 has the highest priority as set in the STEP PRIORITY setpoint or all other STEPS 
    do not meet all of the above conditions.
     MOD 506 []
    ACTUAL VALUESPICKUP TIMERS (min) 
    0.0 0.0 0.0 0.0
    MESSAGEDISABLE TIMERS (min) 
    0.0 0.0 0.0 0.0
    MESSAGESYSTEM STABILIZATION
    TIMER: 5.0 min
    MESSAGELOW VOLTAGE DETECT
    TIMER: 0.0 s 
    						
    							APPENDIX A
    PQMII POWER QUALITY METER  – INSTRUCTION MANUALA–5
    A.1.5 Additions to Modbus Memory Map
    The following two sections are added to the Modbus Memory Map for Mod 506..
    The following memory map format has also been added:
    GROUPADDR
    (HEX)DESCRIPTIONRANGESTEP VALUEUNITS and
    SCALEFOR-MATFACTORY DEFAULT
    MOD 506 
    ACTUAL 
    VALUES0E10 Step 1 Pickup T imer --- --- 0.1 x F1 ---
    0E11 Step 2 Pickup T imer --- --- 0.1 x F1 ---
    0E12 Step 3 Pickup T imer --- --- 0.1 x F1 ---
    0E13 Step 4 Pickup T imer --- --- 0.1 x F1 ---
    0E14 Step 1 Disable T imer --- --- 0.1 x F1 ---
    0E15 Step 2 Disable T imer 0.1 x F1 ---
    0E16 Step 3 Disable T imer --- --- 0.1 x F1 ---
    0E17 Step 4 Disable T imer --- --- 0.1 x F1 ---
    0E18 System Stabilization --- --- 0.1 x F1 ---
    0E19 Low Voltage Detect --- --- 0.1 x F1 ---
    MOD 506 
    SETPOINTS1300 Step 1 Relay 0 to 4 1 --- F1 0 = OFF
    1301 Step 1 Pickup Level 1 to 65000 1 kvar F1 6000=600.0 kvar
    1302 Step 1 Dropout Level–32000 to 
    320001 kvar F2 0=0.0 kvar
    1303 Step 1 Pickup Delay 1 to 600 1 min F1 10=1.0 min
    1304 Step 1 Disable T ime 1 to 600 1 min F1 50=5.0 min
    1305 Step 2 Relay 0 to 4 1 --- F1 0 = OFF
    1306 Step 2 Pickup Level 1 to 65000 1 kvar F1 6000=600.0 kvar
    1307 Step 2 Dropout Level–32000 to 
    320001 kvar F2 0=0.0 kvar
    1308 Step 2 Pickup Delay 1 to 600 1 min F1 10=1.0 min
    1309 Step 2 Disable T ime 1 to 600 1 min F1 50=5.0 min
    130A Step 3 Relay 0 to 4 1 --- F1 0 = OFF
    130B Step 3 Pickup Level 1 to 65000 1 kvar F1 6000=600.0 kvar
    130C Step 3 Dropout Level–32000 to 
    320001 kvar F2 0=0.0 kvar
    130D Step 3 Pickup Delay 1 to 600 1 min F1 10=1.0 min
    130E Step 3 Disable T ime 1 to 600 1 min F1 50=5.0 min
    130F Step 4 Relay 0 to 4 1 --- F1 0 = OFF
    1310 Step 4 Pickup Level 1 to 65000 1 kvar F1 6000=600.0 kvar
    1311 Step 4 Dropout Level–32000 to 
    320001 kvar F2 0=0.0 kvar
    1312 Step 4 Pickup Delay 1 to 600 1 min F1 10=1.0 min
    1313 Step 4 Disable T ime 1 to 600 1 min F1 50=5.0 min
    1314 System Stabilization 1 to 600 1 min F1 50=5.0 min
    1315Low Voltage Detect 
    Level30 to 
    650001 V F1 100 V
    1316Low Voltage Detect 
    Delay5 to 6000 1 s F1 10=1.0 s
    1317 Step Sequence 0 to 23 1 --- F42 0=“1,2,3,4”
    CODE DESCRIPTION BITMAS
    K
    F42 Step Sequence PriorityFFFF
    0 = “1, 2, 3, 4” ---
    1 = “1, 2, 4, 3” ---
    2 = “1, 3, 2, 4” --- 
    						
    							A–6PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
       APPENDIX A
    3 = “1, 3, 4, 2” ---
    4 = “1, 4, 2, 3” ---
    5 = “1, 4, 3, 2” ---
    6 = “2, 1, 3, 4” ---
    7 = “2, 1, 4, 3” ---
    8 = “2, 3, 1, 4” ---
    9 = “2, 3, 4, 1” ---
    10 = “2, 4, 1, 3” ---
    11 = “2, 4, 3, 1” ---
    12 = “3, 1, 2, 4” ---
    13 = “3, 1, 4, 2” ---
    14 = “3, 2, 1, 4” ---
    15 = “3, 2, 4, 1” ---
    16 = “3, 4, 1, 2” ---
    17 = “3, 4, 2, 1” ---
    18 = “4, 1, 2, 3” ---
    19 = “4, 1, 3, 2” ---
    20 = “4, 2, 1, 3” ---
    21 = “4, 2, 3, 1” ---
    22 = “4, 3, 1, 2” ---
    23 = “4, 3, 2, 1” ---
    CODE DESCRIPTION BITMAS
    K 
    						
    							APPENDIX A
    PQMII POWER QUALITY METER  – INSTRUCTION MANUALA–7
    A.2 Revision History
    A.2.1 Release Dates
    A.2.2 Release Notes
    Table A–1: Release Dates
    MANUAL GE PART NO. PQMII 
    REVISIONRELEASE DATE
    GEK-106435 1601-0118-A1 1.0x 17 September 2003
    GEK-106435A 1601-0118-A2 1.0x 06 November 2003
    GEK-106435B 1601-0118-A3 2.0x 01 December 2003
    GEK-106435C 1601-0118-A4 2.0x 02 December 2003
    GEK-106435D 1601-0118-A5 2.1x 18 June 2004
    GEK-106435E 1601-0118-A6 2.2x Not released
    GEK-106435F 1601-0118-A7 2.2x 15 May 2006
    GEK-106435G 1601-0118-A8 2.2x 22 February 2007
    GEK-106435H 1601-0118-A9 2.2x 1 October 2007
    GEK-106435J 1601-0118-AA 2.2x 4 March 2008
    GEK-106435K 1601-0118-AB 2.2x 25 November 2008
    GEK-106435L 1601-0118-AC 2.2x 1 April 2009
    GEK-106435M
    (GEK-106475D) 1601-0118-AD
    (1601-0130-A5)
    2.2x 21 May 2010
    GEK-106435N
    (GEK-106475E) 1601-0118-AE
    (1601-0130-A6)
    2.2x 16 March 2012
    Table A–2: Major Updates for GEK-106435N (GEK-106475E) 
    SECT 
    (AD) SECT
    (AE) CHANGE DESCRIPTION
    T itle T itle Update Manual part number to 1601-0120-AE (1601-0130-A6)
    1.5.2 1.5.2 Added MOD 525 addition
    1.5.3 1.5.3 Update RS485 Accessory update 
    						
    							A–8PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
       APPENDIX A
    Table A–3: Major Updates for GEK-106435M (GEK-106475D) 
    SECT 
    (AC)SECT
    (AD)CHANGE DESCRIPTION
    T itle T itle Update Manual part number to 1601-0120-AD (1601-0130-A5)
    1.5.2 1.5.2 Update MOD 506 update
    A.1.2 A.1.2 Added Note added
    Table A–4: Major Updates for GEK-106435L 
    SECT 
    (AB)SECT
    (AC)CHANGE DESCRIPTION
    T itle T itle Update Manual part number to 1601-0120-AC
    --- --- Update New Communications Guide (formerly Ch.7)
    1.6.1 1.6.1 Update Revised Current Inputs section
    5.5.1 5.5.1 Added Note added
    6.4.5 6.4.5 Update SAG Voltage references
    Table A–5: Major Updates for GEK-106435J 
    SECT 
    (A9)SECT
    (AA)CHANGE DESCRIPTION
    T itle T itle Update Manual part number to 1601-0120-AA
    All All Update Re-establish all cross-references
    Table A–6: Major Updates for GEK-106435H 
    SECT
    (A8)SECT
    (A9)CHANGE DESCRIPTION
    T itle T itle Update Manual part number to 1601-0120-A9
    8.6.4 8.6.4 Update (p.19) T ime Stamping - sampling time accuracy 
    						
    							APPENDIX A
    PQMII POWER QUALITY METER  – INSTRUCTION MANUALA–9
    Table A–7: Major Updates for GEK-106435G 
    PA G
    E
    (A7)SECT
    (A8)CHANGE DESCRIPTION
    T itle T itle Update Manual part number to 1601-0120-A8
    1.6.1 Update Voltage Input Specif ication change
    5.2.6 Text Addn. Modbus time and date setting
    2.2.8 Text Change Switch Input
    Table A–8: Major Updates for GEK-106435F 
    PA G
    E
    (A5)PA G
    E
    (A7)CHANGE DESCRIPTION
    T itle T itle Update Manual part number to 1601-0120-A7
    7-9 7-9 Update Updated Modbus Memory Map
    7-58 7-58 Update Updated Default Variations section
    7-59 7-59 Update Updated Binary Input/ Binary Input Change section
    7-62 7-62 Update Updated Analog Input/Output Change section 
    						
    							A–10PQMII POWER QUALITY METER  – INSTRUCTION MANUAL
       APPENDIX A 
    						